SYMBOL DESCRIPTION
ELEVATION CALLOUT
XXX'-XX"
STEP
SLOPE
KEY NOTE
SUBGRADE
FORM SAVER
DRAWING REVISION
NUMBER
CURRENT REVISION CLOUD
X
SECTION OR
DETAIL CUT
SHEET NUMBER
ELEVATION CUT
SHEET NUMBER
X
XX
X
XX
ROUGHENED SURFACE,
INTENTIONALLY ROUGHEN TO 1/4"
AMPLITUDE, UNO
NOTES:
1. ITEMS NOT DESIGNED BY M/M ARE SHOWN HALFTONED,
2. ITEMS INCLUDE:
- EXISTING CONSTRUCTION
- PERFORMANCE SPECIFIED ITEMS (FIBERGLASS FLUMES, ETC.)
EXISTING STRUCTURE
(HALFTONE)
X'-XX" DIMENSIONS TO EXISTING
STRUCTURE,
FIELD VERIFY (ITALICS)
X'-XX"
DIMENSIONS TO NEW
STRUCTURE
NEW STRUCTURE
SYMBOL DESCRIPTION
1) GENERAL:
1A) ALL WORK SHALL CONFORM WITH ACI 301-10, UNLESS NOTED OTHERWISE.
1B) DETAIL BARS IN ACCORDANCE WITH THE DRAWINGS AND ACI PUBLICATION SP-66 (2004): “ACI
DETAILING MANUAL”
2) REINFORCING MATERIALS:
2A) SEE ‘REINFORCING MATERIAL TABLE’
3) REINFORCING FABRICATION:
3A) SPLICES:
- NO SPLICING OF REINFORCEMENT PERMITTED EXCEPT AS NOTED ON DRAWINGS. MAKE BARS
CONTINUOUS AROUND CORNERS WHERE DETAIL NOT PROVIDED. WHERE PERMITTED, SPLICES MAY BE
MADE BY CONTACT LAPS OR MECHANICAL CONNECTORS.
- SEE ‘LAP SPLICE SCHEDULE’ FOR LAP LENGTHS.
- SPLICE CONTINUOUS TOP AND BOTTOM BARS IN WALLS, BEAMS, AND GRADE BEAMS ‘LTS’ UNLESS
NOTED OTHERWISE.
3B) MISCELLANEOUS REINFORCING REQUIREMENTS:
- PROVIDE ADDITIONAL BARS OR STIRRUPS REQUIRED TO SECURE REINFORCING IN PLACE DURING
CONCRETE PLACEMENT.
- MAKE ALL REINFORCING BAR BENDS IN THE FABRICATOR’S SHOP UNLESS NOTED.
- NO WELDING OF REINFORCING PERMITTED UNLESS NOTED ON DRAWINGS. WHERE PERMITTED,
PERFORM WELDING IN ACCORDANCE WITH AWS D1.4-2011.
- PROVIDE ADDED REINFORCING TO TRIM ALL OPENINGS AND NOTCHES AS NOTED IN TYPICAL DETAILS.
4) STRUCTURAL CONCRETE MIX REQUIREMENTS:
4A) SEE ‘CONCRETE MIX TABLE’
5) NON-SHRINK GROUT:
5A) CONFORM TO ASTM C1107
5B) ACHIEVE 6000 PSI COMPRESSIVE STRENGTH AT 28 DAYS.
6) PLACING REINFORCEMENT:
6A) REINFORCEMENT PROTECTION:
- SEE DETAILS
- SEE ACI 117-10 FOR REINFORCEMENT PLACING TOLERANCES
6B) PROVIDE ACCESSORIES NECESSARY TO PROPERLY SUPPORT REINFORCING AND WELDED WIRE REINFORCEMENT AT POSITIONS SHOWN ON PLANS. ALL REINFORCING, DOWELS, BOLTS, AND EMBEDDED PLATES SHALL BE SET AND TIED IN PLACE BEFORE THE CONCRETE IS POURED. “STABBING” INTO
PREVIOUSLY PLACED CONCRETE IS NOT PERMITTED.
7) CONSTRUCTION/CONTROL JOINTS:
7A) SUBMIT DRAWINGS SHOWING CONSTRUCTION LOCATIONS ALONG WITH THE SEQUENCE OF POURS.
