Fire_Alarm_Inspection_Report_06_02_21_0001.pdf
PDF 539 KB Posted
- Attached to
- Fire Alarm Testing and Maintenance Federal contract opportunity
- Solicitation number
- 140D8122Q0002
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| AWWU_Report_06_02_21_0001.pdf | ||
| Sprinkler_Inspection_Report_06_02_21_0001.pdf | ||
| Amended_Exhibit_1_0001.pdf | ||
| Main_Bldg_Hangar_2nd_Floor_0001.pdf | ||
| Secondary_Hangar_0001.pdf | ||
| Sol_140D8122Q0002_Amd_0001.pdf | ||
| Main_Bldg_Hangar_1st_Floor_0001.pdf | ||
| B03_WD_2015-5681_Rev_14.pdf | ||
| Sol_140D8122Q0002.pdf | ||
| B08_SOL_140D8122Q0002_Fire_Alarm_Mx.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Office of Aviation Services
No.
07155 www.gocanvas.com 9980416A-0C21-4C5B-8A85-1956637A844A
5887 E. Blue Lupine Dr.
Palmer, , AK 99645
907-373-1760 www.taylorfire.com
Fire Alarm Inspection Report Status
Status
Date
06/02/2021 Time
13:13
Owner /Client / Contracting Agency
Name
Office of Aviation Services Address 1
4405 Lear Court Address 2
City
Anchorage State
AK
Zip
99502
Representative
Bryant Telephone
907-382-1781 Fax
Property Name (User)
Name
Office of Aviation Services Address 1
4405 Lear Court Address 2
Anchorage City
Anchorage State
Contact
Bryant Telephone
907-382-1781 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
07155 www.gocanvas.com 9980416A-0C21-4C5B-8A85-1956637A844A
AK
Zip
AK
Monitoring Entity
Contact / Agency
TYCO
Telephone
Monitoring Account Ref. No.
023749745
Approving Agency
Contact
Bryant Telephone
907-382-1781
Service
Service
Annually Other (Specify)
Prior To Any Testing Notifications Are
Made To Other (Specify) Yes/No Who Time
Monitoring Entity Yes 13:15 Fire Department Yes 13:15
Type Transmission
Type Transmission
Digital Other (Specify)
Control Panel
Control Panel Manufacturer
Simplex Control Panel Model
Control Panel Location
Entry
Is Panel in "normal" conditions upon arrival?
Yes Circuit Styles
Slc Number of Circuits
Software Rev.
Last Date System Had Any Service Performed
Last Date that Any Software or Configuration Was Revised
No.
07155 www.gocanvas.com 9980416A-0C21-4C5B-8A85-1956637A844A
Printer
Printer Model
None Location
Did Printer Function Properly
Is Printer Supervised?
Alarm-Initiating Devices and Circuit Information Description If Other
(Specify) Quantity of
Devices Installed
Quantity of Devices Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Manual Fire Alarm Boxes
15 15 15
Smoke Detectors 52 52 52 Heat Detectors 6 6 6 Waterflow Switches
1 1 1
Supervisory Switches
2 2 2
Other Beam detectors 2 2 2
Alarm Verification
Alarm Verification feature is
Alarm Notification Appliances & Circuit Info Description If Other
(Specify) Quantity of Appliances
Installed
Quantity of Appliances
Tested
Quantity of Devices Passed
Quantity of Devices
Failed
Circuit Style
Horn/Strobes 53 53 52 1 Bells 1 1 1 Horns 1 1 1 Decibel Levels
Location Description Ambient Level Alarm Level Office areas 96db
Alarm Notification Circuits
No. of alarm notification appliance circuits
Are circuits monitored for integrity?
Yes
Control Equipment Description of
Equipment If Other (Specify)
Quantity Installed
Quantity Tested Quantity Passed Quantity Failed
Elevator Recall 2 2 2 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
07155 www.gocanvas.com 9980416A-0C21-4C5B-8A85-1956637A844A
Initiating Device Circuit
Quantity
N/A Style(s)
Signaling Line Circuits
Quantity and style of signaling line circuits connected to system (see 2007 NFPA 72, Table 6.6.1) Quantity
Style(s)
System Primary Power Supply
(a) Primary (Main) Location (of Primary Supply Panelboard)
Electrical room panel 1b ckt 23 Nominal Voltage
Amps
Overcurrent Protection Type
Overcurrent Protection Amps
Disconnecting Means Location
Secondary (standby) Power Supply Type Location Battery
Dated:
Storage Battery:
Amp Hour Rating
Battery Type
Other Battery
Type
Calculated capacity in Amp-Hours to operate system for 24 hours.
Calculated capacity in Amp-Hours to operate system for 60 hours.
Control Panel In panel 2019 12ah Sealed Lead- Acid
Booster Panel
1fl electrical 2019 7ah Sealed Lead-
Booster Panel
2nd floor electrical
2018 7ah Sealed Lead-
Secondary (standby) Power Primary Power Supply Location of
Primary Power Supply
(Distribution Panel)
Nominal Voltage of Primary Power
Supply
Amps of Primary Power Supply
Overcurrent Protection Type
Overcurrent Protection Amps
Disconnecting Means Location
Generator System http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
07155 www.gocanvas.com 9980416A-0C21-4C5B-8A85-1956637A844A
Engine-driven generator dedicated to fire alarm system.
Location of fuel storage:
Other Backup
(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:
Emergency system described in NFPA 70, Article 700
Legally required standby described in NFPA 70, Article 701 Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701
Transient Suppressors
Transient Suppressors Visual
Comments
Central Station Monitoring Type of Signal Yes/No Time Comments
Alarm Signal Yes 13:21 Notifications That Testing is Complete Notification Given
To Other (Specify) Yes/No Who Time
Building Management Yes 13:21 Monitoring Agency Yes 13:22
Deficiencies and Issues
The following did not operate correctly
Horn strobe just inside office 208 did not sound during alarm.
Recommend replacement System restored to normal operation
Date
06/02/2021 Time
13:22 http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
07155 www.gocanvas.com 9980416A-0C21-4C5B-8A85-1956637A844A
Pictures
Photo 1
Photo 1 Description
Alarm panel
Photo 2
Photo 2 Description
Location of horn strobe that failed
Photo 3
Photo 3 Description
Model number of horn strobe needing replacement
Notes and Recommendations
Notes and Recommendations
Could not test beam detectors with filters as they were not on site. Tested with remote test stations underneath beam detectors Plan of Corrective Action:
Corrective Action and Date Taken:
Inspector Information http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link
No.
07155 www.gocanvas.com 9980416A-0C21-4C5B-8A85-1956637A844A
This testing was performed in accordance with (Standard/Edition)
Nfpa 72-2019 Name of Inspector
Robert Doehler License Number
13-021
Date
06/02/2021 Time
13:24
Inspector Signature
Inspector Signature
Owner or Representative Information
Name of Owner or Representative
Bryant Date
06/02/2021
Time
13:24
Owner or Representative Signature
Owner or Representative Signature http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link http://www.gocanvas.com/?utm_source=canvas_pdf&utm_medium=pdf_link&utm_campaign=canvas_pdf_link