A-2_SOW.docx
DOCX document 7 MB Posted
- Attached to
- Upgrade HVAC controller software Federal contract opportunity
- Solicitation number
- 1333ND18QNB680168
About this file
NIST Requirements
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| CLIN_0002_Humidity_Sensors_Manuel.pdf | ||
| CLIN_0003_Operation_Process.pdf | ||
| CLIN_0002_Humidifier_Specifications.pdf | ||
| CLIN_0003_Panel_Picutres_and_Flow_Process.docx | DOCX document | |
| B-3_Amendment_0001_.docx | DOCX document | |
| CLIN_0002_HVAC_Manuel.pdf | ||
| B-2_Combined_Synopsis_Solicitation_CO_rdc_edits.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NIST Requirements Upgrade HVAC controller software
I. Background The Dimensional Metrology Group (DMG) performs many critical calibrations each year, and develops documentary standards for evaluating dimensional measurement systems. To achieve these goals the need to maintain the environmental conditions in the laboratories at precise settings for temperature and humidity are required. As these systems age they need to be replaced or upgraded to maintain reliable operation, or due to failure.
II. Scope The DMG requires an upgrade to the HVAC controller software and computers in three (3) NIST laboratories, and services to repair or replace the humidifier system in the Letiz CMM lab (BLDG 220/A12) and the API Lab (BLDG 220/B05). Within these labs they need new computers with specialized software and hardware to interface and control the existing heating, ventilation and air conditioning (HVAC) systems.
III. Minimum Requirements The products shall meet or exceed the minimum requirements identified below. Selection of automation application to be used shall be either Alerton, Andover, Siemens, Automated Logic. All devices must be new. Used or remanufactured equipment will not be considered for award. Experimental, prototype, or custom items will not be considered. The use of “gray market” components not authorized for sale in the U.S. by the Contractor is not acceptable. All line items shall be shipped in the original manufacturer’s packaging and include all original documentation and software, when applicable.
Contract Line Item Number (CLIN) 0001: The Contractor shall upgrade the existing HVAC software, provide a new interface computer, and provide a new interface card in the Dilatometer lab, if necessary, (BLDG 220/B13 Figure 1) in accordance with the following minimum specifications:
1. Supply an automation software to control an existing HVAC system.
2. Configure and furnish a new computer, with Windows 10 operating system and compatible automation software application installed, to operate and control HVAC system.
3. Connect new computer to existing wiring harness for currently installed Control Systems International 7718 PCU Direct Digital Controller HVAC controller boards for lab, Figure 2.
4. Integrate control points from 7718 PCU to new HVAC automation software, current system uses I/NET software
5. Supply Graphical interface for lab and reporting system. The interface shall perform the following functions:
a) Allow the user to adjust setpoints for temperature
b) Record and display the temperatures measured from each sensor in the laboratory, as well as their average, and plot data on a XY graph vs. time
c) Record and display lab humidity and plot the data on a XY graph vs. time.
d) A screen showing the lab floor plan with temperature sensors, humidity sensors, average space temperatures, humidity, and any other applicable setpoints in their installed locations shall be provided
e) A screen showing HVAC schematic that will display real-time temperatures for return air, cooling coil air exit, and post reheat, along with air handling unit (AHU) status, reheat percentages, and other applicable points.
6. Automation application shall control temperature setpoints on a user defined schedule/ range, from 15C to 30C, and hold at that set point for a defined time interval, (i.e. Start at 15C and hold for 5 hours, then adjust to 17C and hold for 5 hours, and adjust to 20C and hold for 5 hours, as examples). The temperature setpoints and sensing devices used to maintain setpoints, shall have a tolerance of .01C +/-setpoint
7. Up to 4 hours of training shall be provided to NIST staff on how to use software.
Figure 1: Dilatometer lab is contained in large white box
Figure 2: CSI 7718 PCU DDC for Dilatometer lab
CLIN 0002: The Contractor shall upgrade the HVAC software, provide a new interface computer for the HVAC system, and provide new steam humidifiers in the Leitz CMM Lab (BLDG 220/A12) and API Lab (BLDG 220/B05) in accordance with the following minimum specifications (See Appendix A for drawings related to system):
1. Supply an automation software to control an existing HVAC system.
2. Configure and furnish a new computer, with Windows 10 operating system and compatible automation application software installed, to operate HVAC system.
3. Connect new computer to existing wiring harness for currently installed Control Systems International 7718 PCU Direct Digital Controller HVAC controller boards for lab, Figure 3.
Figure 3: CSI 7718 PCU DCC for API CMM Lab
4. Integrate control points from CSI 7718 PCU to new HVAC automation software, current system uses Docutrend 7000 Software.
5. Supply Graphical interface and reporting system for each lab. The interface shall perform the following functions at a minimum:
a) Allow the user to adjust setpoints for temperature; 15C -30C +/-.01C tolerance and humidity between 40-50% RH +/- 3%.
b) Record and display the temperature measured from each sensor in the laboratory, as well as their average, and plot data on a XY graph vs. time
c) Record and display lab humidity and plot the data on a XY graph vs. time.
d) A screen showing the lab floor plan with temperature sensors, humidity sensors, average space temperatures, humidity, and any other applicable setpoints in their installed locations shall be provided
e) A screen showing HVAC schematic will display real-time temperatures for return air, cooling coil air exit, and post reheat, along with air handling unit (AHU) status, reheat percentages, and other applicable points.
