Questions/ Answers Part 2

1) Do these existing tanks have an Electronic Monitoring System currently attached to them? If so, what make and model is it and does it need to be re-installed onto the new tank or should it be replaced?

a. No, we do not have an electronic monitoring system

2) How are these tanks filled? Is it from a pressurized pumping system which would need to be attached to the tank in order to make the overfill valve in the tank work properly? Is that coupling system a standard 2" or 3"?

a. Yes, it is a pressurized pumping system, coupling is 2"

3) Do to the current steel shortages and the ability to obtain U.S. Made Steel Products, would it be possible to use either double wall flexible piping for the supply and return lines or rubber coated flexible steel braided hoses inside of a chase pipe from the tank to the Generator building?

a. Yes, as long as it meets codes and standards

4) By looking at the pictures, it would appear that there is only one pipe going to the

Generator, where is the return line from the generator to the tank?

a. Yes, the return line is from the generator to the tank

5) Can both the supply and return lines be run together in a chase pipe between the tank and the Generator building?

a. Yes

6) Are you specifying a certain Tank Manufacturer and Tank type beyond UL-2085?

a. No

7) Are you requiring a specific external coating type for the tank due to its location?

a. This is a highly corrosive marine environment, if not wrapped cement it should have some kind of marine specialty coating.