STATEMENT OF WORK (SOW)
The Department of Veteran Affairs VA Medical Center located in Chillicothe, OH, has a requirement for two (2) replacement Air Chillers (a Trane RTAF-115 and a Trane RTAE-150). The Chillers will be located at Bldg. 31 and Bldg. 211.
This is a Service Disabled Veteran Owned Small Business (SDVOSB) set-aside.
FOB: Destination (VA Medical Center, 17273 State Route 104, Chillicothe, OH 45601). New equipment only, all items must be quoted, brand name or equal. If submitting Equal, the provisions of clauses 52.212-2 and 852.211-73 must be followed exactly. Evaluation based on technically acceptable, compatible with existing system. Scroll compressors are not acceprtable.
All responses must be submitted by email, to contact listed below, by noon Monday, September 28, 2015.
See attached.
Current building automation system is configured and uses Tridium based JACE controllers.
For Bldg. 31:
Trane RTAF-115
RTAF air-cooled screw chiller
Unit startup
115 nominal tons
60 hertz
460V/60Hz/3 phase
High efficiency
Minimum efficiency at AHRI conditions
Full Load: 10.0 EER
Part Load: 15.8 EER
UL listed to US and Canadian safety std
ASME pressure vessel code
Refrigerant charge R-134a
AHRI certified
ASHRAE 90.1 all versions compliant
Standard cooling
2 pass evaporator
Fluid type - propylene glycol
Grooved pipe
Factory installed flow switch fluid other than water - 15 cm/s
Factory insulation-all cold parts 0.75 inch
Wide ambient
Microchannel coil
Variable speed fans
Oil cooler
Variable speed screw compressors required for part load operation
Single point power connection
Circuit breaker
Default amp short circuit rating
BACnet MS/TP interface (Tracer compatible)
Programmable relay
2nd-5th year compressor parts
1st year labor warranty whole unit
Startup and training included
Bldg. 211
Trane RTAE-150
Air-cooled Series R model RTAE
150 ton single circuit
200 volt 3 phases 60 Hertz
Minimum efficiency at AHRI conditions
Full Load: 10.7 EER
Part Load: 19.7 EER
UL listed to US and Canadian Safety Standard
ASME pressure vessel code
Refrigerant charge HFC-134a
AHRI certified
ASHRAE 90.1 - all versions compliant
Standard cooling (40 to 65F/4.4 to 18C)
2 pass evaporator
Factory installed flow switch - glycol fluid (15 cm/s)
Factory insulation - all cold parts 0.75"
Wide ambient (0 to 125F)
Aluminum fins with slits
Variable speed screw compressors required for part load operation
Adaptive Frequency Drive 3rd generation
Single point connection main line unit power-ancillary items require other power
Circuit breaker high fault rated panel
High amp short circuit rating 65,000 amps
Factory installed transformer
Line reactors (~30% TDD)
BACnet MS/TP interface (Tracer compatible)
Architectural louvered panels
Elastomeric isolators
2nd-5th year compressor parts
1st year labor warranty whole unit
Startup and training included
Update #2 ·
Added: Sep 23, 2015 12:30 pm
Modified: Sep 23, 2015 1:30 pmTrack Changes
STATEMENT OF WORK (SOW)
The Department of Veteran Affairs VA Medical Center located in Chillicothe, OH, has a requirement for two (2) replacement Air Chillers (a Trane RTAF-115 and a Trane RTAE-150). The Chillers will be located at Bldg. 31 and Bldg. 211.
This is a Service Disabled Veteran Owned Small Business (SDVOSB) set-aside.
FOB: Destination (VA Medical Center, 17273 State Route 104, Chillicothe, OH 45601). New equipment only, all items must be quoted, brand name or equal. If submitting Equal, the provisions of clauses 52.212-2 and 852.211-73 must be followed exactly. Evaluation based on technically acceptable, compatible with existing system. Scroll compressors are not acceprtable.
All responses must be submitted by email, to contact listed below, by noon Monday, September 28, 2015.
See attached.
Current building automation system is configured and uses Tridium based JACE controllers.
