Attachment_4_-_Q&A.pdf

PDF 39 KB Posted

Attached to
PCLOB - IT HVAC/UPS PMI&W Services Federal contract opportunity
Solicitation number
140D0419Q0067
Issued by
Department of the Interior Departmental Offices Interior Business Center

About this file

Added Attachment 4 Q&A.

View the file

Other files for this federal contract opportunity

Other files attached to PCLOB - IT HVAC/UPS PMI&W Services, newest first.
File Type Posted
140D0419Q0067_Amendment_0004.pdf PDF
Attachment_1_-_Site_Visit_Q&A.pdf PDF
RFQ_140D0419Q0067_Revised_03.01.19.pdf PDF
Attachment_3_-_Pricing_revised_03.01.19.pdf PDF
Attachment_1_-_SOW_Revised_03.01.19.pdf PDF
140D0419Q0067_Amendment_0002.pdf PDF
Attachment_3_-_Pricing_Revised.pdf PDF
140D0419Q0067_Amendment_0001.pdf PDF
RFQ_140D0419Q0067.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers Posted March 1, 2019

Q1. Please confirm no special clearance or finger printing will be required for technicians onsite.

A1. No special clearances required, vendor will be escorted by PCLOB staff.

Q2. Please confirm there are trade specific certifications required to perform the work.

A2. HVAC/ UPS tech vendor must be licensed or certified for equipment supported.

Q3. Is the contractor required to provide refrigerant for the HVAC units?

A3. Yes, if needed to maintain operational effectiveness.

Q4. For remote monitoring, what data/points should be monitored? Does a standalone space temperature sensor suffice or is unit status or other points desired?

A4. Due to security concerns, this is no longer a requirement for the vendor.

Q5. Who should receive the alarms? Just the contractor, specific POCs, etc.

A5. Due to security concerns, this is no longer a requirement for the

Q6. Will an internet connection be provided for remote monitoring? If not, would a cellular solution be acceptable?

A6. Due to security concerns, this is no longer a requirement for the

Q7. What existing controls interface is available on the HVAC units?

Status contact, BACnet interface, etc.

A7. Due to security concerns, this is no longer a requirement for the

Q8. How many UPS systems are there for service on this contract?

A8. 1 unit