NIFC_205-PAR_AHU_Replace_Plans.pdf
PDF 7 MB Posted
- Attached to
- 205-PAR Air Handling Unit Replacements Federal contract opportunity
- Solicitation number
- 140L3718R0005
About this file
Plans/Drawings
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140L3718R0005_Amd_0003.pdf | ||
| Q&A_NIFC_205-PAR_AHU.docx | DOCX document | |
| B03_DOL_Wage_Determination.pdf | ||
| Past_Performance_Questionaire.doc | DOC document | |
| Sol_140L3718R0005_Amd_0002.pdf | ||
| Davis_Bacon_Wages.pdf | ||
| NIFC_205-PAR_AHU_Replace_Bid_Schedule.pdf | ||
| NIFC_205-PAR_AHU_Replace_Prologue.pdf | ||
| NIFC_205-PAR_AHU_Replace_Specs.pdf | ||
| Sol_140L3718R0005.pdf | ||
| B03_Wage_Rate_Determination.pdf | ||
| Past_Performance_Questionaire.doc | DOC document |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL LEGEND
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
HVAC ABBREVIATIONS
AFF ABOVE FINISHED FLOOR
ACFM ACTUAL CFM
AHU AIR HANDLING UNIT
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
AMP AMPERE (AMP,AMPS)
APD AIR PRESSURE DROP
APPROX APPROXIMATE
BHP BRAKE HORSEPOWER, BOILER HORSEPOWER
BTU BRITISH THERMAL UNIT
MBH BTU PER HOUR (THOUSAND)
CU FT CUBIC FEET
CU IN CUBIC INCH
CFM CUBIC FEET PER MINUTE
SCFM CFM, STANDARD CONDITIONS
DB DECIBEL
DIA, Ø DIAMETER
ID DIAMETER, INSIDE
OD DIAMETER, OUTSIDE
DBT DRY-BULB TEMPERATURE
EAT ENTERING AIR TEMPERATURE
E.C. ELECTRICAL CONTRACTOR
EDR EQUIVALENT DIRECT RADIATION
EXP EXPANSION
EWT ENTERING WATER TEMPERATURE
F FAHRENHEIT
FPM FEET PER MINUTE
FPS FEET PER SECOND
FT FOOT OR FEET
HZ FREQUENCY
GA GAGE OR GAUGE
GAL GALLONS
G.C. GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPD GALLONS PER DAY
HD HEAD
HGT HEIGHT
HP HORSEPOWER
RH HUMIDITY, RELATIVE
KW KILOWATT
KWH KILOWATT HOUR
LAT LEAVING AIR TEMPERATURE
LWT LEAVING WATER TEMPERATURE
LF LINEAR FEET
MAX MAXIMUM
M.C. MECHANICAL CONTRACTOR
MIN MINIMUM
N O NORMALLY OPEN
N C NORMALLY CLOSED
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
NO NUMBER
OBD OPPOSED BLADE DAMPER
OA OUTSIDE AIR
% PERCENT
PH PHASE(ELECTRICAL)
LBS POUNDS
PSI POUNDS PER SQUARE INCH
PSIA PSI ABSOLUTE
PD PRESSURE DROP OR DIFFERENCE
PSIG PSI GAUGE
R/O RUN OUT
RH RELATIVE HUMIDITY
RA RETURN AIR
RPM REVOLUTIONS PER MINUTE
SH SENSIBLE HEAT
SPEC SPECIFICATION
SP VOL SPECIFIC VOLUME
STD STANDARD
SP STATIC PRESSURE
SUCT SUCTION
SA SUPPLY AIR
TEMP TEMPERATURE
TD TEMPERATURE DIFFERENCE
T STAT THERMOSTAT
TONS TONS OF REFRIGERATION
T.C. TEMPERATURE CONTROL
VAC VACUUM
VAV VARIABLE AIR VOLUME
VEL VELOCITY
V VOLT
VOL VOLUME
VFD VARIBLE FREQUENCY DRIVE
WPD WATER PRESSURE DROP
W/ WITH
AIR HANDLING UNIT SOUND DATA
UNIT TYPE
UNIT SOUND POWER (dB)
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz
MZ-1
RADIATED 91 86 74 72 65 53 46 51
UNIT DISCHARGE 101 96 92 93 87 81 77 73
UNIT RETURN 92 87 82 83 77 71 67 63
MZ-2
RADIATED 70 66 59 70 63 56 46 51
UNIT DISCHARGE 80 76 77 86 85 84 82 76
UNIT RETURN 73 68 70 84 72 71 72 67
AIR HANDLING UNIT ZONE DAMPER SCHEDULE
MZ UNIT CFM ZONE SERVING AREA EXISTING DUCTWORK SIZE
MZ-1 3390 5 SEWING 32 x 14 MZ-1 2190 6 PACKING 12 x 30
MZ-1 3400 7 TOWER 24" ROUND
MZ-2 1200 1 OFFICES 14 x 14 MZ-2 500 2 WOMENS-MENS SHOWERS 14 x 12 MZ-2 2095 3 TRAINING, CREW SUP, READY, OFFICES, WEIGHT 16 x 15 MZ-2 800 4 EXERCISE 14 x 12
1. CONTRACTOR SHALL BE AWARE THAT THIS IS A REMODELING PROJECT
AND AS SUCH, CERTAIN ITEMS AND SIZES CANNOT BE FULLY ILLUSTRATED
NOR EXPLAINED WITHOUT FIELD OBSERVATION. THEREFORE,
CONTRACTOR IS ADVISED TO VISIT AND EXAMINE THE JOB SITE AND
BUILDING IN EVERY DETAIL AS PERTAINS TO THIS PROJECT AND MAKE
ALLOWANCES IN THEIR PROPOSAL FOR ALL CONDITIONS THAT WILL
AFFECT THE WORK INDICATED IN THE PROJECT SPECIFICATIONS AND
CONTRACT DRAWINGS.
2. ALL REMOVED ITEMS, EXCEPT THOSE NOTED TO BE REUSED OR TO
REMAIN THE PROPERTY OF THE GOVERNMENT, SHALL BECOME
PROPERTY OF THE CONTRACTOR AND SHALL BE REMOVED FROM THE
JOBSITE. THE GOVERNMENT RESERVES THE RIGHT TO KEEP ANY
REMOVED ITEMS EVEN THOUGH NOT NOTED ON DRAWINGS.
