This document contains an amendment to a federal solicitation for the purchase of a 48V solar battery bank. The amendment provides answers to contractor questions, including that lithium-ion batteries will not meet requirements and dimensions cannot be provided as the building has not been constructed. It also attaches an EnergyCell REHC battery data sheet specifying the technical details and specifications of battery models from 800RE to 2700RE to be supplied, including dimensions, weights, voltages, capacities, and warranty information. The quote due date remains September 6, 2023 at 2pm PDT.

View the file

Other files for this federal contract opportunity

Other files attached to PURCHASE 48V SOLAR BATTERY BANK, newest first.
File Type Posted
Sol_140P8123Q0118.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(x)

140P8123Q0118 x x copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted ; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGEMENT TO BE

RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR

OFFER. If by virtue of this amendment you desire to change an offer already submitted , such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

x

PPL

Boulder City NV 89005-2426 601 Nevada Way

NPS, PWR - LAKE MABO

08/28/20230001

13. THIS ITEM ONLY APPLIES TO MODIFICATION OF CONTRACTS/ORDERS. IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

12. ACCOUNTING AND APPROPRIATION DATA (If required) is not extended.is extended, Items 8 and 15, and returning

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended , by one of the following methods: (a) By completing

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

FACILITY CODE CODE

10B. DATED (SEE ITEM 13)

10A. MODIFICATION OF CONTRACT/ORDER NO.

9B. DATED (SEE ITEM 11)

9A. AMENDMENT OF SOLICITATION NO.

CODE

8. NAME AND ADDRESS OF CONTRACTOR (No., street, county, State and ZIP Code)

7. ADMINISTERED BY (If other than Item 6)CODE 6. ISSUED BY

PAGE OF PAGES

4. REQUISITION/PURCHASE REQ. NO.3. EFFECTIVE DATE2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO. (If applicable)

1. CONTRACT ID CODE

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

08/24/2023

CHECK ONE A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority) appropriation data, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

E. IMPORTANT: Contractor is not is required to sign this document and return __________________ copies to the issuing office.

ORDER NO. IN ITEM 10A.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

See Continuation Page

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)15A. NAME AND TITLE OF SIGNER (Type or print)

15C. DATE SIGNED 16B. UNITED STATES OF AMERICA 15B. CONTRACTOR/OFFEROR 16C. DATE SIGNED

(Signature of person authorized to sign) (Signature of Contracting Officer)

Caroline Bachelier

STANDARD FORM 30 (REV. 11/2016)

Prescribed by GSA FAR (48 CFR) 53.243

Previous edition unusable

Except as provided herein, all terms and conditions of the document referenced in Item 9 A or 10A, as heretofore changed, remains unchanged and in full force and effect .

140P8123Q0118 Amendment 0001

The purpose of this amendment is to answer contractor questions and add Energy Cell REHC Data Sheet.

A. Contractor questions and answers are provided as follows:

Question 1: Can you provide the AH capacity for the battery pack or a picture of the existing battery nameplate?

Answer 1: See attached data sheet.

Question 2: Can you provide a picture or dimensions for the floor and wall space these will fit into?

Answer 2: We cannot prove a photo of the space because the concrete building has not been installed yet. The size of the building is 10’x13’.

Question 3: Is the Government open to a lithium-ion battery pack to eliminate the watering and venting requirements?

Answer 3: Lithium will not work for this set up, they can cause too many issues with the heat and if the go dead it is too much work to get them boosted. Th watering system helps with heat dissipation and keeping the batteries functional.

B. The quote due date remains the same, Sep 6, 2023, at 2pm PDT.

• 1,800 cycles @ 50% depth of discharge

• Space-saving 4×6 standard 48V system configuration

• Battery frame design allows for maximum heat dissipation

• 100% out of box initial battery capacity

• VRLA-AGM technology: 99% gas recombination efficient, no periodic watering of cells, no re-torquing of terminal connections and no equalization charge under standard operating conditions

• Steel module design, cells factory installed in permanent steel modules with 1 or 2 cells per can, allowing for ease of replacement

• Flame-retardant battery jars for increased safety

• OPTICS RE™ connectivity means real-time access to critical battery performance data

The EnergyCell™ RE High Capacity battery family offers an ideal solution for large applications requiring the use of Valve Regulated Lead Acid (VRLA) batteries.

The EnergyCell™ RE High Capacity battery’s modular design concept with steel-can casing and its integral racking system provide a cost-effective battery system with a compact, quick and simple installation process. The battery system’s cell design, with Absorbed Glass Mat (AGM) technology, incorporates thicker positive plates for longer battery life. The welded/epoxy dual-post sealed design provides the highest integrity battery casing in the industry—large copper post design also enhances high rate performance.

The module’s protective steel can encases the cells to maintain constant, uniform compression for the life of the battery. The easy-to-assemble racking provides total flexibility for system configuration and allows fast, simple installation even in the most difficult locations. The EnergyCell RE High Capacity battery, with its optimized recombination chemistry and extra thick plates, has excellent performance, extended service life and low maintenance requirements for grid-interactive and off-grid renewable energy and UPS applications.

EnergyCell™ RE High Capacity 2V VRLA AGM Battery

SUB PANELLOAD ENERGYCELL™ RE-HC

POWER FLOW

GRID MAIN PANEL

FLEXPOWER™ TWO

PV SOURCE

Alpha Technologies Services, Inc. 3767 Alpha Way, Bellingham, WA 98226 Tel: +1 360 435 6030 Technical Support: +1 360 618 4363 Email: sales@outbackpower.com For more information visit: www.outbackpower.com © 2022 EnerSys. All Rights Reserved. Trademarks and logos are the property of Alpha Technologies Services, Inc., EnerSys and its affiliates unless otherwise noted. Subject to revisions without prior notice. E. & O.E.

