Questions_asked_in_regards_to_Fire_Extinguisher_0001.docx
DOCX document 15 KB Posted
- Attached to
- FIRE EXTINGUISHERS/FIRE SPRINKLERS/BFLOW Federal contract opportunity
- Solicitation number
- 140L3924Q0045
About this file
This document contains questions asked in regards to the Fire Extinguisher/Fire Sprinklers/Backflow solicitation number 140L3924Q0045. The key details are:
The solicitation is for fire extinguishers, fire sprinklers, and backflow preventers. It includes details on the existing fire alarm control panels, fire suppression systems, sprinkler system testing, and quantities of various fire protection equipment at two facilities - the Silver State Hotshots Operations Center and the Palomino Fire Station. Specific details are provided on the number of wet sprinkler risers, tamper switches, waterflow switches, and backflow preventers at each site. No dry sprinkler risers, pre-action systems, fire pumps, or kitchen hood suppression systems are present. The Silver State facility has one special hazards suppression system (Kidde IND-21 fuel room). The document does not contain a full Performance Work Statement or Statement of Objectives, but rather a list of questions and responses related to the existing fire protection systems and equipment.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140L3924Q0045_Amd_0003.pdf | ||
| A06_Fire_Ext_Bid_Schedule_0003.xlsx | XLSX spreadsheet | |
| Sol_140L3924Q0045_Amd_0002.pdf | ||
| Sol_140L3924Q0045_Amd_0001.pdf | ||
| Sol_140L3924Q0045.pdf | ||
| B03-_Wage_Determination_Carson_City.txt | TXT text file | |
| SOW_Fire_backflows_and_Extingushers_2_9_23.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Questions asked in regards to Fire Extinguisher/Fire Sprinklers/Backflow- Solicitation Number 140L3924Q0045
1. The make/model of the Fire Alarm Control Panel(s). (Silver State 1 Yaskawa Vanguard E7, Palomino 2 Leviton Model 5200)
1. The type of fire suppression systems at the Silver State Hotshots Operations Center and Palomino Fire Station. (Palomino and Silver State are both Hydraulic (wet) systems)
1. When was the last time there was a 5 year internal obstruction test performed on the Fire Sprinkler System? (Never has been done)
1. Quantities for the following items broken out by building.
Wet Sprinkler Risers (2 at Palomino, 1 at Silver State) Dry Sprinkler Risers (None) Tamper Switches (2 at Palomino, 1 at Silver State.)
Waterflow Switches (2 at Palomino, 1 at Silver State) Pre-Action Systems (computer rooms) (None) Manual Pull Stations ( I believe there are 8 pull stations at Silver State however, could not confirm).
Smoke Detectors (For Palomino, not part of the system) Heat Detector (None) Duct Smoke Detectors (None) Fire & Smoke Dampers (None) Fire Extinguishers (Please refer to SOW) Backflow Preventers (Fire & Domestic) (Palomino 2 fire, 1 domestic, 1 agriculture. For Silver State 1 fire, 1 domestic, 1 agriculture).
Fire Pumps (None) Kitchen Hood Suppression Systems (None) Special Hazards Suppression (FM-200, Halon Systems, etc.) (Silver State 1 Kidde IND-21 fuel room)