3. WHERE EXISTING EQUIPMENT, DUCTS, PIPES ETC. ARE TO BE REMOVED,
SUCH REMOVAL SHALL INCLUDE ALL ANCHORS, BASES, HANGERS, ETC.
4. CONTRACTOR SHALL REPORT AMOUNTS OF MATERIAL RECYCLED IN
WEIGHT TO GOVERNMENT.
5. DEMOLITION IS SHOWN AS DASHED LINE IN AREA OF WORK.
6. CONTRACTOR SHALL PERFORM ALL CUTTING AND PATCHING REQUIRED.
7. THE PURPOSE OF DEMOLITION IS TO REMOVE MULTI-ZONE AIR HANDLERS
MZ-1, MZ-2 AND ALL ASSOCIATED DUCTWORK, PNEUMATIC CONTROLLED
DAMPERS, PNEUMATIC CONTROLLED VALVES, HYDRONIC BRANCH PIPING
AND ALL FITTINGS TO COILS TO COORDINATE WITH DEMOLITION TO
MINIMIZE AFFECT ON EXISTING INFRASTRUCTURE.
1. COORDINATE INSTALLATION OF PIPING AND DUCTWORK WITH STRUCTURAL COMPONENTS AND
OTHER SYSTEM INSTALLATIONS. CREATE PENETRATIONS IN EXISTING BUILDINGS AND PATCH
AND REPAIR SURFACES AS REQUIRED TO MATCH EXISTING.
2. ALL DUCTWORK SHALL BE SEALED TO SEAL LEVEL A. SEAL ALL TRANSVERSE JOINTS, ALL
LONGITUDINAL SEAMS AND ALL DUCT WALL PENETRATIONS.
3. ALL DUCT DIMENSIONS SHOWN ARE INTERIOR DIMENSIONS.
4. SEAL ALL MECHANICAL PENETRATIONS THROUGH FIRE-RATED ASSEMBLIES WITH U.L. APPROVED
FIRE-RATED SYSTEM.
5. COORDINATE LOCATION OF HVAC EQUIPMENT WITH ALL OTHER TRADES TO MAINTAIN ACCESS
AND SERVICE CLEARANCES.
6. COORDINATE REQUIREMENTS FOR ACCESS PANELS AND DOORS FOR MECHANICAL ITEMS
REQUIRING ACCESS THAT ARE CONCEALED BEHIND FINISHED AREAS. PROVIDE A DRAWING WITH
PROJECT SUBMITTALS THAT SHOWS THE LOCATIONS AND SIZE OF PANELS.
7. CONTRACTORS MUST BE ON-SITE DURING THE STARTUP SERVICES, TROUBLE SHOOTING AND
TEMPERATURE CONTROL WORK WILL BE REQUIRED OF THE MECHANICAL AND TEMPERATURE
CONTROLS CONTRACTOR.
8. PROVIDE PRE MANUFACTURED ACCESS PANELS IN DUCT FOR EACH SMOKE DETECTOR.
COORDINATE EXACT LOCATION OF PANEL WITH GOVERNMENT.
9. THE CONTRACTOR SHALL RE-ESTABLISH THE HEATING LOOP IMMEDIATELY UPON
DISCONNECTION FROM THE MZ UNITS SO THE HEATING LOOP CAN BE USED TO PROVIDE
HEATING WATER TO FINTUBE HEATERS DURING CONSTRUCTION. THE CONTRACTOR SHALL
ENSURE MANUAL OPERATION OF THE BOILER AND HYDRONIC PUMPS DURING THIS PERIOD. THE
CONTRACTOR SHALL NOT COMPROMISE THE OPERATION OF THE CONTROL AIR COMPRESSOR,
AND HYDRONIC PUMPS, BOILER AND CHILLER DURING THIS PERIOD.
10. BUILDING 205 CAN HAVE ONLY ONE SOURCE OF BUILDING HEAT DOWN AT A TIME. MAINTAIN
PERIMETER HEATING CONTROL VALVES AND SYSTEM CONTROLS WHEN MZ UNITS REPLACEMENT
IS IN PROGRESS.
DEMO WORK GENERAL NOTES: NEW GENERAL NOTES:
AIR HANDLING UNIT SCHEDULE
MARK MFGR MODEL NO.
SUPPLY FAN COOLING COIL HEATING COIL FILTERS
WEIGHT REMARKSCFM ESP TSP MOTOR CFM CAPACITY FPM ROWS EAT EAT LAT LAT AIR PD EWT LWT GPM WATER AIR CAPACITY ROWS EAT LAT AIR PD EWT LWT GPM WATER TYPE MERV FILTER AIR PD
(IN W.C.) (IN W.C.) HP MCA MOP ELECTRICAL POWER TOTAL/SENS BTUH DB WB DB WB (IN W.C.) - - - PD (FT) FLOW BTUH MIN. DB DB (IN W.C.) - - - PD (FT) CLEAN, MEAN, DIRTY (IN WC) MZ-1 DAIKIN APPLIED CAH024GMAM 8,980 1.50 3.39 10 - - 208V-3PH-60HZ 8980 258,988 / 229,109 395 4 80F 63F 54.1F 52.7F 0.32 45F 54.4F 55 6.4 8980 354,208 2 55F 95F 0.33 180F 160F 35.4 4.3 PLEATED 8 0.14, 0.57, 1.0 4004 LBS 1, 2, 3, 4, 6, 7 MZ-2 DAIKIN APPLIED CAH010GMGM 4,595 1.50 3.54 (2) 3HP 19.8 25 208V-3PH-60HZ 4595 121,117 / 110,373 465 4 80F 63F 55.4F 53.5F 0.42 45F 55F 27.0 3.4 4595 186,638 2 55F 96.7 0.37 180F 159.3 18 4.2 PLEATED 8 0.17, 0.59, 1.0 2688 LBS 1, 2, 3, 4, 5, 6, 7
SCHEDULE NOTES:
1. SEE DRAWING M202 FOR EACH MULTI ZONE AIR HANDLER PHYSICAL DIMENSIONS.
2. NO GLYCOL IN CHILLED OR HEATING WATER SOLUTION.
3. UNIT PERFORMANCE BASED ON 2800FT ELEVATION.
4. INSTALL LED LIGHTS IN FAN, FILTER AND MIXING SECTIONS. PROVIDE SEPARATE 110V-1PH-60 ELECTRICAL CONNECTION FOR LIGHTS.
5. PROVIDE ON UNIT MZ-2 EXTERNAL J BOX WITH VFD.
6. PROVIDE VFD WITH DISCONNECT WITH MULTI ZONE AIR HANDLERS, VFD IS FOR BALANCING AIR FLOW PURPOSES.
7. HORIZONTAL DISCHARGE LOCATION ON MULTI ZONE AIR HANDLERS WITH MULTI ZONE DAMPERS.
DRAIN
HEATING WATER SUPPLY
HEATING WATER RETURN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
GATE VALVE
BALL VALVE
BUTTERFLY VALVE
GLOBE VALVE
TRIPLE DUTY VALVE
SWING CHECK VALVE
STRAINER
FLEX CONNECTOR
HOSE END DRAIN VALVE
PRESSURE REDUCING VA.
