Questions from Industry 12805B23Q0168 As of 9 February 2023

1. Are there any specifications for this project which tell us the duct heater sizes and models or makes approved?

Govt Response: Duct heaters may need to be custom built. Based on the 200amp disconnect requirement, they should be about 50kw, 208v/3 phase. Ensure that measurements are taken during the site visit to ensure proper fitting.