Discharge in Hours:

2V Ampere Hour Capacity to 1.75 Volts Per Cell @ 77°F (25°C)

1 5 8 20 24 100

EnergyCell 800RE 347 555 600 672 676 810

EnergyCell 1100RE 495 790 864 960 984 1150

EnergyCell 1300RE 575 920 1008 1148 1176 1340

EnergyCell 1600RE 690 1105 1208 1378 1416 1600

EnergyCell 2000RE 886 1390 1512 1716 1776 2070

EnergyCell 2200RE 920 1470 1616 1836 1872 2140

EnergyCell 2700RE 1182 1850 2016 2288 2352 2770

EnergyCell™ Models*: 800RE 1100RE 1300RE 1600RE 2000RE 2200RE 2700RE

Nominal Voltage per Cell: 2V 2V 2V 2V 2V 2V 2V

Nominal Voltage per System: 24VDC / 48VDC 24VDC / 48VDC 24VDC / 48VDC 24VDC / 48VDC 24VDC / 48VDC 24VDC / 48VDC 24VDC / 48VDC

Cycle Life (50% DOD, 1.75VPC): 1800 1800 1800 1800 1800 1800 1800

Absorb Voltage (25°C): 55.6VDC 55.6VDC 55.6VDC 55.6VDC 55.6VDC 55.6VDC 55.6VDC

Absorb Time: 2hrs 2hrs 2hrs 2hrs 2hrs 2hrs 2hrs

Float Voltage (25°C): 54VDC 54VDC 54VDC 54VDC 54VDC 54VDC 54VDC

Float Time: = absorb time = absorb time = absorb time = absorb time = absorb time = absorb time = absorb time

Equalize Voltage: 2.32VDC 2.32VDC 2.32VDC 2.32VDC 2.32VDC 2.32VDC 2.32VDC

Re-Bulk Voltage: 24VDC / 48VDC 24VDC / 48VDC 24VDC / 48VDC 24VDC / 48VDC 24VDC / 48VDC 24VDC / 48VDC 24VDC / 48VDC

Re-Float Voltage: 12.5VDC / 25VDC / 50VDC 12.5VDC / 25VDC / 50VDC 12.5VDC / 25VDC / 50VDC 12.5VDC / 25VDC / 50VDC 12.5VDC / 25VDC / 50VDC 12.5VDC / 25VDC / 50VDC 12.5VDC / 25VDC / 50VDC

Maximum Charge Current (per Battery): 148.75A 212.5A 250A 300A 375A 400A 500A

Operating Temperature Range (with Temperature Compensation):

–4 to 122°F (–20 to 50°C)

–4 to 122°F (–20 to 50°C)

–4 to 122°F (–20 to 50°C)

–4 to 122°F (–20 to 50°C)

–4 to 122°F (–20 to 50°C)

–4 to 122°F (–20 to 50°C)

–4 to 122°F (–20 to 50°C)

Optimal Operating Temperature Range: 68 to 86°F (20 to 30°C) 68 to 86°F (20 to 30°C) 68 to 86°F (20 to 30°C) 68 to 86°F (20 to 30°C) 68 to 86°F (20 to 30°C) 68 to 86°F (20 to 30°C) 68 to 86°F (20 to 30°C)

Temp-Comp Factor (Charging): ±5mV / °C / 2V cell ±5mV / °C / 2V cell ±5mV / °C / 2V cell ±5mV / °C / 2V cell ±5mV / °C / 2V cell ±5mV / °C / 2V cell ±5mV / °C / 2V cell

Self-Discharge Time: 6 months @ 25°C 6 months @ 25°C 6 months @ 25°C 6 months @ 25°C 6 months @ 25°C 6 months @ 25°C 6 months @ 25°C

Terminal Type: M8 bolt, lock, flat washer M8 bolt, lock, flat washer M8 bolt, lock, flat washer M8 bolt, lock, flat washer M8 bolt, lock, flat washer M8 bolt, lock, flat washer M8 bolt, lock, flat washer

Terminal Hardware Initial Torque: 88in-lbs 88in-lbs 88in-lbs 88in-lbs 88in-lbs 88in-lbs 88in-lbs

Weight (lb/kg): 2262 / 1189.3 3797 / 1722.3 4330 / 1964.1 5082 / 2305.2 6464 / 2932.0 6707 / 3042.2 8266 / 3749.4

48V System Dimensions H × D × W (in/cm):

43.44 × 23.5 × 39.40 / 110 × 59.69 × 10

60.7 × 23.5 × 37.15 /

154.2 × 59.69 × 94.36

77.96 × 26.25 × 33.32 /

198.0 × 66.68 × 84.63

77.96 × 26.25 × 33.32 /

198.0 × 66.68 × 84.63

74.92 × 27.46 × 44.37 /

190.3 × 69.75 × 11.27

77.96 × 26.25 × 56.37 /

198.0 × 66.68 × 14.32

74.92 × 27.46 × 56.37 /

190.3 × 69.75 × 143.2

Warranty**: 3 years 3 years 3 years 3 years 3 years 3 years 3 years

48V Standard System Configuration: 6w × 4h 4w × 6h 3w × 8h 3w × 8h 4w × 6h 3w × 8h 4w × 6h

*Consult local and regional electrical code for proper installation of energy storage requirements.

**Consult EnergyCell™ RE High Capacity Battery warranty documentation for all terms and conditions.

03/2022

#980-0071-01-00 REV C

EnergyCell™ RE High Capacity Battery Specifications

File details come from the government source that posted it. Updated .