SAFETY RELIEF VALVE
UNION
MOTORIZED T.C. VA/2-WAY
MOTORIZED T.C. VA/3-WAY
ECCENTRIC PLUG BALANCING VALVE
VALVE IN RISER
TEE UP
TEE DOWN
ELBOW UP
ELBOW DOWN
PIPE SIZE CHANGE
MANUAL FLOW BALANCING VALVE
(CIRCUIT SETTER)
AUTOMATIC FLOW BALANCING VALVE
PRESSURE/TEMP. TEST PLUG
NORMALLY OPEN
NORMALLY CLOSED
COMMON
NO
NC
C
A
M
CWR
CWS
HWR
HWS
D ELECTRIC THERMOSTAT
ELECTRIC THERMOSTAT W/GUARD
ACOUSTICALLY LINED SHEET
METAL DUCT
MANUAL BALANCING DAMPER
FLEX CONNECTOR
ACCESS DOORS
FIRE DAMPER
FIRE/SMOKE DAMPER
MOTORIZED DAMPER
TURNING VANE ELL
45° LOW-LOSS TAKE-OFF FITTING W/
DAMPER & FLEX DUCT
45° LOW-LOSS TAKE-OFF FITTING W/
DAMPER & RIGID ROUND DUCT
90° TEE TAKE-OFF FITTING
CONICAL 90° TEE TAKE-OFF FITTING
45° TEE TAKE-OFF FIITTING
45°-90° TEE TAKE-OFF FITTING
DIFFUSER, REGISTER, OR GRILLE THROW
PATTERN SHOWN ON DWGS.
CONNECT NEW WORK TO EXISTING
SD-1 (PLAN CODE)
8x8 (NECK SIZE)
200 (CFM)
AD
AD
FD
FSD
T
T
M
EXISTING(E)
REMOVE FOR DEMOLITION
DIFFUSER, REGISTER & GRILLE SCHEDULE
PLAN
MFGR MODEL NECK SIZE MATERIAL COLOR/ REMARKSCODE FINISH
SG-1 TITUS JFA 24 X 12 STEEL WHITE 2
SG-2 TITUS JFA 16 X 16 STEEL WHITE 2
RG-1 TITUS 350RL 12 X 12 STEEL WHITE 1
SCHEDULE NOTES:
1. PROVIDE OPPOSED BLADE DAMPER IN GRILLE.
2. PROVIDE SUPPLY GRILLE WITH ADJUSTABLE BLADES.
10658
L ENGINEERPR
O
FE
SSIONAL ENGINEERPR
O
FE
SSIONA
HADIFOETAT OS
EREDREGISTEREDREGIST
HADIFOETAT OS
N
7-28-17
VESTIBULE
(E)HWR
(E)HWR
(E)HWS
(E)HWS
(E)HWR
(E )H
W R
(E)HWS
(E)HWR
PD
TC
TC
M
C C
E
ELEC
(E)HWS
(E)HWR
3/4"1"
1"
1"
3/4"
3/4"
3/4"
1-1/4"
3/4"
1-1/4"
1-1/4" 1-1/4"
1-1/4"
3/4"
1"
3/4"
1-1/4"
2"
48x14 OA
SEE ENLARGED PLAN ON
M103 DRAWING.
EXISTING BALANCING
VALVE TO REMAIN IN
HEATING WATER PIPES.
3 4
1. EXISTING HEATING WATER SUPPLY AND RETURN PIPING TO
REMAIN.
2. REMOVE FOR DEMOLITION OUTSIDE AIR DAMPER WITH
PNEUMATIC ACTUATOR IN DUCTWORK. SEE M101 FOR DAMPER
REPLACEMENT ON HVAC PLAN. REMOVE DUCTWORK PORTION
FOR DAMPER REMOVAL.
3. PATH FOR REMOVAL OF EXISTING MZ UNITS, CONTRACTOR WILL
HAVE TO ALLOW FOR REMOVAL OF MZ UNITS IN SECTIONS.
4. EXISTING OUTSIDE AIR LOUVER TO REMAIN.
DEMOLITION SHEET NOTES #
10658
L ENGINEERPR
O
FE
SSIONAL ENGINEERPR
O
FE
SSIONA
HADIFOETAT OS
EREDREGISTEREDREGIST
HADIFOETAT OS
T T
T
T
3 3
3 3 3 3 3 3 3
T
T
2 T-STAT FOR
MZ-2 READY
T-STAT FOR
MZ-1 TOWER
T
T-STAT FOR
MZ-1 SEWING
& PACKING
T
1 T-STAT
FOR
MZ-2
OFFICES
ELECTRIC FINTUBE
HEATERS TO REMAIN
EXISTING FLOOR
REGISTERS TO
REMAIN.
(E) EAST ZONE
FINTUBE
HEATERS
(E) WEST ZONE
FINTUBE
HEATERS
14x11
12x10 x2
R A
(E) 12x12 RETURN
GRILLE IN SIDE OF
DUCT TO REMAIN.
14x12
11x11
9x8
(E)14x11 (E)14x1214x12
(E) 11x11
(E)15x12 SA
(E )2
5x
S A
SUPPLY DUCT
DOWN TO DIFFUSER
IN OFFICE CEILING
(E)28x28 RA
14x9 (E)14x14
25x12
(E)18x14
28x28 RA
(E )1
6x
(E)22x18
(E )1
6x
(E )1
6x
(E)16x10
T-STAT FOR
MZ-2
WOMENS
T-STAT FOR
MZ-2 MENS
(E )1
2x
(E )1
2x
(E )1
2x
(E )1
5x
(E)14x6
(E )1
5x
(E )1
5x
(E)14x6(E)14x6
(E)18x16
1. REMOVE FOR DEMOLITION EXISTING PNEUMATIC
T-STAT. SEE M102 FOR REPLACEMENT DDC SENSORS.
