OVERALL HEIGHT MAY BE GREATER DEPENDING ON
MOTOR, ADAPTER, AND/OR HINGE BASE.
19.00 SQ
1.75
13.44 15.25
Ø 22.25
27.75
(12.50)
Model: CUE-095-VG Direct Drive Upblast Centrifugal Roof Exhaust Fan
Dimensional Quantity 1
Weight w/o Acc's (lb) 34
Weight w/ Acc's (lb) 40
Weight w/ Acc's and Curb (lb) 66
Standard Curb Cap Size (in.) 19 x 19
Optional Damper (in.) 10 x 10
Roof Opening (in.) 15.5 x 15.5
Performance Requested Volume (CFM) 900
Actual Volume (CFM) 900
Total External SP (in. wg) 0.125
Fan RPM 1465
Operating Power (hp) 0.09
Elevation (ft) 105
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.075
Tip Speed (ft/min) 4,172 Static Eff. (%) 19
Misc Fan Data Fan Eff. Index (FEI) -
Outlet Velocity (ft/min) 776
Motor Motor Mounted Yes
Size (hp) 1/6
Voltage/Cycle/Phase 115/60/1
Enclosure TENV
Motor RPM 1725
Efficiency Rating High
Windings 1 FLA (Amps) 2.3
Min. Circuit Ampacity (MCA) 3 Max. Overcurrent Protection (MOP) 15
Short Circuit Current Rtg (SCCR) 5 kA
Notes:
All dimensions shown are in units of in.
*NEC FLA, MCA and MOP are for reference only – based on tables 430.248 or 430.25 of National Electric Code 2020. Actual motor FLA may vary, for sizing thermal overload, consult factory.
MCA and MOP values shown only account for the motor, not accessories (damper actuator, field supplied VFD, etc).
LwA - A weighted sound power level, based on ANSI S1.4 dBA - A weighted sound pressure level, based on 11.5 dB attenuation per Octave band at 5 ft - dBA levels are not licensed by AMCA International Sones - calculated using ANSI/AMCA 301 at 5 ft
Sound Power by Octave Band Sound Data 62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones
Inlet 74 74 72 64 56 59 53 45 68 56 8.4
Cut Sheet - Not for Submittal 04/17/2023Printed Date:
Mark 1 (900 CFM)Mark:
CUE-095-VGModel:
Generated by: cwiginton@hdgrant.comCAPS 4.41.968 Page 1 of 11 H:\Greenheck\Jobs\Chris U\Gray & Green Lab Fan.gfcj
Model: CUE-095-VG Direct Drive Upblast Centrifugal Roof Exhaust Fan Standard Construction Features:
- Aluminum housing - Backward curved composite (sizes 60-95) or aluminum (sizes 99-300) wheel - Aluminum curb cap with prepunched mounting holes - Drain trough - Ball bearing motors (sizes 85-300 and all Vari Green), sleeve bearing motors (sizes 60-80) - Motor isolated on shock mounts - Corrosion resistant fasteners Selected Options & Accessories:
Motor - Vari-Green EC motor Control - Dial for balancing Standard Curb Cap Size - 19 Square UL/cUL 705 Listed - "Power Ventilators" Switch, NEMA-1, Toggle, Shipped with Unit Junction Box Mounted & Wired High Wind Rated (+/- 150 PSF Rating) Florida Product Approval #FL13225.1 & Miami-Dade NOA #22-0606.03 Foam Curb Seal (Factory Applied) Birdscreen: Stainless Steel, nom. 89% Free Area Composite Wheel Material Unit Warranty: 1 Yr (Standard) Damper Shipped Loose, BD-100-PB-10X10, Gravity Operated, Not Coated, Nominal Size Selected Sub Marks See individual submittals for full details
GPF-19-G12
The Vari-Green Motor included in this order has a ‘Multi-Voltage’ ability. The red wire on the motor is called a ‘Voltage Doubler’, and when it is connected the motor can be powered by 115V.
If the Red wire is disconnected, then the motor can be powered with 208-230/277V. The motor will leave the factory with the voltage doubler wired per the order.
Cut Sheet - Not for Submittal 04/17/2023Printed Date:
Mark 1 (900 CFM)Mark:
CUE-095-VGModel:
Generated by: cwiginton@hdgrant.comCAPS 4.41.968 Page 2 of 11
Disconnect Switch Enclosure Rating: NEMA-1 Standard Construction Features:
Enclosure constructed for indoor use to provide a degree of protection to personnel against incidental contact with the enclosed equipment and to provide a degree of protection against falling dust. This enclosure meets the rod entry and the indoor corrosion protection design tests. The rod entry test is intended to simulate incidental contact with enclosure equipment.
