Q and A_Air Handler Unit Repair.pdf

PDF 129 KB Posted

Attached to
Air Handler Unit Repairs Federal contract opportunity
Solicitation number
12405B24Q0001
Issued by
Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery

About this file

This document contains questions and answers regarding Solicitation 12405B24Q0001 for air handler unit repairs issued by the Department of Agriculture Agricultural Research Service Field Research Implementation and Information Delivery. The solicitation involves repairing two air handler units including replacing components such as variable frequency drives, TXV powerheads, and liquid driers if required for proper operation. Controls work will be provided separately by Siemens through the USDA. Model and serial numbers are provided for the chillers and air handlers. No specific safety or quality plans are required from contractors in response.

View the file

Other files for this federal contract opportunity

Other files attached to Air Handler Unit Repairs, newest first.
File Type Posted
Attachment A_SOW Air Handler Unit Repair.pdf PDF
RFQ_12405B24Q0001_Air Handler Unit Repairs.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Questions and Answers

Solicitation 12405B24Q0001

Air Handler Unit Repair

October 31, 2023

1. Will the contractor be responsible for the HVAC controls?

A. The chillers are controlled by a Siemens system that is separate from this contract. We had the system upgraded a few months ago and it is ready to go.

2. Will the USDA coordinate the HVAC controls separately from this contract?

A. Once the contract is awarded, the plan is to have Siemens and the awardee here at the same time to both work through the system.

3. Has the HVAC controls portion of the project been reviewed by the current control’s contractor to verify functionality?

A. Yes

4. Do the controls currently function?

A. They do, and they are “on” for the purposes of the chiller testing. However, potential awardees will not be able to modify controls as that is done only by Siemens or a representative (we don’t have the software to do it).

5. What are the model number and serial numbers for the chillers and air handlers?

A. Chiller: serial, STNU151200061, model AGZ030EPMME-E00; Air handlers: serial, FBOU161101134 and FBOU161101135, model OAHOO3GDGC.

6. Is this project tax exempt?

A. Yes

7. Is a project specific accident prevention, safety, health, and environmental plan required?

A. No

8. Is a project specific quality assurance plan required?

A. No

9. Can one superintendent cover all supervision, safety, and quality assurance duties?

A. Yes

10. What is OSHA training/certification requirement for contractor’s superintendent/safety personnel?

A. I didn’t think there is a requirement for a specific OSHA training certificate. If there is, disregard.

11. Existing fan motor in AHU #2 is in working order and to be installed as-is. Please confirm.

A. I cannot confirm this. I would assume it is not working.

12. Power conductors for fan motor in AHU #2 are in working order and will be reused. Please confirm.

A. I cannot confirm this. I would assume it is not working.

13. Contractor is to replace-in-kind VFD in AHU #2 with OEM part. Please confirm.

A. Yes

14. No troubleshooting or investigation is required to determine cause for failure of VFD in AHU #2.

Please confirm.

A. No

15. Does USDA wish to replace inline dryers while replacing TXV powerheads?

A. If they are required for proper operation, yes.

16. Controls work, if required, will be provided by others (Siemens) through USDA.

A. Yes

17. Should the liquid driers be replaced on the chillers once the repairs are completed?

A. If they are required for proper operation, yes.