Q&A_NIFC_205-PAR_AHU.docx
DOCX document 86 KB Posted
- Attached to
- 205-PAR Air Handling Unit Replacements Federal contract opportunity
- Solicitation number
- 140L3718R0005
About this file
Q&As
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140L3718R0005_Amd_0003.pdf | ||
| B03_DOL_Wage_Determination.pdf | ||
| Past_Performance_Questionaire.doc | DOC document | |
| Sol_140L3718R0005_Amd_0002.pdf | ||
| Davis_Bacon_Wages.pdf | ||
| NIFC_205-PAR_AHU_Replace_Prologue.pdf | ||
| NIFC_205-PAR_AHU_Replace_Specs.pdf | ||
| Sol_140L3718R0005.pdf | ||
| B03_Wage_Rate_Determination.pdf | ||
| Past_Performance_Questionaire.doc | DOC document | |
| NIFC_205-PAR_AHU_Replace_Plans.pdf | ||
| NIFC_205-PAR_AHU_Replace_Bid_Schedule.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
United States Department of the Interior
BUREAU OF LAND MANAGEMENT
Fire and Aviation 3833 S Development Ave Boise, Idaho 83705-5354
January 26, 2018 Amendment
NIFC 205-Paraloft AHU Replacements
1. Q: In relation to drawing page M301, under “Building DDC and Mulitzone AHU Units Sequence of Operation”, section “Boiler and Heating Water System”, East and West Perimeter fintube control. Section states “Replace control valve and actuator with DDC control valve with similar CV, size, and port configuration”. Is any additional information available on the existing valve such as Model Number, Cv, or flow for the two perimeter HW loop valves?
A: For bidding purposes the existing valves are Honeywell with a Cv of 11.7. Per the plans the line size is 1 ¼”. Field verification of actual requirements prior to ordering is required.
--end---image1.jpeg image2.png