7B) CONCRETE CONSTRUCTION JOINT SURFACE SHALL BE CLEANED AND ALL LAITANCE AND LOOSE
MATERIAL REMOVED PRIOR TO SECOND CONCRETE PLACEMENT.
7C)SHEAR FRICTION JOINTS: WHERE CONSTRUCTION JOINTS ARE LABELED AS “ROUGHENED” ON THE DRAWINGS, THE ENTIRE JOINT SURFACE SHALL BE MECHANICALLY ROUGHENED TO A 1/4” AMPLITUDE
AND THOROUGHLY CLEANED. EXPOSE THE COARSE AGGREGATE IN THE HARDENED CONCRETE AND
REMOVE ALL LAITANCE AND LOOSE MATERIAL.
8) MODIFICATIONS TO HARDENED OR EXISTING CONCRETE
8A) UNLESS NOTED ON THE STRUCTURAL DOCUMENTS MODIFICATIONS AS LISTED BELOW SHALL NOT BE
MADE TO HARDENED OR EXISTING CONCRETE WITHOUT APPROVAL OF THE OWNER:
- SAW CUTTING
- CORING
- CHIPPING
8B) DO NOT CUT OR DAMAGE ANY REINFORCING WITHOUT APPROVAL OF THE OWNER
9) SLEEVES, OPENINGS, AND EMBEDED PIPE/CONDUITS:
9A) GENERAL
- REFER TO TYPICAL DETAILS FOR REQUIREMENTS FOR CONDUIT AND PIPE EMBEDDED IN WALLS AND
SLABS
- REFER TO TYPICAL DETAILS FOR SPACING AND LAYOUT LIMITATIONS FOR SLEEVES AND OPENINGS
- FORM OPENINGS AND PROVIDE SLEEVES BEFORE PLACING CONCRETE, CORING OF CONCRETE IS
NOT PERMITTED
9B) REINFORCING
- REFER TO TYPICAL DETAILS FOR REINFORCEMENT REQUIREMENTS AT SLEEVES, OPENINGS OR
CONDUIT
- DO NOT CUT REINFORCING WHICH MAY CONFLICT
1) GENERAL:
1A) ENGINEER: REFERENCES ON THE STRUCTURAL DRAWINGS TO ‘ENGINEER’ MEAN THE STRUCTURAL
ENGINEER OF RECORD.
1B) UNDERGROUND UTILITIES: LOCATE EXISTING UTILITIES AND NOTIFY OWNER OF EXISTING UTILITIES OR
SUBGRADE CONDITIONS WHICH INTERFERE WITH WORK.
2) USE OF DRAWINGS:
2A) DO NOT SCALE DRAWINGS.
2B) DETAILS ON DRAWINGS TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS.
2C)DETAILS NOTED TYPICAL APPLY TO ALL SIMILAR CONDITIONS. WHERE NO SPECIFIC DETAILS ARE SHOWN, CONSTRUCTION SHALL CONFORM TO SIMILAR WORK ELSEWHERE ON THE PROJECT.
2D)WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, AND GENERAL NOTES:
- CONTACT THE OWNER PRIOR TO PROCEEDING WITH CONSTRUCTION
- THE MORE STRINGENT REQUIREMENTS SHALL GOVERN FOR BIDDING / PRICING
3) EXISTING STRUCTURES:
3A) CONTRACT DOCUMENTS HAVE BEEN PREPARED USING AVAILABLE DRAWINGS AND SITE OBSERVATION AS
PERMITTED BY ACCESS RESTRICTIONS DURING DESIGN.
3B) DURING CONSTRUCTION, THE CONTRACTOR MAY ENCOUNTER EXISTING CONDITIONS WHICH ARE NOT KNOWN OR ARE AT VARIANCE WITH PROJECT DOCUMENTATION. CONTRACTOR SHALL NOTIFY THE OWNER OF
ALL CONDITIONS NOT PER THE CONTRACT DOCUMENTS. EXAMPLES INCLUDE:
- SIZES OR DIMENSIONS OTHER THAN THOSE SHOWN
- DAMAGE OR DETERIORATION TO MATERIALS AND COMPONENTS
- CONDITIONS OF INSTABILITY OR LACK OF SUPPORT
- ITEMS NOTED AS EXISTING ON THE DRAWINGS BUT NOT FOUND IN THE FIELD
3C)PREPARE DIMENSIONAL DRAWINGS OF ALL DISCOVERED ITEMS.