Enclosure is equipped with provision to lockout in the off position with customer supplied lock.
Notes: All dimensions shown are in units of in.
Electrical Drawing Details
Wiring Schematic
4.35
2.50
2.000.72 1.06
1.65
1.06
Ø0.28
(4 HOLES)
Disconnect Switch Configuration Type: Toggle Motor Size: 1/6 hp Voltage: 115 UL Listed: Yes Manufacturer: Pass and Seymour Cycle: 60 Amperage: 15 CSA Approved: Yes Overload Protection: None Phase: 1 Switch Pole(s): 1 Rating: 1/2 hp Junction Box Mtg.: Mounted and Wired RPM: 1725 Exp. Resist. Wiring: None Switch Mounting: Shipped With Unit
Cut Sheet - Not for Submittal 04/17/2023Printed Date:
Mark 1 (900 CFM)Mark:
CUE-095-VGModel:
Generated by: cwiginton@hdgrant.comCAPS 4.41.968 Page 3 of 11
Assembly Drawing Type: Direct Drive Upblast Centrifugal Roof Exhaust Fan
RECOMMENDED EXHAUST DUCT SIZE
STANDARD 10 SQ
DUCT TYPE SIZE
MAXIMUM ROOF OPENING
OVERALL HEIGHT MAY BE GREATER DEPENDING ON
MOTOR, ADAPTER, AND/OR HINGE BASE.
DUCT DIMENSIONS ARE LARGEST POSSIBLE DUCT TO FIT THROUGH CURB.
CONSULT SYSTEM DESIGN ENGINEER FOR RECOMMENDED DUCT SIZE.
19.00 SQ
1.75
13.44 15.25
Ø 22.25
27.75
(12.50)
15.50
SQ
19.00 SQ
Curb Cap
Notes: All dimensions shown are in units of in..
Cut Sheet - Not for Submittal 04/17/2023Printed Date:
Mark 1 (900 CFM)Mark:
CUE-095-VGModel:
Generated by: cwiginton@hdgrant.comCAPS 4.41.968 Page 4 of 11
Vari-Green Motor & Control Options An EC motor that uses AC input power and internally converts it to DC power. Potentiometer (dial) mounted on the motor enclosure adjusts the speed (RPM) down 80%. Vari-Green motors feature a soft-start and inherent thermal and current protection built into each unit. Inrush current at start up is eliminated and the motor will automatically reduce speed or turn off if overloaded or it becomes too hot.
Motor Configuration Input Voltage: 115 Speed Reference: Dial on Motor Permanent Dial: Yes
Control Configuration Control Type: N/A Transformer: None
Cut Sheet - Not for Submittal 04/17/2023Printed Date:
Mark 1 (900 CFM)Mark:
CUE-095-VGModel:
Generated by: cwiginton@hdgrant.comCAPS 4.41.968 Page 5 of 11
DAMPER TYP. SECTION VIEW
10 5.5
2.5
Standard Construction Features:
- Model BD-100 is a horizontal mount exhaust damper (air flow up) and is constructed of 24 ga galvanized steel with pre-punched mounting holes - Damper blades are 0.016 in. roll formed aluminum with vinyl seals on the closing edge, and spring assisted for ease of opening - Axle/bearing is constructed of fiberglass reinforced nylon
Notes: All dimensions shown are in units of in.
