Text version
Salient Characteristics
For
Colorado Air National Guard (COANG)
140th Wing Facilities
Buckley AFB, CO
Airfield Lighting Regulators
20 May 2021
1.0 DESCRIPTION OF SERVICES
The supplier will provide two new airfield lighting constant current regulators and delivery to Buckley Air Force Base, Colorado. Regulators are required to be ADB Safegate model number CHF2070-5300 in accordance with the attached Brand Name Justification. ADB Safegate is the only manufacturer of 70KW regulators that are FAA approved per FAA circular AC 150/5345-53D dated February 2021.
1.1 REGULATOR REQUIREMENTS
a. 70KW 5 Step Constant Current Regulators
b. 20 Amp Output- (step 1 is 8.5 amps, step 2 is 10.3 amps, step 3 is 12.4 amps, step 4 is 15.8 amps, step 5 is 20 amps)
c. Input 480V/3 Phase/60Hz
d. Regulator Control Voltage is 120 Volts
e. Face of the regulator will include manual control and an analog current meter
f. Ferro-Resonant Air Cooled
g. Integratable with ADB Safegate ACE2 Lighting System
h. Environmental Operating Conditions are -40℉ to 130℉, 10 to 95% humidity, and an altitude of 5,600ft.
i. If main power is lost, regulator will resume operation within 5 seconds of restoration of power
j. Surge Protection for Input and Output Circuits
k. Monitor for and cease operation for open circuit condition
l. Must be incompliance with FAA L-828/L829 AC 150/5345-10 and UFC 3-535-01 standards.
m. Complies with the Buy American Act
1.2 The contractor shall provide a copy of all technical/service/maintenance manuals.
1.3 The contractor shall provide a separately priced line item for a five-year warranty on the equipment.
1.4 The regulators shall be delivered to Buckley AFB.
File details come from the government source that posted it. Updated .