2. REMOVE FOR DEMOLITION EXISTING DDC T-STAT.
3. EXISTING HYDRONIC FINTUBE HEATERS TO REMAIN.
4. EXISTING EXHAUST IN MENS RESTROOM/LOCKER
ROOM TO REMAIN.
5. EXISTING CABINET EXHAUST FANS IN WOMENS
SHOWER/LOCKER ROOMS TO REMAIN.
6. REMOVE FOR DEMOLITION DUCTWORK SECTION
INCLUDING HANGARS. PATCH AND REPAIR
WALL/CEILING WHERE HANGARS WERE REMOVED. SEE
M103 FOR NEW HVAC PLAN.
7. REMOVE FOR DEMOLITION EXISTING GRILLE ON
DUCTWORK, SEE M103 FOR NEW HVAC PLAN.
8. REMOVE FOR DEMOLITION EXISTING PNEUMATIC
T-STAT. PATCH AND REPAIR WALL, NO REPLACEMENT
T-STAT IN THIS LOCATION.
DEMOLITION SHEET NOTES #
10658
L ENGINEERPR
O
FE
SSIONAL ENGINEERPR
O
FE
SSIONA
HADIFOETAT OS
EREDREGISTEREDREGIST
HADIFOETAT OS
1. PROVIDE MOTORIZED DAMPER WITH DDC ACTUATOR IN
EXISTING FRESH AIR DUCTWORK, VERIFY EXISTING
DUCTWORK SIZE FOR DAMPER SIZE.
2. PATH FOR REMOVAL AND REPLACEMENT UNITS TO BASEMENT
MECHANICAL ROOM. CONTRACTOR WILL HAVE TO ALLOW FOR
SECTIONS OF MZ UNITS TO BASEMENT MECHANICAL RM AND
ASSEMBLE AND SET UP IN BASEMENT MECHANICAL ROOM.
SHEET NOTES
VESTIBULE
(E)HWR
(E)HWR
(E)HWS
(E)HWS
(E)HWR
(E )H
W R
(E)HWS
(E)HWR
TC
TC
M
C C
E
ELEC
(E)HWS
(E)HWR
3/4"1"
1"
1"
3/4"
3/4"
3/4"
1-1/4"
3/4"
1-1/4"
1-1/4" 1-1/4"
1-1/4"
3/4"
1"
3/4"
1-1/4"
2"
48x14 OA
SEE ENLARGED PLAN ON
M103 DRAWING.
EXISTING BALANCING
VALVE TO REMAIN IN
HEATING WATER PIPES.
M
SEE ENLARGED PLAN ON
M103 DRAWING.
10658
L ENGINEERPR
O
FE
SSIONAL ENGINEERPR
O
FE
SSIONA
HADIFOETAT OS
EREDREGISTEREDREGIST
HADIFOETAT OS
14x11
12x10 x2
R A
(E) 12x12 RETURN
GRILLE IN SIDE OF
DUCT TO REMAIN.
9x8
(E)14x11 (E)14x1214x12
(E) 11x11
(E)15x12 SA
(E )2
5x
S A
SUPPLY DUCT
DOWN TO DIFFUSER
IN OFFICE CEILING
(E)28x28 RA
14x9 (E)14x14
25x12
T T
TT
CFM
CFM
T
SG-1
24x12
800 CFM
CFM
CFM
CFM
8Ø
8Ø
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
CFM
T
RG-1
SG-2
16x16
CFM
T
CFM
530 CFM
EACH
FLOOR
REGISTER
1700 CFM
FLOOR
REGISTER
1700 CFM
1. PROVIDE AVERAGING SENSOR FOR RIGGING AND SEWING
ZONES ON MZ-1 UNIT. PATCH AND REPAIR WALL FOR DDC T-STAT
REPLACEMENT, PROVIDE BACKING PLATE AS NECESSARY AT
T-STAT LOCATION.
2. PROVIDE SENSOR FOR OFFICE ZONE ON MZ-2 UNIT. PATCH AND
REPAIR WALL FOR DDC T-STAT REPLACEMENT. PROVIDE
BACKING PLATE AS NECESSARY AT T-STAT LOCATION.
3. PROVIDE SENSOR FOR TOWER ZONE ON MZ-1 UNIT.PATCH AND
REPAIR FOR DDC T-STAT REPLACEMENT. PROVIDE BACKING
PLATE AS NECESSARY AT T-STAT LOCATION.
4. PROVIDE SENSOR FOR READY ZONE ON MZ-2 UNIT. PATCH AND
REPAIR WALL FOR DDC T-STAT REPLACEMENT. PROVIDE
BACKING PLATE AS NECESSARY AT T-STAT LOCATION.
5. PROVIDE SENSOR FOR WEIGHT/EXCERCISE ZONE ON MZ-2 UNIT.
PATCH AND REPAIR WALL FOR DDC T-STAT REPLACEMENT.
PROVIDE BACKING PLATE AS NECESSARY AT T-STAT LOCATION.
6. PROVIDE AVERAGING SENSOR FOR WOMENS/MENS SHOWER
ZONE ON MZ-2 UNIT. PATCH AND REPAIR WALL FOR DDC T-STAT
REPLACEMENT. PROVIDE BACKING PLATE AS NECESSARY AT
T-STAT LOCATION.
SHEET NOTES
7. TRANSITION EXISTING DUCTWORK TO NEW SUPPLY GRILLE,
WITH MANUAL VOLUME DAMPER IN DUCTWORK. SUPPLY GRILLE
IS TO DISCHARGE AT 45DEG.
8. CONNECT 8"Ø TO EXISTING 14x11 DUCTWORK, ROUTE 8"Ø HIGH
AS POSSIBLE. SEE DETAIL 2/M201.
9. CONNECT 8"Ø TO EXISTING 11x11 DUCTWORK WITH HIGH
EFFICIENT TAKE OFF WITH VOLUME DAMPER, SEE DETAIL 2/M201.
10. TRANSITION EXISTING DUCTWORK TO NEW SUPPLY GRILLE AND
INSTALL MANUAL VOLUME DAMPER IN DUCTWORK. ANGLE OF
DISCHARGE SIMILAR TO EXISTING 45DEG.
11. INSTALL RETURN AIR GRILLE WITH OBD IN BOTTOM OF EXISTING
25x12 DUCTWORK.