Horizontal Mount Exhaust Damper Model: BD-100
Cut Sheet - Not for Submittal 04/17/2023Printed Date:
Mark 1 (900 CFM)Mark:
CUE-095-VGModel:
Generated by: cwiginton@hdgrant.comCAPS 4.41.968 Page 6 of 11
CUE-095-VG Min/Max Fan Curve
Performance Requested
Volume
(CFM)
Actual Volume
(CFM)
Total External SP (in. wg)
Fan
RPM
Operating Power (hp)
900 900 0.125 1465 0.09
Cut Sheet - Not for Submittal 04/17/2023Printed Date:
Mark 1 (900 CFM)Mark:
CUE-095-VGModel:
Generated by: cwiginton@hdgrant.comCAPS 4.41.968 Page 7 of 11
WARRANTY AND LIABILITY: SELLER warrants to Buyer that products manufactured are free from defects in material and workmanship for a period of 1 Yr (Standard) from the date of shipment. SELLER's obligations and liabilities under this warranty are limited to furnishing FOB factory or warehouse at SELLER's designated shipping point, freight allowed to Buyer's city, (or point of export for shipments outside the conterminous United States) replacement equipment (or at the option of SELLER parts therefore) for all Seller's products not conforming to this warranty and which have been returned to the manufacturer. No liability whatever shall attach to SELLER until said products have been paid for and such liability shall be strictly limited to the purchase price of the equipment shown to be defective. Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by SELLER prove defective during this period, they should be returned to the nearest authorized motor service station. SELLER will not be responsible for any removal or installation costs. Electrical components, excluding motors, are warranted only to the extent warranted by the original manufacturer. To the extent that SELLER is entitled to pass through a warranty of the original equipment manufacturer of the electrical goods sold, SELLER will pass through such warranties to Buyer. The legal remedies described in this Warranty are the sole exclusive remedy of Buyer. SELLER MAKES NO OTHER WARRANTY, EITHER EXPRESS OR IMPLIED, REGARDING ITS PRODUCTS, OR ITS SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITH BUILDING CODES, SAFETY CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This warranty is extended solely to the Buyer. It is nontransferable and non-assignable, and the Buyer shall not permit or authorize its employees, agents, representatives or customers to claim, represent or imply that this limited warranty extends or is available to anyone other than the Buyer. ANY MISUSE, NEGLECT, FAILURE TO FOLLOW INSTRUCTIONS OR MANUALS OF INSTALLATION OF MAINTENANCE REPAIR, SERVICE, RELOCATION OR ALTERATION TO OR OF, OR OTHER TAMPERING WITH, THE PRODUCTS PERFORMED BY ANY PERSON OR ENTITY OTHER THAN SELLER WITHOUT SELLER'S PRIOR WRITTEN APPROVAL OR ANY USE OF REPLACEMENT PARTS NOT SUPPLIED BY SELLER, SHALL IMMEDIATELY VOID AND CANCEL ALL WARRANTIES WITH RESPECT TO THE AFFECTED PRODUCTS. THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESSED OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR USE. SELLER PROVIDES NO INDEPENDENT WARRANTY FOR THIRD PARTY PRODUCTS OR COMPONENTS SOLD TOGETHER OR INCORPORATED WITH SELLER'S PRODUCT(S). THE SELLER HAS THE
RIGHT TO SETTLE ANY AND ALL DISPUTES REGARDING THE WARRANTY.
Warranty 1 Yr (Standard)
Cut Sheet - Not for Submittal 04/17/2023Printed Date:
Mark 1 (900 CFM)Mark:
CUE-095-VGModel:
Generated by: cwiginton@hdgrant.comCAPS 4.41.968 Page 8 of 11
AMCA
AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) does not include transmission losses.
Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation type A: Free inlet, Free outlet. Power rating (BHP/kW) does not include transmission losses. Performance ratings do not include the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5
ft. (1.5 m) in a hemispherical free field calculated per ANSI/AMCA Standard 301. Values shown are for installation type A: free inlet hemispherical sone levels. dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal applies to sone ratings only.
Cut Sheet - Not for Submittal 04/17/2023Printed Date:
Mark 1 (900 CFM)Mark:
CUE-095-VGModel:
Generated by: cwiginton@hdgrant.comCAPS 4.41.968 Page 9 of 11
21.75 21.75
12.50
17.75 17.75 Model: GPF Roof Curb Standard Construction Features:
- Roof Curb fits between the building roof and the fan mounted directly to the roof support structure - Constructed of either 18 ga galvanized steel or 0.064 in.
aluminum - Straight Sided without a cant - 2 in. or 5 in. mounting flange - 1 in.
thick 3 lb density insulation - Height - Available from 8 in. to 42 in. as specified in
0.5 in. increments. Notes: - The maximum roof opening dimension should not be greater than the "Actual" top outside dimension minus 2 in.. - The minimum roof opening dimension should be at least 2.5 in. more than the damper dimension or recommended duct size. - The Roof Opening Dimension may or may not be the same as the Structural Opening Dimension. - Damper Tray is optional and must be specified. Tray size is same as damper size. - Security bars are optional and must be specified. Frames and gridwork are all 12 ga steel. Gridwork is welded to the frame and the frame is welded to the curb.
***This curb can be mounted on the roof or wall (with a sidewall mounted CUE or CUBE fan).
General
Tag Qty Model Sizing
Method Undersizing
(in.)