3D)CONTRACTOR SHALL FIELD VERIFY ALL EXISTING STRUCTURAL CONDITIONS PRIOR TO SUBMITTING SHOP
DRAWINGS.
3E) CONTRACTOR SHALL MAKE ALLOWANCE FOR THE RESOLUTION OF SUCH DISCOVERIES IN THE
CONSTRUCTION SCHEDULE.
3F) SUBMIT A DIMENSIONED DRAWING OF ALL NEW OPENINGS THROUGH EXISTING STRUCTURE AND SECURE APPROVAL PRIOR TO CUTTING. NEW OPENING MAY BE EITHER SHOWN ON THE CONTRACT DOCUMENTS OR
PROPOSED BY THE CONTRACTOR. DRAWING SHALL SHOW:
- VERTICAL & HORIZONTAL LOCATION AND SIZE OF NEW OPENING(S)
- ALL EXISTING OPENINGS IN THE VICINITY OF THE NEW OPENING(S)
- ALL EXISTING STRUCTURE (BEAMS, COLUMNS, SLABS, WALLS, ETC) IN THE VICINITY OF THE NEW OPENING(S)
- ALL REINFORCING BAR SIZES AND POSITIONS (LAYOUT LOCATION AND DEPTH) CONFLICTING WITH OR IN THE
VICINITY OF THE NEW OPENING(S).
4) COORDINATION:
4A) COORDINATE DIMENSIONS OF ALL OPENINGS, BLOCKOUTS, DEPRESSIONS, ETC., WITH FIELD CONDITIONS
PRIOR TO SHOP DRAWING SUBMITTAL.
5) SUBMITTALS AND SUBSTITUTIONS:
5A) SUBMITTALS:
- IF THE CONTRACTOR REQUESTS A CHANGE FROM THE STRUCTURAL DRAWINGS, IT SHALL BE APPROVED BY THE OWNER AND DESIGNED BY MARTIN/MARTIN, INC. PRIOR TO SUBMITTING SHOP DRAWINGS. VARIATION SHALL
BE INDICATED ON THE SHOP DRAWINGS.
- CONSTRUCTION DOCUMENTS SHALL NOT BE REPRODUCED FOR USE IN SUBMITTALS
- ALL SHOP DRAWINGS SHALL REFERENCE THE STRUCTURAL DRAWING NUMBER AND DETAIL USED TO
PREPARE THE SUBMITTAL
5B) SUBSTITUTIONS: OWNER’S APPROVAL SHALL BE SECURED FOR ALL SUBSTITUTIONS
5C)NONCONFORMANCE: NOTIFY OWNER OF CONDITIONS NOT CONSTRUCTED PER THE CONTRACT DOCUMENTS PRIOR TO PROCEEDING WITH CORRECTIVE WORK. SUBMIT PROPOSED REPAIR TO THE OWNER FOR
ACCEPTANCE.
5D)THE FOLLOWING SUBMITTALS ARE REQUIRED:
- CONCRETE DESIGN MIXTURES PER ACI. FOR EACH CONCRETE AND GROUT MIXTURE (INCLUDE: MIX ID#, MIX PROPORTIONS, W/C RATIO, TOTAL AIR CONTENT, SLUMP, F'c TEST). SUBMIT ALTERNATE DESIGN MIXTURES WHEN CHARACTERISTICS OF MATERIALS, PROJECT CONDITIONS, WEATHER, TEST RESULTS, OR OTHER CIRCUMSTANCES WARRANT ADJUSTMENTS. INCLUDE MATERIAL CERTIFICATES (CEMENTITIOUS MATERIALS, ADMIXTURES, REPAIR MATERIALS) AND MATERIAL TEST REPORTS FOR AGGREGATES INDICATING THE
AGGREGATE IS NOT POTENTIALLY REACTIVE.
- STEEL REINFORCING SHOP DRAWINGS.
- POST INSTALLED ANCHOR PRODUCT DATA.
- FIBERGLASS GRATING & BEAM PRODUCT DATA
5E) ALL SHOP DRAWINGS SHALL BE SUBMITTED IN ELECTRONIC FORMAT ONLY.