12. ADD MANUAL VOLUME DAMPER INTO EXISTING DUCTWORK TO
FACILITATE TEST AND BALANCE. VERIFY EXISTING DUCTWORK
SIZE.
10658
L ENGINEERPR
O
FE
SSIONAL ENGINEERPR
O
FE
SSIONA
HADIFOETAT OS
EREDREGISTEREDREGIST
HADIFOETAT OS
VESTIBULE
TC
TC
M
C C
EL
EC
ELEC
48x14 OA
(E )3
6x
R A
(E )2
4x
R A
3"
MZ-2
MZ-1
(E ) 2
4" Ø
R
A(E) HWR
D
D
3"
(E)HWR
(E)HWS
(E)CWR
(E)CWS
(E) 24x36 RA
(E)12x30 SA (E)14x32 SA
1. (E) CHILLED WATER EXP. TANK TO REMAIN.
2. (E) HEATING WATER EXP. TANK TO REMAIN.
3. REMOVE FOR DEMOLITION EXISTING AIR COMPRESSORS AND
REFRIGERATED AIR DRYER AND ALL PNEUMATIC CONTROL TUBING.
4. REMOVE FOR DEMOLITION ENTIRE CONC/CORK PAD UNDER MULTI
ZONE AIR HANDLING UNITS.
5. TEMPERATURE CONTROL PANEL TO BE USED FOR NEW DDC
CONTROLLERS. REMOVE FOR DEMO ALL PNEUMATIC DEVICES IN
PANEL.
6. REMOVE PNEUMATIC DAMPER IN DUCTWORK. SEE M103 FOR
REPLACEMENT HVAC PLAN.
7. REMOVE FOR DEMOLITION ENTIRE MULTI ZONE AIR HANDLING
UNITS MZ-1, MZ-2 FOR REPLACEMENT.
8. EXISTING CHILLED WATER SYSTEM, CHILLER, BUFFER TANK, AND
PUMP TO REMAIN.
9. DISCONNECT CHILLED WATER AND HEATING WATER PIPING FROM
MULTI ZONE AIR HANDLING UNITS.
DEMOLITION SHEET NOTES #
10. REMOVE FOR DEMO MZ UNIT HEATING COIL PNEUMATIC VALVES
FOR REPLACEMENT.SEE PLAN 2 ON M103 FOR NEW LOCATION
OF HEATING CONTROL VALVES.
11. EXISTING BOILER, HEATING WATER PUMPS, AND PIPING TO
REMAIN.
12. REMOVE FOR DEMO FINTUBE HEATING ZONE CONTROL VALVES.
BUILDING 205 CAN HAVE ONLY ONE SOURCE OF BUILDING HEAT
DOWN AT A TIME. MAINTAIN PERIMETER HEATING CONTROL
VALVES AND SYSTEM CONTROLS WHEN MZ UNITS
REPLACEMENT IS IN PROGRESS.
13. PROVIDE CAPS ON EXISTING HUB DRAINS.
14. EXISTING SUMP PUMP PIT SERVING BASEMENT MECHANICAL
ROOM FLOOR DRAINS.
15. EXISTING WATER HEATER TO REMAIN.
16. REMOVE FOR DEMOLITION MZ UNIT DUCTWORK TO WITHIN 2FT
OF BASEMENT CEILING.
17. REMOVE PORTION OF HEATING WATER PUMP DISCHARGE
PIPING FOR INSTALLATION OF CHECK VALVES.
VESTIBULE
PD
TC
TC
M
C C
EL
EC
ELEC
MZ-2 MZ-1
PD
(E)48x14 OA x2
R
A
(E ) 2
4x
R A
(E ) 2
4x
S A
(E)12x30 SA (E)14x32 SA
3"
PARALOFT AIR
COMPRESSOR TO
(E ) 2
4" Ø
R
A(E) HWR
EXISTING ELEC
CONDUIT TO
REMAIN
(E)HWR
(E)HWS
(E)CWR
(E)CWS
(E) 24x36 RA
(E)BOILER FLUE
TO REMAIN.
(E)COMBUSTION
AIR DUCTWORK
TO REMAIN.
1. PROVIDE 4" HIGH CONCRETE HOUSEKEEPING PAD, UNDER MZ UNIT, WITH 6x6xW1.4 x
W1.4 WWF REINFORCING FABRIC IN PAD. EXTEND CONC. PAD 2" PAST UNIT FOOTPRINT.
2. CAP FLOOR DRAIN WASTE PIPE BEFORE HOUSEKEEPING PAD INSTALLATION.
3. SEE M202 FOR COIL PIPING DETAILS FOR HEATING WATER AND CHILLED WATER
CONNECTION TO MZ UNITS.
4. PROVIDE DDC MODULATING CONTROL VALVE FOR MZ-1, MZ-2 HEATING COIL. SEE
CONTROL DRAWING M301 FOR VALVE CONTROL SEQUENCE.
5. PROVIDE STENCIL OR LABEL ON ALL SUPPLY DUCTWORK INSULATION FOR EACH
MZ-ZONE AREA SERVED, SIMILAR TO EXISTING ZONE IDENTIFICATION.
6. CONTRACTOR TO BE AWARE OF EXISTING FIRE SPRINKLER HEADS AND PIPES LOCATION
WITH IN BASEMENT MECHANICAL ROOM. MODIFY FIRE SPRINKLER PIPE AND SPRINKLER
PLACEMENT FOR DUCTWORK AND MZ UNIT REPLACEMENT PER NFPA 13.
7. PROVIDE 1" CONDENSATE DRAIN WITH TRAP TO DISCHARGE INTO EXISTING SUMP,
ROUTE ALONG FLOOR TO SUMP.
8. INSTALL MANUAL VOLUME DAMPER IN EACH ZONE DUCTWORK TO BE ACCESSIBLE IN
BASEMENT MECHANICAL ROOM.
9. ACCESS DOORS ON MZ-2 SHALL NOT BE BLOCKED BY EXISTING CHILLED WATER PUMP.
SHEET NOTES
10658
L ENGINEERPR
O
FE
SSIONAL ENGINEERPR
O
FE
SSIONA
HADIFOETAT OS
EREDREGISTEREDREGIST
HADIFOETAT OS
BASEMENT
(E) AIR SEPARATOR
TO FLOOR
T
MZ-1
HEATING
WATER COIL
MZ-2
HEATING
WATER COIL
(E) BOILER
(E)HWR
(E)HWR
FINTUBE HEATER
ZONES
(E) HW EXPANSION TANK
(E) MANUAL
AIR VENT
(E)HWS(E)HWS
(E) HEATING WATER PUMP (E) HEATING WATER PUMP
96 GPM @ 55 FT TDH 96 GPM @ 55 FT TDH
EXISTING CONTROL
VALVE TO REMAIN
(E) HWS
(E) HWR
3"
3"
UNIONS (TYP.)