Weight
(lb) Shipped
Assembled Union Label
1 GPF-19 Nominal 1.25 26 Yes No Preference
Dimensions
Curb Height
(in.)
Nominal Outside Width (in.)
Nominal Outside Length
(in.)
Actual Outside Width (in.)
Actual Outside Length
(in.)
Actual Inside Width (in.)
Actual Inside Length
(in.)
Flange Width (in.)
Flange Length
(in.)
Hinge Base
Width* (in.)
Hinge Base
Length* (in.)
12.5 19 19 17.75 17.75 14.25 14.25 21.75 21.75 18 18 *May not be applicable
Accessories
Material Security
Bars Liner Insulation
(in.)
Insulation R Value
Galvanized No No 1 R4.3
Cut Sheet - Not for Submittal 04/17/2023Printed Date:
Mark 1 (900 CFM)Mark:
GPF-19-G12Model:
Generated by: cwiginton@hdgrant.comCAPS 4.41.968 Page 10 of 11
October 21, 2022
Subject: Greenheck High Wind Certified Models
To whom it may concern:
Greenheck has tested and certified a number of models to meet the Miami Dade Building Code Compliance Office hurricane and high wind standards. In addition all products are also certified by the Florida Building Council with a Florida Product Approval number for use in areas of Florida not governed by the Miami Dade regulations. All products are tested and certified by an independent third party for use in high wind and hurricane areas.
The chart below lists the applicable information for each of the certified models. A complete certification report can be found on the Miami-Dade website for the Notice of Acceptance (NOA) numbers (www.miamidade.gov) or the Florida Building Code website for the FLPA numbers (www.floridabuilding.org).
Fan Model Available Sizes Protocols Tested
Miami-Dade NOA FLPA Number Max. Wind
Load - PSF
G/GB 060-300
TAS-201
TAS-202
TAS-203
22-0606.03 FL13225.1 150
CUE/CUBE 060-300 22-0606.03 FL13225.1 150
FGI/FGR
Intake 54x54
Relief 66x66
21-1122.09 FL12917.1
Steel - 70
Aluminum - 40
R Series Rooftop
Prop
Unfiltered 18-48
Filtered 18-42
21-1122.09 FL12917.1
Steel - 70
Aluminum - 40
RSF 90-200 22-0606.02 FL41062.1 40
Cut Sheet - Not for Submittal 04/17/2023Printed Date:
Generated by: cwiginton@hdgrant.comCAPS 4.41.968 Page 11 of 11
NOA No. 22-0606.03 Expiration Date: September 23, 2024
Approval Date: July 28, 2022
MIAMI-DADE COUNTY
PRODUCT CONTROL SECTION
11805 SW 26 Street, Room 208 DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) Miami, Florida 33175-2474
BOARD AND CODE ADMINISTRATION DIVISION T (786) 315-2590 F (786) 315-2599
NOTICE OF ACCEPTANCE (NOA) www.miamidade.gov/economy
Greenheck Fan Corporation 1110 Greenheck Drive (PO Box 410) Schofield, WI 54476
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The documentation submitted has been reviewed and accepted by Miami-Dade County RER-Product Control Section to be used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami-Dade County Product Control Section (In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance if it is determined by Miami-Dade County Product Control Section that this product or material fails to meet the requirements of the applicable building code.
This product is approved as described herein and has been designed to comply with the Florida Building Code, including the High Velocity Hurricane Zone.
DESCRIPTION: Series CUE/CW, CUBE/CWB, S-CUBE and G/GB Aluminum Rooftop and Sidewall Mounted Exhaust Fans APPROVAL DOCUMENT: Drawing No. HSA3001 to HSA3009, titled “Cue/Cube, G/GB and CW/CWB- 060-300”, sheets 1 through 9 of 9, dated 05/11/2022, prepared by Greenheck Fan Corporation, signed and sealed by Wayne K. Helmila, P.E., bearing the Miami-Dade County Product Control revision stamp with the Notice of Acceptance number and expiration date by the Miami-Dade County Product Control Section.
MISSILE IMPACT RATING: Large and Small Missile Impact Resistant LIMITATION: Models G-060 through G-133 and GB-071 through GB-131 are not Large Missile Impact Resistant.
LABELING: A permanent label with the manufacturer's name or logo, manufacturing plant’s city, state, model/series, and following statement: "Miami-Dade County Product Control Approved", is to be located on each unit.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami-Dade County, Florida, and followed by the expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official.
