ADDITIONS AND CLARIFICATIONS

1. Steel pipe specification: 2 7/8 inch diameter. Used Drill pipe stem is acceptable.

2. Single wood posts should be referred to as single steel post with brace.

3. Caps on pipe – contractor will provide and install metal caps to post suitable to prevent water and debris from entering post.

4. Metal H – brace structures – cross wiring in not required.

5. Pipe construction depth - four foot minimum, or until refusal.

6. T-Post specification: 1.33 gauge with heavy plate or spade.

7. All gates require a mechanical latch for closure.

8. All gates require two gate sticks constructed of 1 7/8 in schedule 40 pipe minimum, four strand barbed wire, 16 feet in length.

9. On portions of fence contract where existing wire is acceptable and does not require replacement, existing wire spacing is also acceptable.

10. Use of crimp connectors for tightening of existing fence wire is acceptable.

11. The north end of the fence will be the starting point (near Nancy Russell Creek Bay

(formerly Squaw Creek)).