(E) TEMP
SENSOR
(TYP.)
3" 2"
3"
STRAINER (TYP.)
2 1/2" 1 1/2"
2 1/2" 3"
1 1/4"
1 1/4"
(E) BOILER
CIR. PUMP
(E) CHEMICAL FEEDER
(E) HWS
(E) HWR
TT
REMOVE PORTION OF
PIPING TO INSTALL
CHECK VALVES.
1 1/2"
2 1/2" 1 1/2" 1 1/4"
1 1/4" (E)STRAINER(TYP)
(E)GATE
VALVE (TYP)
FT WESTFT EAST
MAIN SUPPLY DUCT
SUPPLY REGISTER
OR GRILLE
SQUARE TO ROUND
HIGH EFFICIENCY
TAKEOFF WITH
VOLUME DAMPER
FLEXIBLE OR
RIGID ROUND
RUN OUT,
SEE PLANS
MAIN SUPPLY DUCT
VOLUME DAMPER
USE THIS IF BRANCH
CFM IS 40% OR LESS
OF MAIN DUCT CFM
BRANCH DUCT
PROVIDE VOLUME DAMPER
WHEN SHOWN ON PLANS
SQUARE ELBOW SHOWN.
ROUND ELBOW IS
ACCEPTABLE
PROVIDE VOLUME DAMPER
WHEN SHOWN ON PLANS
SUPPLY REGISTER
OR BRANCH DUCT
TURNING VANES
MAIN SUPPLY
DUCT
MAIN EXHAUST OR
RETURN DUCT
BRANCH DUCT
VOLUME DAMPER
EXHAUST AND/OR RETURN BRANCH DUCT
SUPPLY DUCT TAKEOFFS
AIR SPLIT TYPE DUCT TAKEOFF
BRANCH DUCT TAKEOFF
SUPPLY REGISTER & RUN OUT TAKEOFF
1/4 W -
4" MIN.
1/4 W -
4" MIN.
1/4 W -
4" MIN.
24"
W
W
1/4 W -
4" MIN.
24"
SPLIT DIM
PROPORTIONATE
TO CFM SPLIT
USE THIS IF BRANCH
CFM IS 40% OR LESS
OF MAIN DUCT CFM
REMOVE PORTION OF HEATING
WATER PIPING TO FACILITATE
REPLACEMENT MZ UNITS AND HW
CONTROL VALVE NEW LOCATION.
10658
L ENGINEERPR
O
FE
SSIONAL ENGINEERPR
O
FE
SSIONA
HADIFOETAT OS
EREDREGISTEREDREGIST
HADIFOETAT OS
EXISTING
EXPANSION TANK
EXISTING CHILLER
EXISTING CHILLED
WATER PUMP
94.6 GPM @ 45 FT TDH
BASEMENT
EXISTING
CHILLED
WATER
BUFFER
TANK
3"
3"
MZ-2 CHILLED
WATER COIL
27 GPM
3"
GRADE
T
T
MZ-1 CHILLED
WATER COIL
55 GPM
(E)CHWS
(E)CHWR
3"
BASEMENT
(E) AIR SEPARATOR
TO FLOOR
T
MZ-1
HEATING
WATER COIL
35.4 GPM
(E) RPBP FOR
MAKE UP WATER
MZ-2
HEATING
WATER COIL
18 GPM
(E) BOILER
(E)HWR
(E)HWR
FINTUBE HEATER
ZONES
(E) HW EXPANSION TANK
REPLACE
MANUAL AIR
VENT
(E)HWS(E)HWS
FT
WEST
FT
EAST
(E) HEATING WATER PUMP (E) HEATING WATER PUMP
96 GPM @ 55 FT TDH 96 GPM @ 55 FT TDH
(E)CHWS
(E)CHWR
3"
EXISTING CONTROL
VALVE TO REMAIN
3"2 1/2"
2 1/2"
2"2"
(E) HWS
(E) HWR
3"
3"
UNIONS (TYP.)
T T
(E) TEMP
SENSOR
(TYP.)
3" 2"
3"
STRAINER (TYP.)
2 1/2"
2 1/2" 3"
1 1/4"
1 1/4"
(E) BOILER
CIR. PUMP
(E) CHEMICAL FEEDER
(E) HWS
(E) HWR
1 1/2"
REVISED CHILLED WATER
PIPING DOWN TO MZ UNIT
REPLACEMENT, INSTALL
SHUT OFF VALVE AND
BALANCING VALVE IN
CHILLED WATER PIPING.
REVISED CHILLED WATER
PIPING DOWN TO MZ UNIT
REPLACEMENT, INSTALL
SHUT OFF VALVE AND
BALANCING VALVE IN
CHILLED WATER PIPING.
PROVIDE TRIPLE DUTY
VALVE ON EACH PUMP
DISCHARGE.
PROVIDE HOSE
END DRAIN VALVE
PROVIDE HOSE
END DRAIN VALVE
10658
L ENGINEERPR
O
FE
SSIONAL ENGINEERPR
O
FE
SSIONA
HADIFOETAT OS
EREDREGISTEREDREGIST
HADIFOETAT OS
O pn
O pn
9.
O.
D.
B
AS
E
(E) 24"x36 RA
DRYING TOWER
3400 CFM ZONE 7
PACKING/RIGGING 2190 CFM
ZONE 6
SEWING 3390 CFM ZONE 5
24"x16 OA
C H
IL
LE
D W
AT
ER
H
EA
T W
AT
ER
FAN
FI
LT
ER
SE
C
TI
O N
NEUTRAL
DECK
14x24 OA
4" HIGH CONCRETE
HOUSEKEEPING PAD
M
(E) 36x24 RA
M
M
M
M
COMBINE DAMPERS TO
ACTUATOR FOR AIRFLOW PER
ZONE
ZONES
T
T
T
14x16
(E) 20"x36 RA
16x28 RA
14x16 OA
M
ZONES
NEUTRAL
DECK
4" HIGH CONCRETE
HOUSEKEEPING PAD
READY & OFFICE
1295 CFM ZONE 3
OFFICES 1200 CFM ZONE 1
EXERCISE
1600 CFM ZONE 4
MENSWOMENS SHOWER 500 CFM ZONE 2
FI
LT
ER
SE
C
TI
O N
CHILLED WATER COIL
HEATING WATER COIL
14x16 OA
28x16 RA
(E)48x14 OA
(E )4
8x
O A
M
M
M
M
M
COMBINE DAMPERS TO
ACTUATOR FOR AIRFLOW PER
ZONE
(E)36x20 OA
T
T
T
T
10658
L ENGINEERPR
O
FE
SSIONAL ENGINEERPR
O
FE
SSIONA
HADIFOETAT OS
EREDREGISTEREDREGIST
HADIFOETAT OS
M301
MZU-1, MZU-2 CONTROL DIAGRAM
NOT TO SCALE
RA
N.C.