6) TEMPORARY CONDITIONS, CONSTRUCTION ENGINEERING, AND OSHA STANDARDS:
6A) THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION AND IS DESIGNED ONLY FOR
LOADS ANTICIPATED DURING THE STRUCTURE’S SERVICE LIFE.
6B) THE CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL TEMPORARY BRACING AND/OR SUPPORT THAT MAY BE REQUIRED AS THE RESULT OF THE CONTRACTOR’S CONSTRUCTION METHODS AND/OR SEQUENCES.
CONTRACTOR SHALL PROVIDE ALL REQUIRED ENGINEERING AND OTHER MEASURES TO ACHIEVE THE MEANS, METHODS, AND SEQUENCES OF WORK WHICH MAY INCLUDE, BUT IS NOT LIMITED TO:
- LAYOUT
- DESIGN FOR FORMWORK AND SHORING
- DESIGN OF CONCRETE MIXES
- DESIGN OF TEMPORARY BRACING OF WALLS FOR WIND, SEISMIC, OR SOIL LOADS
- SURVEYING TO VERIFY CONSTRUCTION TOLERANCES
- EVALUATION OF TEMPORARY CONSTRUCTION LOADS ON STRUCTURE DUE TO EQUIPMENT AND MATERIALS
- STRUCTURAL ENGINEERING TO RESIST ANY OTHER LOADS NOT IDENTIFIED ON DESIGN DRAWINGS
6C)NOTHING SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE CONSTRUED AS ELIMINATING THE NEED FOR THE CONTRACTOR TO COMPLY WITH ALL OSHA REQUIREMENTS. WHERE THE STRUCTURAL DRAWINGS APPEAR TO CONFLICT WITH OSHA REQUIREMENTS, THE STRUCTURAL DRAWINGS REPRESENT FINAL CONDITIONS ONLY.
- THE CONTRACTOR SHALL ADD ALL NECESSARY BRACING, ETC., AS WELL AS CLOSURES FOR OPENINGS. IN
ADDITION, PROTECT ANYTHING THAT MAY BE CONSIDERED A TRIP HAZARD.
1) CODES AND STANDARDS:
1A) GENERAL DESIGN
- INTERNATIONAL BUILDING CODE 2012
2) GRAVITY LOADS
- GROUND SNOW LOAD = 60 PSF
3) SEISMIC LOADS
- SEISMIC DESIGN CATEGORY = D
- RISK CATEGORY = II
- EARTHQUAKE IMPORTANCE FACTOR, le = 1.00
- MAPPED SPECTRAL RESPONSE ACCELERATION, Ss = 69.40 %g
- MAPPED SPECTRAL RESPONSE ACCELERATION, S1 = 20.30 %g
- DESIGN SPECTRAL RESPONSE COEFFICIENT, SDs = 0.576
- DESIGN SPECTRAL RESPONSE COEFFICIENT, SD1 = 0.270
- SOIL SITE CLASS = D
4) WIND LOADS
- RISK CATEGORY = II
- BASIC ULTIMATE WIND SPEED, Vult = 115 mph
- BASIC NOMINAL WIND SPEED, Vasd = 89.1 mph
- EXPOSURE CATEGORY = C
1) MOLDED FIBERGLASS GRATING:
1A) CONSTRUCTION TYPE: MOLDED SQUARE
1B) RESIN: POLYESTER, VINYL ESTER, FIRE RETARDANT WITH CLASS A FLAME RATING OF 25 OR LESS
PER ASTM E-84
1C) ACCESSORIES: CLIPS & FASTENERS PER MANUFACTURER
2) PULTRUDED FIBERGLASS BEAMS:
2A) CONSTRUCTION TYPE: PULTRUDED FIBERGLASS STRUCTURAL WIDE FLANGE SECTION BY DYNAFORM
OR EQUIVALENT
2B) RESIN: POLYESTER OR VINYL ESTER, FIRE RETARDANT WITH CLASS A FLAME RATING OF 25 OR LESS
PER ASTM E-84
2C) MECHANICAL PROPERTIES:
- TENSILE STRESS = 30,000 PSI PER ASTM D-638
- FLEXURAL STRESS = 30,000 PSI PER ASTM D-790
- MODULUS OF ELASTICITY = 2.8x10^6 PSI
- SHEAR MODULUS = 0.450x10^6 PSI
Martin/Martin, Inc. considers that design data is only in its final form on plotted drawings with original signatures and professional certification being visibly present on the drawings. Data supplied via computer generated format does not contain this approval or certification. The receiver of electronically transmitted drawings is responsible for verifying the information contained within the electronic data against the recorded or approved documents.
