Is this supposedly a 2088 model number? And an “S1” option requires 1199 model number. Transmitter model 2088 is required for both CLIN 1 & 2. The S1 option designates the requested seal system for the transmitter which is 1199. The selected options for the 1199 seal system if different for CLIN 1 & 2. See attached doc for full model number with selected options for both.
See product datasheet below for reference
Rosemount™ 2088 Absolute and Gauge Pressure Transmitter
Rosemount™ DP Level Transmitters and 1199 Diaphragm Seal Systems
RTD w/ transmitter and level switch model numbers – See attached doc for full model number with selected options.
• For both sets of pressure transmitters, what are the intended calibration ranges? Calibration from 0 – 150psi. Below snip is from the original factory calibration of the existing pressure transmitters. Calibration completed in 30 psi increments.
• Do we need to include any tag #’s? Provide standard manufacturer tags/nameplate data. No project specific information is required. See attached photos for examples of existing.
• For the temperature sensor and transmitter, do you need these directly assembled? Do you need a thermowell included in this assembly? The temperature sensor and transmitter need to be assembled but a thermowell is not required. The model number which indicates selected options of the current installed and assembled sensors/transmitters are in the attached doc.
o If so, what is the process connection size and rating if flanged? What immersion length is needed and overall sensor length? See full model number that indicates selected options.
• For the level switch, are you able to advise the model #? See attached doc for full model number with selected options.
https://gcc02.safelinks.protection.outlook.com/?url=https%3A%2F%2Fwww.emerson.com%2Fdocuments%2Fautomation%2Fproduct-data-sheet-rosemount-2088-absolute-gage-pressure-transmitter-en-73236.pdf&data=05%7C01%7C%7Ca4395a398f8b402438d608db679c9ffe%7Ced5b36e701ee4ebc867ee03cfa0d4697%7C0%7C0%7C638217694902492340%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C3000%7C%7C%7C&sdata=iJk%2BEhzKYHwX2%2Bgrzvg4LXmArrrm5Tpxy6RNFDjLskI%3D&reserved=0 https://gcc02.safelinks.protection.outlook.com/?url=https%3A%2F%2Fwww.emerson.com%2Fdocuments%2Fautomation%2Fproduct-data-sheet-rosemount-dp-level-transmitters-1199-seal-systems-en-73226.pdf&data=05%7C01%7C%7Ca4395a398f8b402438d608db679c9ffe%7Ced5b36e701ee4ebc867ee03cfa0d4697%7C0%7C0%7C638217694902492340%7CUnknown%7CTWFpbGZsb3d8eyJWIjoiMC4wLjAwMDAiLCJQIjoiV2luMzIiLCJBTiI6Ik1haWwiLCJXVCI6Mn0%3D%7C3000%7C%7C%7C&sdata=G%2FuluP2D%2FaU6USy6nNc%2FPjPkRtpvW7imb2yJd248nnM%3D&reserved=0