H
C
TO ZONE
CWR
OA
C
C
NEUTRAL DECK
DAMPER
COLD DECK
DAMPER
EXISTING FIRE
ALARM PANEL
HOT DECK
DAMPER
N.C.
AO OUTSIDE AIR
DAMPER
CWS
SUPPLY
FAN
AI-RETURN AIR TEMP
AI-TEMP
AI-TEMP
AI-TEMP
AO-ZONE DAMPER
NO-RETURN
AIR
DAMPER
HWR
HWS
AO- MODULATING HEATING
CONTROL VALVE
AI-FILTER
DIFF
PRESSURE
VFD
M
CT
BO - SUPPLY FAN
START/STOP
AO - SUPPLY FAN
SPEED
BI - SUPPLY
FAN VFD
FAULT
AO- OUTSIDE
AIR DAMPER
AI OUTSIDE AIR
TEMP SENSOR
PARALOFT BLDG
AI- OUTSIDE
AIR TEMP
AI- MIXED
AIR TEMP
AI - ZONE TEMP
AI - ZONE SETPOINT ADJUST
T
ZONE TEMPERATURE
JCI NS-BTP 7002
CHILLER CONTROL AND CHILLED WATER SYSTEM
EXISTING CONTROL SEQUENCE FOR CHILLER AND CHILLED WATER SYSTEM TO
REMAIN AS IS. SEE JCI CONTROL SHOP DRAWINGS FOR NIFC BLDG 205, DATED
4/22/2014.
BOILER AND HEATING WATER SYSTEM
EXISTING CONTROL SEQUENCE FOR BOILER AND HEATING WATER SYSTEM TO REMAIN
EXCEPT REPLACEMENT OF PNEUMATIC VALVES AND ACTUATOR TO MZ UNIT COILS
AND FINTUBE HEATING LOOP CONTROL VALVES. SEE JCI CONTROL SHOP
DRAWINGS FOR NIFC BLDG 205, DATED 12/7/2011.
CONTROL CONTRACTOR SHALL CONVERT EXISTING PNEUMATIC CONTROL VALVES ON
MZ AHU UNITS AND FINTUBE HEATING LOOP TO DDC VALVES. REMOVE ANALOG
OUTPUTS FROM EXISTING DDC CONTROL PANEL TO PNEUMATIC CONTROL PANEL
AND REPLACE WITH NEW DDC CONTROL VALVES OUTPUT TO EXISTING JCI
NCE2560 CONTROLLER. REMOVE 4 EP SWITCHES FROM PNEUMATIC CONTROL
PANEL.
EAST PERIMETER HW LOOP AND WEST PERIMETER FINTUBE HW LOOP CONTROL
SEQUENCE TO REMAIN THE SAME, REPLACE CONTROL VALVE AND ACTUATOR
WITH DDC CONTROL VALVE WITH SIMILAR CV, SIZE AND PORT CONFIGURATION.
MULTI ZONE AHU CONTROL SEQUENCE
OCCUPIED MODE - THE MZ AHU SUPPLY FAN SHALL START BY MANUAL COMMAND OR
BY SCHEDULE. THE OCCUPIED SCHEDULE SHALL INCORPORATE AN OPTIMAL
START ROUTINE TO START THE MZ AHU UP TO 2 HOURS PRIOR TO SCHEDULED
OCCUPANCY TIME BASED ON ZONE AND OUTSIDE AIR TEMPERATURES. THE MZ
AHU SUPPLY FAN SHALL STOP AT THE SCHEDULED STOP TIME.
UNOCCUPIED MODE - THE MZ AHU SUPPLY FAN SHALL BE OFF UNTIL THE ZONE
HIGHEST TEMPERATURE REACHES 85DEG F OR THE ZONE LOWEST TEMPERATURE
REACHES 55DEG F. BOTH SETPOINTS SHALL HAVE 3 DEG F DIFFERENTIAL. WHEN
SUPPLY FAN IS OPERATING IN UNOCCUPIED MODE, COLD DECK SHALL BE
MAINTAINED AT 56DEG F AND HOT DECK SHALL BE MAINTAINED AT 115DEGF WITH
OUTSIDE AIR DAMPER CLOSED.
WHEN SUPPLY FAN IS OFF, THE COOLING VALVE AND OUTSIDE AIR DAMPER SHALL BE
FULLY CLOSED AND HEATING WATER VALVE SHALL REMAIN IN CONTROL OF HOT
DECK.
DURING OCCUPIED MODE, OUTSIDE AIR DAMPER WILL BE ALLOWED TO OPEN TO
MAINTAIN MINIMUM OSA SETPOINT.
MIXED(NUETRAL) DECK TEMPERATURE CONTROL - AN ZONE SATISFIED WILL GET
NEUTRAL DECK AIR AT STANDARD MIXED AIR TEMPERATURE SETPOINT BASED ON
MINIMUM OUTSIDE AIR AND RETURN AIR BYPASSING BOTH COLD DECK AND HOT
DECK COILS. PROVIDE EACH ZONE WITH DUCT TEMPERATURE SENSOR TO BE
MONITORED AT JCI FRONT END.
COLD DECK CONTROL - COLD DECK TEMPERATURE SHALL BE MAINTAINED BY
MECHANICAL COOLING CHILLER. THE COOLING OUTPUT TO THE ZONES SUPPLIED
BY MZ AHU SHALL BE MONITORED AND HIGHEST COOLING OUTPUT WILL RESET
THE COLD DECK TEMPERATURE SETPOINT AS FOLLOWS:
OUTSIDE AIR TEMPERATURE 95DEG F, COLD DECK TEMP SETPOINT 65DEG F
OUTSIDE AIR TEMPERATURE 75DEG F, COLD DECK TEMP SETPOINT 70DEF F
BUILDING DDC AND MULTI ZONE AHU UNITS SEQUENCE OF OPERATION
PROVIDE REPLACEMENT MZ AHU CONTROLLERS, JCI BACnet MS-FEC26xx-x CONTROLLER AND MS-IOMxxxx-x EXPANSION MODULES, BASED ON TOTAL POINT COUNT.
