Attachment 4 - QA 1240LT21Q4002 - Sunshine Water Replacement.pdf

PDF 422 KB Posted

Attached to
Sunshine Water System Replacement Federal contract opportunity
Solicitation number
1240LT21Q4002
Issued by
Department of Agriculture Forest Service

View the file

Other files for this federal contract opportunity

Other files attached to Sunshine Water System Replacement, newest first.
File Type Posted
1240LT21Q4002-0002.pdf PDF
1240LT21Q4002-0001.pdf PDF
Attachment 3 - WD CO20210001.pdf PDF
Attachment 1 - Sunshine CG Water System Replacement - Specifications.pdf PDF
Attachment 2 - Sunshine CG Map and Drawings.pdf PDF
Attachment 3 - WD AK20210001.pdf PDF
RFQ 1240LT21Q4002 - Sunshine Water System Replacement.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1240LT21Q4002

Sunshine Water Replacement

Questions and Answers August 19, 2021

Question 1: Do you know the depth of the well?

Answer 1: The well at Sunshine campground is 122 feet deep, with a perforated casing from 91 feet to 122 feet.

Question 2: Will the tanks highlighted needed for the project?

Answer 2: All of the item in the “Key Notes” on drawing U-0 will need to be furnished and installed by the contractor, including the highlighted items: chemical container, chemical spill container, and the three baffle tanks. The highlighted tanks in the treatment system layout on drawing U-0 (three baffle tanks, and one pressure tank), shall be furnished and installed by the contractor.

Question 3: What size are the Baffle tanks?

Answer 3: Each baffle tanks shall be 119 gallons.

Question 4: The spec section 221124 refers to 119 gallon Indoor potable water tanks. Are these tanks the baffle tanks below? If not, the what size are the baffle tanks?

Answer 4: Yes, the “119 gallon indoor potable water tanks” referred to in specification section 221124, are the baffle tanks.

Question 5: Would there be an option to provide a proposal for an alternative of polyethylene tanks for all the tanks needed for this project?

Answer 5: The design for the Sunshine Water System has already been approved by the Colorado Department of Public Health and Environment (CDPHE). We may be able to accept an alternative tank, but any proposed alternative tank(s) would need to be listed as a Pre-Accepted Treatment Facility water system component on CDPHE’s Pre-Accepted Non-Community Groundwater Source/Chlorine Disinfection/Storage Drinking Water Design Submittal (page 24 of 24), which can be viewed at the following link:

https://drive.google.com/file/d/1go_E7Rge73wV9lUVtRISUlrTiQcdld9f/view?usp=drive_web.

Furthermore, any proposed alternative baffle tank will need to have a baffle factor of 0.7, as recognized by the State of Colorado.

File details come from the government source that posted it. Updated .