The use of electronically transmitted drawings is considered to be at your own risk. Martin/Martin, Inc. assumes no responsibility for any claims or damages resulting from your use of this information. Electronic information is provided for the convenience of the recipient only. The recipient of this file agrees that the information may not be transferred to any other party.
SHEET
M M
J O
B
P
R
IN
C
IP
A L:
E O
R
P R
O
JE
C T
M A
N A
G E
R
D E
S
IG
N E
R S
LE
A D
R E
V
IT
T E
C H
D
A T
E P
R
IN
T E
D
F
IL
E P
A T
H
REVISION STATUS DATE
PROJECT:
SHEET TITLE:
DESCRIPTION
PREPARED BY:
MARTIN/MARTIN CONSULTING ENGINEERS 12499 W. COLFAX AVE, LAKEWOOD, CO 80215
DATE DESIGNED DRAWN CHECKED DRAWING NO.
OFDATEREV DESCRIPTION BY
06/21/20190 CONSTRUCTION DOCUMENTS M/M
M. TALMAGE L. VERENINI M. PIPER
6/
/2
5:
:1
P
M C
:\P ro j\1 9.
.S .0
1- B oz em an F is h
T ec hn ol og y
C en te r_
S
_g bu rr el l@ m ar tin m ar tin .c om .rv t
BOZEMAN FISH TECHNOLOGY CENTER
06/21/2019
S-001
GENERAL NOTES
M T al m ag e
G B ur re ll
M M cA ffr ey
.0
0.
S
.0
M P ip er
L V er en in i
EPOXY COATING OF REINFORCING A775 OR A934 - - -
WELDED & FIELD BENT REINF A706 60 80 -
TYP REINFORCING A615 60 90 -
REINF ELEMENT ASTM Fy (KSI) Fu (KSI) COMMENTS
REINFORCING MATERIAL TABLE
CWA = CRYSTALLINE WATERPROOF ADMIXTURE, MASTERLIFE 300D BY BASF (OR EQUIVALENT).
MCI = MAXIMUM CHLORIDE ION LIMIT: 0.10 FOR CONCRETE IN WATER RETAINING STRUCTURES.
MSS = MAXIMUM SHRINKAGE STRAIN: SHRINKAGE STRAINS SHALL NOT EXCEED 0.046%
d. ABBREVIATIONS FOR OTHER REQUIREMENTS AS FOLLOWS:
c. WHERE AIR CONTENT IS INDICATED IN THE MIX TABLE, PROVIDE AIR ENTRAINING ADMIXTURE. TOTAL AIR CONTENT LIMITS INCLUDE BOTH ENTRAINED AND ENTRAPPED AIR ± 1 1/2%. AIR CONTENT NOTE IS BASED
ON 3/4" AGGREGATE. IF 3/8" AGGREGATE IS USED, INCREASE AIR CONTENT BY 1 1/2%.
3/4”: #67 AGGREGATE
b. FOR THE MAXIMUM COARSE AGGREGATE SIZE INDICATED, USE THE FOLLOWING AGGREGATE SIZE
NUMBERS PER ASTM C33:
a. UP TO 25% TYPE F FLY ASH IS PERMITTED
FOR CONCRETE PLACED BY PUMPING PROVIDE CONCRETE MIX FLOWABILITY TO FACILITATE PUMPING.
ENTRAINED AIR MAY BE USED TO FACILITATE PUMPING SUBJECT TO THE PROVISIONS OF NOTE c BELOW.
USE TYPE I/II OR TYPE V PORTLAND CEMENT.
- PROVIDE WORKABILITY AND CONSISTENCY TO PERMIT CONCRETE TO BE WORKED READILY INTO FORMS
AND AROUND REINFORCEMENT UNDER CONDITIONS OF PLACEMENT TO BE EMPLOYED, WITHOUT
SEGREGATION OR EXCESSIVE BLEEDING. CONTRACTOR SHALL SELECT APPROPRIATE SLUMP. USE
ADMIXTURES AS REQUIRED TO OBTAIN DESIRED RESULTS.
