Z1DA--Correct UST Deficiencies 583-23-509
Closed Pre-Solicitation Posted
This opportunity was awarded. See the award notice from , or the latest solicitation from .
- Solicitation number
- 36C25023B0050
- Agency
- Veterans Integrated Service Network 10 Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- Service-Disabled Veteran-Owned Small Business
Opportunity facts
- NAICS code
- 236220 Commercial and Institutional Building Construction
- Place of performance
- Richard L. Roudebush VA Medical Center 1481 W. 10th Street
Notice details come from SAM.gov. Updated .
About this opportunity
This pre-solicitation notice from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 seeks a contractor to correct underground storage tank deficiencies at the Richard L. Roudebush VA Medical Center in Indianapolis, Indiana. The contractor must provide all labor, materials and equipment to perform work including underground storage tank and aboveground storage tank repairs and upgrades, rerouting day tank emergency vents, painting exterior aboveground storage tanks, installing sump sensors and entry boots, replacing spill buckets and overfill valves, and upgrading cathodic protection systems. The estimated value is between $250,000 and $500,000. The solicitation is scheduled to be issued on April 13, 2023.
This requirement is fully set aside for Service-Disabled Veteran-Owned Small Businesses. The NAICS code is 238220 - Plumbing, Heating, and Air-Conditioning Contractors and the PSC code is R499 - Other Facility Related Services. The procurement is valued between $250,000 and $500,000 and must be completed by an SDVOSB. Plans and specifications will be available electronically with no cost to potential offerors.
Notice text
Description proposed work.
Contractor shall completely prepare site for building operations, to include labor and materials to perform work for Project# 583-23-509, Correct UST deficiencies; work includes UST and AST repairs to become compliant with deficiencies listed in the technical requirements below:
UST #1 C-Wing South
Icon Containment Watertight Sump Lid Installation & Icon Split Repair Entry
Spill Bucket & Overfill valve replacement
Emco A1004EVR-317SS103 5 Gallon Double Wall Spill Containment
OPW 61SOC-4011 Overfill Valve
Remove and Replace Concrete 6 x 5 x 8 Boots
UST #2 & #6 A-Wing South
Tank Sump Sensor Installation
Veeder Root 794380-352 Sump Sensors
Required Electrical
Icon Entry Boot Replacement
Tank sump crack repair
UST #3 D-Wing
Entry Boot Replacement
Icon spilt repair entry boot installation
UST #4 C-Wing NE
Overfill Valve replacement
OPW 61SO-4011 Overfill Valve
UST #5 A-Wing Building 19
Tank Sump Sensor Installation
Veeder Root 794380-352 sump sensors
Day Tank Emergency Vents (All Day Tanks)
Re-route existing day tank emergency vents (primary and secondary) to building exterior per NFPA 30, Install 4 schedule 40 steel piping, Install Morrison Model 246 4 /8oz emergency vents, Seal wall with link seal and fire caulk if applicable
Upgrade Cathodic Protection on UST #1 C-Wing South
Painting of Exterior AST, Sand existing paint to remove rust, Re-paint areas of concern with urethane paint
The estimated magnitude of construction is between $250,000 and $500,000.
Tentative dates for issuing invitation.
The VA plans to issue the solicitation on or about 4/14/23.
Will plans be available for inspection without charge?
The solicitation and all appliable information, drawings and specifications will be published electronically at no cost.
Date by which requests for the invitation for bids should be submitted.
Will be determined based on actual solicitation posting.
Restricted to small businesses?
This procurement is 100% set aside for Service-Disabled Veteran-Owned Small Business (SDVOSB) socio-economic concerns.
Amount to be charged for solicitation documents.
$0.00
Publicized through the Governmentwide point of entry?
Yes.
***END OF SYNOPSIS***
Attachments
| File | Type | Posted |
|---|---|---|
| 36C25023B0050.docx | DOCX document |
Notice history
| Notice | Type | Posted |
|---|---|---|
| Z1DA--Project No. 583-23-509 - Correct UST Deficiencies | Award Notice | |
| Z1DA--Correct UST Deficiencies 583-23-509 | Solicitation | |
| Z1DA--Correct UST Deficiencies 583-23-509 | Pre-Solicitation |
On GovTribe
Work this opportunity on GovTribe
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity