Spray foam insulation
Awarded Award Notice Posted
- Solicitation number
- W44W9M13T0075
- Agency
- Joint Munitions Command Army Materiel Command, Department of Defense
- Awarded
- to Blue Diamond Builders, Inc.
- Set-aside
- Total Small Business
Opportunity facts
- Contract number
- W44W9M13P0187 Federal contract award
- NAICS code
- 423390 Other Construction Material Merchant Wholesalers
- PSC
- Not on record
- Place of performance
- ACC - McAlester Contracting Office (ACC-RI-McAlester) Attn: Ccrc-IDM, 1 C Tree Road McAlester OK 74501 US
- More information
Notice details come from SAM.gov. Updated .
Notice text
2 versions
Update #2 · Latest ·
Added: Feb 26, 2013 3:11 pm
Modified: Mar 07, 2013 3:19 pmTrack Changes
This is a combined synopsis/solicitation for commercial items prepared in accordance with the format in Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; proposals are being requested and a written solicitation will not be issued.
CLOSED CELL, EXPANDING, SPRAY FOAM INSULATION, FOAM TO INCLUDE INSTALLATION. FOAM TO BE SPRAYED ON THE FOLLOWING LOCATIONS BY PROFESSIONAL INSTALLER. BUILDING 180.
2 walls - 16 FT X 60 FT
5 walls - 10 FT X 51 FT
1 ceiling - 7 FT X 60 FT
TOTAL SFT: 4,890 SFT
All locations are to be sprayed to a maximum of 5 inches depth to an R value of no less than 20. Vendor will need approximately 150-200 feet of hose to reach all areas that require foam insulation.
Sprayed foam must withstand 125 degree temperatures.
Update #1 ·
Added: Feb 26, 2013 3:11 pm
This is a combined synopsis/solicitation for commercial items prepared in accordance with the format in Subpart 12.6, as supplemented with additional information included in this notice. This announcement constitutes the only solicitation; proposals are being requested and a written solicitation will not be issued.
CLOSED CELL, EXPANDING, SPRAY FOAM INSULATION, FOAM TO INCLUDE INSTALLATION. FOAM TO BE SPRAYED ON THE FOLLOWING LOCATIONS BY PROFESSIONAL INSTALLER. BUILDING 180.
2 walls - 16 FT X 60 FT
5 walls - 10 FT X 51 FT
1 wall - 15 FT X 40 FT
1 wall - 10 FT X 15 FT
1 ceiling - 7 FT X 60 FT
All locations are to be sprayed to a maximum of 5 inches depth to an R value of no less than 20.
Sprayed foam must withstand 125 degree temperatures.