- PROVIDE THE MINIMUM COMPRESSIVE STRENGTH AS INDICATED IN THE MIX TABLE. DO NOT EXCEED THE
MAXIMUM WATER-CEMENT RATIO NOTED.
PROPORTIONS OF MATERIALS IN CONCRETE MIX SHALL BE ESTABLISHED TO:
CONCRETE MIX TABLE NOTES:
WATER RETAINING
STRUCTURES 4.5 NWC 0.45 3/4 4.5
MCI MSS
CWA
CONC
MIX
TYPE
INTENDED USE
28 DAY
STRENGTH
f'c (KSI)
CONC
WEIGHT
MAX W/C
RATIO,
INCLUDING
FLY ASH,
NOTE a
MAX
AGGREGATE
SIZE (IN),
NOTE b
TOTAL AIR
CONTENT
(%), NOTE c
OTHER
REQTS,
NOTE d
CONCRETE MIX TABLE
STRUCTURAL DRAWING LIST
DESIGN CRITERIA
SYMBOLS LEGEND
GENERAL NOTES CONCRETE NOTES
SHEET NUMBER SHEET NAME
S-001 GENERAL NOTES
S-100 PLAN & DETAILS
S-101 DETAILS
FIBERGLASS NOTES
June 21, 2019
S-100
S-100
S-100
11'-0"
56'-0"
27'-0"
20'-0"
FIBERGLASS FLUE
NORTH TANK
SOUTH TANK
SUMP PIT
S-101
TYP AT CHUTE
OUTLET
EXISTING WATER TROUGH
MS-S-200
LINE OF EXCAVATION BY
CONTRACTOR
3'-0" WIDE x 0'-6" DEEP
OVERFLOW WEIR
VE
RI
FY
I N
FI
EL
D
9' -0
8' -0
"(4
LO
C
S
S-101
S-101
S-101
S-101
9' -0
9' -0
S-100
6x 6x
1/
W F
F R
P
2"x2: SLOTS (2 LOCATIONS)
2"x2" SLOTS (10 LOCATIONS)
2' -0
6" 6"
'-0
8'-0"
6" 6"
HYDROPHILIC WATER
STOP, CENTERED
2" C
LR
3"
C
LR
2" CLR2" CLR
#6@8" VERT EA
FACE, EPOXY
COATED
#6@8" HORIZ EA
FACE, EPOXY
COATED
(E) WATER TROUGH
McNICHOLS MS-S-200 OR
EQUIVALENT FIBERGLASS MOLDED
GRATING WITH 2"x2" SQUARE GRID
SIZE, LOAD RATED AT 100 PSF @
4'-0" SPAN
6x6x1/4 PULTRUDED
FIBERGLASS WIDE
FLANGE BEAM BY
DYNAFORM, OR
EQUIVALENT
PREPARED COMPACTED
SOIL, 95% OF MAXIMUM
DENSITY PER ASTM D698
#6@8" EA WAY EA
FACE, EPOXY
COATED
(2) 3/8"Ø x 3 1/4"
EMBEDMENT SCREW
ANCHORS (TYPE 316
STAINLESS STEEL) AT
3" GAGE, TYP EA END
F CLIPS W/ 1/4" Ø STAINLESS
STEEL BOLTS BETWEEN
GRATING PANELS @ 2'-0" OC
MAX
M CLIPS W/ 1/4" Ø x 2-1/4"
BOLT @ 4'-0" OC MAX,
MINIMUM OF (4) HOLD
DOWN CLIPS PER
GRATING PANEL
4" 1 1/2"
8"
8"
9'-0"
8"
HYDROPHILIC WATER
STOP, CENTERED2"
C
LR
2" CLR
(E) CONC WALLS
2" CLR
4' -7
A
T N
O R
T H
T A
N K
5' -9
A
T S
O U
T H
T A
N K
2" C
LR
(E) WATER TROUGH
#5@12" VERT,
EPOXY COATED
#5@12" HORIZ,
EPOXY COATED
#5@12" EA WAY,
EPOXY COATED
EXISTING SLAB, WALLS &
TROUGH TO REMAIN,
REMOVE & REPLACE AS
REQUIRED FOR SUMP
PIT INSTALLATION
SEE 3/S-100 FOR
WALL REINFORCING
SEE 2/S-100 FOR SUMP PIT
WALL REINFORCING
4/S-100
3/S-100
TEMPORARY SHORING
BY CONTRACTOR (4)
SIDES
Martin/Martin, Inc. considers that design data is only in its final form on plotted drawings with original signatures and professional certification being visibly present on the drawings. Data supplied via computer generated format does not contain this approval or certification. The receiver of electronically transmitted drawings is responsible for verifying the information contained within the electronic data against the recorded or approved documents.
