1a Salient Features Existing Equipment.pdf

PDF 4 MB Posted

Attached to
Waste Water Fine Screen and Sludge Conveyor System Federal contract opportunity
Solicitation number
12805B22Q0349
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery Plains Area

View the file

Other files for this federal contract opportunity

Other files attached to Waste Water Fine Screen and Sludge Conveyor System, newest first.
File Type Posted
Sol_12805B22Q0349_Amd_0001.pdf PDF
Solicitation_12805B22Q0349.pdf PDF
Attachment 1 SPECIFICATIONS.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

12'-0"

2'-8

3'-8"

VENT OUTLET

6" w/FERNCO

TYPE COUPLING

SLUDGE OUTLET

2'-7

4'-4

4'-10

WATER REJECT

4" w/FERNCO

TYPE COUPLING

HOT WATER INLET FROM

HOT WATER HEATER

1/2" FPT

INLET

4", CLASS 150#

OUTLET

6", CLASS 150#

11'-4

5'-1

4'-3

4'-3

1'-7

2'-8

1'-7

(3) PLS

5'-0

DUCT TO ODOR

CONTROL UNIT

SEE M-SERIES

3" HDPE INFLUENT

FROM EQ TANK

FLOW METER

3" HDPE SLUDGE

AND WETLANDS

RECYCLE LINES

10'-1"

8'-5

7'-4" 1'-11

25°

SAFETY PULL

CHORD 110V AC

SAFETY PULL

CORD 110V AC

6" ODOR CONTROL

CONN.

4" DRAIN TO

FLOOR DRAIN

SYSTEM

4" DRAIN TO

FLOOR DRAIN

SYSTEM

4" LINE TO FLOOR

DRAIN SYSTEM

4'-8"

WORK SPACE

(TYP)

2X PIPE

DIAMETER

MIN.

3" HDPE INFLUENT

FROM EQ TANK

6" HDPE EFFLUENT TO

TRICKLING FILTERS SEE CW5001

FOR GRAVITY PIPE INLET

3" HDPE PRESSURE

RECYCLE LINE TO

EQ TANK

5X PIPE

DIAMETER

MIN.

3" BALL VALVE

INFLUENT SHUT OFF

FLOW METER

36"

MIN.

2X PIPE

DIAMETER

MIN.

5X PIPE

DIAMETER

MIN.

PSC

3-051

PSC

3-051

PSC

3-051

E

A

Approver Name Signed & Sealed By :

THE ATTACHED MATERIALS CONTAIN DEPARTMENT OF HOMELAND SECURITY INFORMATION THAT IS "FOR OFFICIAL USE ONLY", OR OTHER TYPES OF SENSITIVE BUT UNCLASSIFIED INFORMATION REQUIRING PROTECTION AGAINST UNAUTHORIZED DISCLOSURE. THE ATTACHED MATERIALS WILL BE HANDLED AND SAFEGUARDED IN ACCORDANCE WITH DHS MANAGEMENT DIRECTIVES GOVERNING PROTECTION AND

DISSEMINATION OF SUCH INFORMATION.

AT A MINIMUM, THE ATTACHED MATERIALS WILL BE DISSEMINATED ONLY ON A "NEED TO KNOW" BASIS AND WHEN UNATTENDED, WILL BE STORED IN A LOCKED CONTAINER OR AREA OFFERING SUFFICIENT PROTECTION AGAINST THEFT, COMPROMISE, INADVERTENT ACCESS AND UNAUTHORIZED DISCLOSURE.