6. Replace two (2) steam humidifiers (live steam plant), one for each lab, Figure 4.
Figure 4: Example of non-functional steam trap for one of the CMM labs
CLIN 0003: The Contractor shall upgrade the software, provide a new interface computer, and provide a new interface card, if necessary, in the Tape Tunnel lab (BLDG 220/C03) in accordance with the following minimum specifications:
1. Supply an automation software to control and existing HVAC system
2. Configure and furnish a new computer, with Windows 10 and automation software installed, to operate HVAC system, Figure 5.
3. Connect new computer to existing wiring harness for currently installed Control Systems International 78010-C TAP HVAC controller boards for lab, Figure 6.
4. Integrate control points from CSI 78010-C TAP
5. Supply Graphical interface for lab and reporting system. The interface shall perform the following functions at a minimum:
a) Allow the user to adjust setpoints for temperature and humidity
b) Record and display the temperature measured from each sensor in the laboratory, as well as their average, and plot data on a XY graph vs. time
c) Record and display lab humidity and plot the data on a XY graph vs. time.
d) A screen showing the lab floor plan with temperature sensors, humidity sensors, average space temperatures, humidity, and any other applicable setpoints in their installed locations shall be provided
6. A screen showing HVAC schematic will display real-time temperatures for return air, cooling coil air exit, and post reheat, along with air handling unit (AHU) status, reheat percentages, and other applicable points
Figure 5: Existing computer connection to HVAC controller for Tape Tunnel
Figure 6: CSI 78010-C TAP
IV. Inspection/Acceptance In addition to the inspection and acceptance terms articulated in 52.212-4, the Government reserves the right to perform such performance tests and evaluations as defined below to verify specified system performance. Such tests and evaluations, if performed, shall be conducted within the environment that the system is to be operated. The Contractor has the right to be present during the tests and evaluations, if performed, at the Contractor’s expense. The following tests shall be performed:
· Each room/laboratory will be inspected prior to the installation for temperature stability, performance, as is conditions and operations. There shall be no degradation of performance once the new operating system(s), application software, devices, and equipment detailed in above CLN definitions, found in prior statements. Temperatures in these labs, when operational, is typically controlled to the following tolerances:
1. 20 (+/- 0.15) degrees Celsius for the Tape Tunnel (220/C03), when evaluated on the tape bench, with a sensor at 10 meter intervals from 0 to 60 meters; a total of 7 sensors, and control humidity to below 50%RH +/- 3%, for a period of 24 hours.
2. 20 (+/- 0.05) degrees Celsius for the Leitz Lab (220/A12) and API Lab (220/B05) when evaluated at the center of the measurement volume of each measurement machine currently installed in these labs (800x1000x600 mm for the lab in 220/A12 and 800x600x500 mm for the lab in 220/B05), and control humidity to between 40-50% RH +/- 3%, for a period of 24 hours.
3. 15-30 (+/-0.01) degrees Celsius for the Dilatometer lab, at three points along the center of the measurement volume of the machine, which is 1000mm x 500mm x 500mm for a period of 24 hours
· After installation of the software and hardware listed in Section 2, each room/laboratory will be re-inspected to ensure that temperature and humidity is controlled to specifications listed above
· Humidity control function in the two labs receiving the new units will also be verified for function using methods recommended by vendor and/or manufacturer.
The Government reserves the right to (witness) Contractor Performance Verification Testing. (PVT). PVT shall be developed by contractor and submitted for approval by COR prior to conducting quality assurance testing. To confirm that the products meet the stated performance specifications. All Contractor PVT will be completed within thirty (30) days of the completion date of the installation. Acceptance by Government will not occur until analytical data proves new systems integration is meeting this statement of work specifications as are related to environmental control and tolerances.
V. Period of Performance and Place of Performance The Contractor shall deliver and install all components within sixteen (16) weeks after the issuance of Notice to Proceed.
Performance and materials shall be delivered/completed at NIST, 100 Bureau Drive, Gaithersburg, MD in the building and rooms indicated on each CLIN.
VI. Security
NIST is a restricted campus. An identification badge is required for access for entry into buildings and also is shown to the armed Security Police when entering the campus. Contractor personnel must wear the identification badge issued by NIST Security while working at any NIST campus.
REGULAR BUSINESS HOURS
Regular business hours are Monday through Friday, 8:00 am to 5:00 pm local time.
VII. Vehicle Registration
All Contractor employees must register their vehicles with the NIST Security Office to gain access to the campus. A valid driver’s license, Government-furnished civilian ID, proof of insurance and current registration must be presented to the NIST Security Office, at which time a NIST vehicle pass will be issued. The pass shall be displayed on the vehicle in accordance with NIST Security Office instructions.
VIII. Warranty One (1) year warranty shall be provided to ensure that installed software and hardware are free from defects and is fully operational. Coverage period will begin once all the installed hardware has passed acceptance.
IX. Payment Schedule The Contractor shall be paid, in accordance with Net 30-day payment terms, upon receipt and acceptance of a proper invoice, in accordance with the following schedule:
1. 100% after receipt and acceptance by the technical point of contact (TPOC) of fully installed system and Government acceptance.
2. The Government anticipates inspection will occur upon:
a. After all testing requirements set forth in this document have been completed and the system has demonstrated operation to the required specifications.
X. Appendix
A. Drawings for CLIN 0002
Figure 7: Air Flow, refrigeration and piping
Figure 8: Typical wiring drawings and Hardware interface diagram
Figure 9: PCU 1 Interface panel diagram
Figure 10: Control diagram for one Leitz CMM Lab (220/A12) image3.tiff image4.tiff image5.tiff image6.jpeg image7.emf image8.emf image9.emf image10.emf image1.tiff image2.tiff