NEW FEC CONTROLLERS SHALL BE BACnet COMMUNICATION, HAVE ENOUGH POINT
CAPACITY TO HAVE ZONE TEMPERATURE INPUTS, OPERATE MZ AHU ZONE DAMPERS AS
WELL AS CONTROL MZ AHU FUNCTIONS(VALVES AND DAMPERS).
EXTEND EXISTING CHILLER NCE2560 BACnet COMMUNICATION TRUNK CONNECTION TO NEW FEC CONTROLLERS. THIS WILL CONNECT ALL CONTROLLERS WITH BACnet
COMMUNICATION BUS ON THE EXISTING SUPERVISORY CONTROLLER.
THROUGH SUPERVISORY CONTROLLER, CONTROL CONTRACTOR SHALL MAP ALL
AVAILABLE CONTROLS POINTS FROM NEW CONTROLLERS INTO EXISTING JOHNSON
CONTROLS METASYS EA BUILDING AUTOMATION SYSTEM ADX10U CENTRAL SERVER.
CONTROL CONTRACTOR SHALL PROVIDE ALL GRAPHICS FOR REPLACEMENT MZU UNITS,
PNEUMATIC CONTROL CONVERSIONS AND UPGRADE EXISTING GRAPHICS TO
INCORPORATE CONTROL SEQUENCES.
CONTROL CONTRACTOR SHALL ADJUST AND BIND ALL GRAPHICS AS NECESSARY TO
REFLECT FLOOR PLAN LAYOUT AND SYSTEM LAYOUT. CONTROL CONTRACTOR SHALL
ADD TRENDS ON ALL CONTROL POINTS THAT SHALL BE RE-POSITORIED INTO SERVER
FOR LONG TERM STORAGE.
CONTROL CONTRACTOR SHALL FULLY COMMISSION ALL NEW CONTROLLERS, HEATING
WATER CONTROL VALVES AND ASSIST THE TEST AND BALANCE CONTRACTOR IN
BALANCING.
CONTROL CONTRACTOR SHALL DELETE POINTS FROM REMOVED CONTROLLERS FROM
BUILDING 205 AUTOMATION SYSTEM.
CONTROL CONTRACTOR'S AS BUILT SUBMITTAL PACKAGE SHALL INCLUDE LOCATION
AND ROUTING OF ALL NEW COMMUNICATION CABLE.
ALL NEW BACNET MSTP COMMUNICATION CABLE SHALL BE RUN IN CONDUIT.
COORDINATE WITH DIVISION 26 ELECTRICAL.
CONTROL CONTRACTOR SHALL REMOVE PNEUMATIC TUBING THROUGHOUT BASEMENT
MECHANICAL ROOM, PE SWITCHES IN CONTROL PANEL, AND PNUEMATIC VALVES.
PROVIDE CONTACT IN MZ AHU UNITS CONTROLLER TO SHUTDOWN ON GENERAL FIRE
ALARM.
PROVIDE NIFC CAMPUS HEATING SETPOINTS AND DISTINCT COOLING SETPOINTS-
OCCUPIED T-STAT SETPOINTS - HEATING UP TO 70 DEG F(ADJ.) AND COOLING DOWN TO
75 DEG F(ADJ.).
UNOCCUPIED T-STAT SETPOINTS - HEATING UP TO 55 DEG F(ADJ) AND COOLING DOWN
TO 85 DEG F(ADJ.).
THE OCCUPIED / UNOCCUPIED MODES WILL BE SCHEDULED FROM THE OPERATOR
WORKSTATION.
MZ AHU SAFETIES AND ALARMS - ALL SAFETY AND ALARMS DEVICES SHALL BE
MANUAL RESET, THE DEVICE THAT HAS TRIPPED MUST BE MANUALLY RESET
BEFORE RESTARTING THE MZ AHU UNITS.
FILTER ALARM. IF THE DIFFERENTIAL PRESSURE (ADJUSTABLE) ACROSS THE AIR
FILTER SHOULD EXCEED 0.2 IN W.G., THE FILTER ALARM SHALL BE INITIATED.
FREEZE ALARM. IF THE HEATING COIL DISCHARGE TEMPERATURE SHOULD FALL
BELOW 35F, THE FREEZESTAT CONTACTS SHALL CLOSE, A FREEZE ALARM SHALL
BE INITIATED AND THE FAN SHALL BE SHUT OFF. THE HEATING VALVE SHALL
OPEN, THE OUTDOOR AIR DAMPER SHALL CLOSE AND THE COOLING VALVE SHALL
FULLY CLOSE. PROVIDE FREEZESTAT IN REPLACEMENT MZ AHU UNITS.
SHUTDOWN: WHEN THE UNIT IS SHUTDOWN BY EITHER A STOP COMMAND OR SYSTEM
SAFETY THE WILL BE SET AS FOLLOWS: SUPPLY FAN SHALL BE OFF, OUTSIDE AIR
DAMPER SHALL CLOSE, RETURN AIR DAMPER SHALL OPEN.
MINIMUM OUTSIDE AIR:
EACH MZ AHU SHALL POSITION THE OUTSIDE AIR DAMPER ON UNIT AT 10% OPEN WHEN
IN OCCUPIED MODE.
WHEN EITHER MZ AHU UNITS IS OPERATING, THE CENTRAL DUCT OUTSIDE AIR DAMPER
SHALL BE OPEN TO MATCH THE LARGEST DEMAND OF THE TWO MZ AHU OUTSIDE AIR
DAMPER COMMANDS.
HOT DECK CONTROL - HEATING DECK TEMPERATURE SHALL BE MAINTAINED BY
MODULATING EACH MZ AHU HEATING WATER CONTROL VALVE. THE HEATING
DECK SETPOINT SHALL BE RESET ACCORDING TO THE FOLLOWING:
OUTSIDE AIR TEMPERATURE 17DEG F, HOT DECK TEMP SETPOINT 96DEG F
OUTSIDE AIR TEMPERATURE 55DEG F, HOT DECK TEMP SETPOINT 72DEG F
10658