Project Status:

Copyright © 2009 NDP8 97654321 10

FOR OFFICIAL USE ONLY

Approvals Stamps &

B

C

D

F

G

H

E

A

B

C

D

F

G

H

8 97654321 10 W

:\N

BA

F

\C ur re nt\

NB

AF

W as tew ate r - T re atm en t -

D eta ils

Ea st.

dw g

Project Information

Rev. No.Sheet Number

Sheet TitleSheet Information Sheet Issue Date:

Project Package:

Drawn By: Checked By:

NDP Firm Internal Project Number: 06604-00

Client Project Number:

Project Name: Department of Homeland SecurityLGL07C00004

NBAF Client Name:

05/23/14

ISSUED FOR CONSTRUCTION

GMP #3 (LAB + OUTBUILDINGS)

GENERAL SHEET NOTES

SHEET KEYNOTES

NSI/JL NSI/PM 7-CW5007

FOR CONSTRUCTION

SCREEN FILTER

SCALE : NONE

SCREEN FILTER

NOTES:

1. BELT FILTER SHALL BE INSTALLED UPON A LEVEL FOUNDATION WITH

ANCHOR BOLTS. FOUNDATION SHALL HAVE A MINIMUM LOAD BEARING

CAPACITY OF 1,325 LB. ALL PLUMBING TO BE INSTALLED PER UPC.

2. 3'-4" RECOMMENDED MINIMUM HEIGHT ABOVE FILTER FOR FILTER BELT

SERVICE WINCH.

PART TABLE

1. ROTATING BELT FILTER

480 V, 3 PHASE, 20 AMP

WITH HOT WATER HEATER

480 V, 3 PHASE, 15 AMP

SEE SPEC. 44 43 33

2. FLOW METER (TYP 2)

MODEL: MG-47038

AVAILABLE FROM: USA BLUE BOOK

SEE SPEC. 40 91 23.33

3. SLUDGE CONVEYOR

AVAILABLE FROM: ENVIRONMENTAL PROCESS

EQUIPMENT CO.

SEE SPEC. 44 46 13

N-1. ALL GRAVITY LINES IN CW-SERIES

DRAWINGS TO BE HDPE TYPE SDR 21

UNLESS SPECIFIED OTHERWISE.

N-2. ALL PRESSURE PIPES IN CW-SERIES

DRAWINGS TO BE HDPE SDR 17 UNLESS

SPECIFIED OTHERWISE.

Rev Date Description

NOT USED THIS SHEET-1

-2

POST BID REVISION01/30/153

NOT USED THIS SHEET

PSC-GMP-05106/24/164

PBR

PBR

REF. RFI-1374

Route to sanitary system via indirect waste

Blue Water is Now Nexom

Blue Water Technologies, Inc. | 10450 North Airport Road | Hayden, Idaho 83835 | www.bluewater-technologies.com|

( ) 888.710.2583 | ( ) 208.209.0396 |

Blue Water is Now Nexom As of September 7, 2016 Blue Water’s assets have been acquired by Nexom Incorporated. All contact information including emails and phone numbers are still active. For more information about the acquisition see http://nexom.com/news/bluewater.

Scope of Supply SECTION: 44 46 13, Sludge Conveyors

ADDENDA: N/A

ITEM: "A" - One (1) WAM Flo-Spiral Shaftless Conveyor, Model FSC250, to include:

• U-trough of 304SS @ 25o incline

• 9” diameter shaftless auger of alloy steel with end flange connection

• Wear liner of 3/8” thick 304SS wear bars

• U-trough covers of 304SS

• Inlet hopper of 304SS

• Flanged discharge

• 4” drain at inlet end with flushing valve

• Spray system with 3 nozzles

• Support legs/feet

• Gear reducer driven by 480V, 3Ph, 2 hp TEFC motor (motor suitable for Class I, Division 1 [CID1] area)

HARDWARE:

Fasteners and anchor bolts of 304SS

ELECTRICAL CONTROLS AND DEVICES

Qty (1) NEMA 4X 304SS control panel wall-mounted enclosure suitable for 480VAC/3Ph/60Hz electrical supply Qty (1) brass body wash water ½” solenoid valve, suitable for CID1 area Qty (1 Lot) E-stop cable system with (1) RS1X SP/DT, no light, orange vinyl cable and fittings, suitable for CID1 area Qty (1 Lot) Milltronics Zero Speed Switch complete with MFA-4P motion failure alarm control

(not suitable for CID1) and XPP-5 probe (suitable for CID1)

7-CW5007 As-Built
1a EM-3
Solids Conveyor_Submittal Sheet

File details come from the government source that posted it. Updated .