The use of electronically transmitted drawings is considered to be at your own risk. Martin/Martin, Inc. assumes no responsibility for any claims or damages resulting from your use of this information. Electronic information is provided for the convenience of the recipient only. The recipient of this file agrees that the information may not be transferred to any other party.
SHEET
M M
J O
B
P
R
IN
C
IP
A L:
E O
R
P R
O
JE
C T
M A
N A
G E
R
D E
S
IG
N E
R S
LE
A D
R E
V
IT
T E
C H
D
A T
E P
R
IN
T E
D
F
IL
E P
A T
H
REVISION STATUS DATE
PROJECT:
SHEET TITLE:
DESCRIPTION
PREPARED BY:
MARTIN/MARTIN CONSULTING ENGINEERS 12499 W. COLFAX AVE, LAKEWOOD, CO 80215
DATE DESIGNED DRAWN CHECKED DRAWING NO.
OFDATEREV DESCRIPTION BY
06/21/20190 CONSTRUCTION DOCUMENTS M/M
M. TALMAGE L. VERENINI M. PIPER
6/
/2
5:
:2
P
M C
:\P ro j\1 9.
.S .0
1- B oz em an F is h
T ec hn ol og y
C en te r_
S
_g bu rr el l@ m ar tin m ar tin .c om .rv t
BOZEMAN FISH TECHNOLOGY CENTER
06/21/2019
S-100
PLAN & DETAILS
M T al m ag e
G B ur re ll
M M cA ffr ey
.0
0.
S
.0
M P ip er
L V er en in i
1/8" = 1'-0"
FOUNDATION PLAN
3/4" = 1'-0"
SUMP PIT
3/4" = 1'-0"
NORTH & SOUTH TANK SECTION
NORTH
1/4" = 1'-0"
SOUTH TANK TO SUMP PIT
A
A
ADD 1/2 NUMBER OF
BARS INTERRUPTED
BY OPENING PLUS 1,
SPACE AT 3" OC
DETAIL SIMILAR
FOR CIRCULAR
OPENINGS
NOTES:
1. DETAIL APPLIES UNLESS REINFORCING IS SPECIFICALLY DETAILED ON THE DRAWINGS
2. HOOK BARS WITH STANDARD HOOK WHERE LTS CANNOT BE ACHIEVED
H , 3
'-0
M A
X
T Y
P
LT
S
H
TYPICAL OPENING (WALL ELEVATION)
D NOTE 1
MAX
12"
N O
T E
ALIGN
PENETRATIONS
VERTICALLY AND
HORIZONTALLY
EDGE OF WALL
(BOTTOM,
OPENING, ETC.)