This NOA revises NOA # 21-1129.02 and consists of this page 1 and evidence pages E-1, E-2, E-3, E-4, E-5, E-6 and E-7, as well as approval document mentioned above.
The submitted documentation was reviewed by Carlos M. Utrera, P.E.
utrera New Stamp
Carlos M. Utrera, P.E.
Product Control Examiner
NOA No. 22-0606.03 Expiration Date: September 23, 2024
E - 1
Greenheck Fan Corporation
NOTICE OF ACCEPTANCE: EVIDENCE SUBMITTED
1. Evidence submitted under previous NOA’s
A. DRAWINGS “Submitted under NOA # 13-0220.08”
1. Drawing No. HSA3001 to HSA3008, titled “Cue/Cube, G/GB and CW/CWB-060-300”, sheets 1 through 8 of 8, dated 04/02, 05/26, 05/27, 05/29, 06/04/2009 and 01/12/2012, prepared by the manufacturer, signed and sealed by L. David Rice, P.E.
B. TESTS “Submitted under NOA # 13-0220.08”
1. Test report on 1) Uniform Static Air Pressure Test per FBC, TAS 202-94
2) Large Missile Impact Test per FBC, TAS 201-94,
3) Cyclic Wind Pressure Test per FBC, TAS 203-94, along with marked-up drawings and installation diagram of Model Cube-300, CUBE-161/HP and CUE-075 Rooftop Ventilating Fans, prepared by Architectural Testing, Inc., Test Report No. C0120.01-602-18, dated 08/07/2012, with revision 2 dated 05/28/2013, signed and sealed by Shawn G. Collins, P.E.
2. Test report on 1) Uniform Static Air Pressure Test per FBC, TAS 202-94
2) Large Missile Impact Test per FBC, TAS 201-94,
3) Cyclic Wind Pressure Test per FBC, TAS 203-94, along with marked-up drawings and installation diagram of Model GB-300, GB-161/HP and
GB-141/HP Rooftop Ventilating Fans, prepared by Architectural Testing, Inc., Test Report No.
C0120.02-602-18, dated 08/07/2012, with revision 2 dated 05/28/2013, signed and sealed by Shawn G. Collins, P.E.
“Submitted under NOA # 12-0120.13”
3. Test report on Large Missile Impact Test per FBC, TAS 201-94 of Model Cube-300 Side Wall Ventilating Fans, prepared by Architectural Testing, Inc., Test Report No. B3520.01-602-18, dated 11/18/2011, signed and sealed by Shawn G. Collins, P.E.
“Submitted under NOA # 09-0624.09”
4. Test report on 1) Uniform Static Air Pressure Test per FBC, TAS 202-94
2) Large Missile Impact Test per FBC, TAS 201-94,
3) Cyclic Wind Pressure Test per FBC, TAS 203-94, along with marked-up drawings and installation diagram of Model Cube-300 Belt Drive
Rooftop Ventilating Fans, prepared by Architectural Testing, Inc., Test Report No. 88029.01- 602-18, dated 02/04/2009, signed and sealed by Joseph A. Reed, P.E.
5. Test report on 1) Uniform Static Air Pressure Test per FBC, TAS 202-94
2) Large Missile Impact Test per FBC, TAS 201-94,
3) Cyclic Wind Pressure Test per FBC, TAS 203-94, along with marked-up drawings and installation diagram of Model GB-300 Belt Drive Rooftop
Ventilating Fans, prepared by Architectural Testing, Inc., Test Report No. 88799.01-602-18, dated 04/06/2009, signed and sealed by Joseph A. Reed, P.E.
NOA No. 22-0606.03 Expiration Date: September 23, 2024
E - 2
C. CALCULATIONS “Submitted under NOA # 13-0220.08”
1. Anchor verification calculations, prepared by Rice Engineering, dated 03/05/2012, signed and sealed by L. David Rice, P.E.
“Submitted under NOA # 12-0120.13”
2. Anchor verification calculations, prepared by Rice Engineering, dated 03/05/2012, “Submitted under NOA # 09-0624.09”
3. Anchor verification calculations, prepared by Rice Engineering, dated 06/12/2009, D. QUALITY ASSURANCE
1. Miami-Dade Department of Regulatory and Economic Resources (RER)
E. MATERIAL CERTIFICATIONS
1. None.
F. STATEMENTS “Submitted under NOA # 16-0209.05”
1. Statement letter of code conformance to the 5th edition (2014) FBC issued by Rice Engineering, dated 01/06/2016, signed and sealed by L. David Rice, P.E.
“Submitted under NOA # 14-0731.03”
2. Statement letter of code conformance to 2010 FBC, issued by Rice Engineering, dated
07/22/2014, signed and sealed by L. David Rice, P.E.
“Submitted under NOA # 13-0220.08”
3. No financial interest letter issued by Rice Engineering, dated 01/17/2013, signed and sealed by L. David Rice, P.E.
NOA No. 22-0606.03 Expiration Date: September 23, 2024
E - 3
2. Evidence submitted under NOA #19-0205.08
A. DRAWINGS
1. Drawing No. HSA3001 to HSA3008, titled “Cue/Cube, G/GB and CW/CWB-060- 300”, Sheets 1 through 8 of 8, dated 04/02, 05/26, 05/27, 05/29, 06/04/2009 and 01/12/2012, prepared by Greenheck Fan Corporation, signed and sealed by Wayne K.
Helmila, P.E. on 01/21/2019.
B. TESTS
C. CALCULATIONS
1. Anchor verification calculations prepared by Rice Engineering, dated 01/15/2019, signed and sealed by Wayne K. Helmila, P.E.
F. STATEMENTS
1. Statement letter of code conformance to the 6th edition (2017) FBC, dated 01/14/2019, issued by Rice Engineering, signed and sealed by Wayne K. Helmila, P.E.
2. Statement letter of no financial interest issued by Rice Engineering, dated 01/14/2019, signed and sealed by Wayne K. Helmila, P.E.
NOA No. 22-0606.03 Expiration Date: September 23, 2024
E - 4
3. Evidence submitted under NOA # 19-0717.02
300”, Sheets 1 through 8 of 8, dated 04/02, 05/26, 05/27, 05/29, 06/04/2009 and 01/12/2012, prepared by Greenheck Fan Corporation, signed and sealed by Wayne K.
Helmila, P.E. on 09/05/2019.
1. Statement letter of code conformance to the 6th edition (2017) FBC, dated 09/03/2019, issued by Rice Engineering, signed and sealed by Wayne K. Helmila, P.E.
2. Statement letter of no financial interest issued by Rice Engineering, dated 09/03/2019, signed and sealed by Wayne K. Helmila, P.E.
G. OTHERS
1. Test proposal #19-0535.
NOA No. 22-0606.03 Expiration Date: September 23, 2024
E - 5
4. Evidence submitted under NOA # 21-0318.05
300”, Sheets 1 through 8 of 8, dated 04/02, 05/26, 05/27, 05/29, 06/04/2009 and 01/12/2012, prepared by Greenheck Fan Corporation, signed and sealed by Robert J.
Amoruso, P.E. on 03/08/2021.
1. Curb to deck/sidewall mounting anchor calculations for the rooftop and sidewall mounted fans, prepared by PTC Product Design Group, LLC, dated 02/24/2021, signed and sealed by Robert J. Amoruso, P.E.
1. Miami-Dade Department of Regulatory and Economic Resources (RER).
1. Statement letter of code conformance to the 7th edition (2020) of the FBC and of no financial interest, dated 03/08/2021, issued by PTC Product Design Group, LLC, signed and sealed by Robert J. Amoruso, P.E.
NOA No. 22-0606.03 Expiration Date: September 23, 2024
E - 6
5. Evidence submitted under NOA # 21-1129.02
300”, sheets 1 through 8 of 8, dated 04/02, 05/26, 05/27, 05/29, 06/04/2009 and 01/12/2012, with revision 8 dated 10/19/2021, prepared by Greenheck Fan Corporation, signed and sealed by Robert J. Amoruso, P.E.
1. Statement letter of code conformance to the 7th edition (2020) of the FBC and of no financial interest, dated 10/19/2021, issued by PTC Product Design Group, LLC, signed and sealed by Robert J. Amoruso, P.E.
NOA No. 22-0606.03 Expiration Date: September 23, 2024
E - 7
6. New evidence submitted
1. Drawing No. HSA3001 to HSA3009, titled “Cue/Cube, G/GB and CW/CWB-060-
300”, sheets 1 through 9 of 9, dated 05/11/2022, prepared by Greenheck Fan Corporation, signed and sealed by Wayne K. Helmila, P.E.
1. Fan anchor calculations, prepared by Rice Engineering, dated 07/08/2022, signed and sealed by Wayne K. Helmila, P.E.
1. Statement letter of code conformance to the 7th edition (2020) of the FBC, dated 07/08/2022, issued by Rice Engineering, signed and sealed by Wayne K. Helmila, P.E.