NOTES:
1. GREATER OF 2xD AND 12", WHERE CLEAR DISTANCE IS NOT ACHIEVABLE, TREAT
AREA AS SINGLE OPENING REINFORCED PER "TYPICAL OPENING" DETAIL
2. DO NOT CORE OPENINGS, SLEEVE OPENINGS PRIOR TO PLACING CONCRETE
3. DO NOT CUT REBAR AT PENETRATION LOCATIONS. REBAR MAY BE MOVED 8" MAX TO
ACCOMMODATE PENETRATIONS
4. SCHEDULE 40 STEEL SLEEVES SHALL BE USED IN CRITICAL AREAS OF THE WALL AND
SLABS AS DETERMINED BY STRUCTURAL ENGINEER OF RECORD
E D
G E
S , T
Y P
F R
O M
A
LL
TYP EACH WAY
2" CLR TO REINFORCING,
NOTE 2
AT OPENINGS 12" OR LESS
(WALL ELEVATION)
TYP
LTS+W W, 3'-0" MAX 3" TYP
CONTINUOUS BAR OR
SPLICE TO MATCH TYPICAL
WALL HORIZONTAL SIZE &
SPACING LT
S
LTS LTS
LTS
LT
S
LTS
LT
S
AT (1) LAYER OF REINF AT (2) LAYERS OF REINF
INSIDE FACE INSIDE FACE
ALUMINUM CHUTE
BY CONTRACTOR
2"x2" SLOT x FULL
HEIGHT, CENTERED IN
WALL
1" 2"
HILTI KWIK HUS HR 6,
STAINLESS STEEL W/
2 3/16" MIN EMBEDMENT
@ 1'-0" OC
2"
2x LUMBER BY OWNER
2" 2"
3" CLR
NOTES:
1. ALL BENDS SHALL BE MADE COLD
2. #14 & #18 BARS SHALL BE BEND TESTED &
LAB APPROVED PRIOR TO BENDING
STANDARD BENDS
90° HOOK (#3-#5)
d
3" MIN
6d
STIRRUP/TIE BENDS
180° HOOK (#3-#8)
D2
MAX OFFSET BEND
D1
#3 - #8 6d
#9 - #11 8d
90° HOOK (#6-#8)
d
12d
D2
135° HOOK (#3-#8)
d
3" M
IN6d
D2
90° HOOK
d d
D1
180° HOOK
d
2 1/2" MIN
4d
D1
#3 - #5 4d
#6 - #8 6d
D2 d D2
2 1/2" MIN
4d
Martin/Martin, Inc. considers that design data is only in its final form on plotted drawings with original signatures and professional certification being visibly present on the drawings. Data supplied via computer generated format does not contain this approval or certification. The receiver of electronically transmitted drawings is responsible for verifying the information contained within the electronic data against the recorded or approved documents.
The use of electronically transmitted drawings is considered to be at your own risk. Martin/Martin, Inc. assumes no responsibility for any claims or damages resulting from your use of this information. Electronic information is provided for the convenience of the recipient only. The recipient of this file agrees that the information may not be transferred to any other party.
SHEET
M M
J O
B
P
R
IN
C
IP
A L:
E O
R
P R
O
JE
C T
M A
N A
G E
R
D E
S
IG
N E
R S
LE
A D
R E
V
IT
T E
C H
D
A T
E P
R
IN
T E
D
F
IL
E P
A T
H
REVISION STATUS DATE
PROJECT:
SHEET TITLE:
DESCRIPTION
PREPARED BY:
MARTIN/MARTIN CONSULTING ENGINEERS 12499 W. COLFAX AVE, LAKEWOOD, CO 80215
DATE DESIGNED DRAWN CHECKED DRAWING NO.
OFDATEREV DESCRIPTION BY
06/21/20190 CONSTRUCTION DOCUMENTS M/M
M. TALMAGE L. VERENINI M. PIPER
6/
/2
5:
:2
P
M C
:\P ro j\1 9.
.S .0
1- B oz em an F is h
T ec hn ol og y
C en te r_
S
_g bu rr el l@ m ar tin m ar tin .c om .rv t
BOZEMAN FISH TECHNOLOGY CENTER
06/21/2019
S-101
DETAILS
M T al m ag e
G B ur re ll
M M cA ffr ey
.0
0.
S
.0
M P ip er
L V er en in i
3/4" = 1'-0"
CAST IN PLACE WALL PENETRATIONS
3/4" = 1'-0"
CROSS WALL DETAIL
3/4" = 1'-0"
WALL CORNER DETAIL
3/4" = 1'-0"
TANK CHUTE OUTLET
12" = 1'-0"
TYPICAL REINFORCING BENDS & LAP SPLICES
'LTS' = TENSION LAP SPLICE LENGTH
'LDH' = HOOK DEVELOPMENT LENGTH
ABBREVIATIONS:
#6 16" 42"
#5 14" 34"
#4 12" 28"
BAR SIZE LDH LTS
LAP SPLICE SCHEDULE
| Sheets |
| S-001 - GENERAL NOTES |
| S-100 - PLAN & DETAILS |
| S-101 - DETAILS |