For Bldg. 31:
Trane RTAF-115
RTAF air-cooled screw chiller
Unit startup
115 nominal tons
60 hertz
460V/60Hz/3 phase
High efficiency
Minimum efficiency at AHRI conditions
Full Load: 10.0 EER
Part Load: 15.8 EER
UL listed to US and Canadian safety std
ASME pressure vessel code
Refrigerant charge R-134a
AHRI certified
ASHRAE 90.1 all versions compliant
Standard cooling
2 pass evaporator
Fluid type - propylene glycol
Grooved pipe
Factory installed flow switch fluid other than water - 15 cm/s
Factory insulation-all cold parts 0.75 inch
Wide ambient
Microchannel coil
Variable speed fans
Oil cooler
Variable speed screw compressors required for part load operation
Single point power connection
Circuit breaker
Default amp short circuit rating
BACnet MS/TP interface (Tracer compatible)
Programmable relay
2nd-5th year compressor parts
1st year labor warranty whole unit
Startup and training included
Bldg. 211
Trane RTAE-150
Air-cooled Series R model RTAE
150 ton single circuit
200 volt 3 phases 60 Hertz
Minimum efficiency at AHRI conditions
Full Load: 10.7 EER
Part Load: 19.7 EER
UL listed to US and Canadian Safety Standard
ASME pressure vessel code
Refrigerant charge HFC-134a
AHRI certified
ASHRAE 90.1 - all versions compliant
Standard cooling (40 to 65F/4.4 to 18C)
2 pass evaporator
Factory installed flow switch - glycol fluid (15 cm/s)
Factory insulation - all cold parts 0.75"
Wide ambient (0 to 125F)
Aluminum fins with slits
Variable speed screw compressors required for part load operation
Adaptive Frequency Drive 3rd generation
Single point connection main line unit power-ancillary items require other power
Circuit breaker high fault rated panel
High amp short circuit rating 65,000 amps
Factory installed transformer
Line reactors (~30% TDD)
BACnet MS/TP interface (Tracer compatible)
Architectural louvered panels
Elastomeric isolators
2nd-5th year compressor parts
1st year labor warranty whole unit
Startup and training included
Update #1 ·
Added: Sep 23, 2015 12:30 pm
STATEMENT OF WORK (SOW)
The Department of Veteran Affairs VA Medical Center located in Chillicothe, OH, has a requirement for two (2) replacement Air Chillers (a Trane RTAF-115 and a Trane RTAE-150). The Chillers will be located at Bldg. 31 and Bldg. 211.
This is a Service Disabled Veteran Owned Small Business (SDVOSB) set-aside.
FOB: Destination (VA Medical Center, 17273 State Route 104, Chillicothe, OH 45601). New equipment only, all items must be quoted, brand name or equal. If submitting Equal, the provisions of clauses 52.212-2 and 852.211-73 must be followed exactly. Evaluation based on technically acceptable, compatible with existing system. Scroll compressors are not acceprtable.
All responses must be submitted by email, to contact listed below, by noon Monday, September 28, 2015.
See attached.
Current building automation system is configured and uses Tridium based JACE controllers.
For Bldg. 31:
Trane RTAF-115
RTAF air-cooled screw chiller
Unit startup
115 nominal tons
60 hertz
460V/60Hz/3 phase
High efficiency
Minimum efficiency at AHRI conditions
Full Load: 10.0 EER
Part Load: 15.8 EER
UL listed to US and Canadian safety std
ASME pressure vessel code
Refrigerant charge R-134a
AHRI certified
ASHRAE 90.1 all versions compliant
Standard cooling
2 pass evaporator
Fluid type - propylene glycol
Grooved pipe
Factory installed flow switch fluid other than water - 15 cm/s
Factory insulation-all cold parts 0.75 inch
Wide ambient
Microchannel coil
Variable speed fans
Oil cooler
Variable speed screw compressors required for part load operation
Single point power connection
Circuit breaker
Default amp short circuit rating
BACnet MS/TP interface (Tracer compatible)
Programmable relay
2nd-5th year compressor parts
1st year labor warranty whole unit
Startup and training included
Bldg. 211
Trane RTAE-150
Air-cooled Series R model RTAE
150 ton single circuit
200 volt 3 phases 60 Hertz
Minimum efficiency at AHRI conditions
Full Load: 10.7 EER
Part Load: 19.7 EER
UL listed to US and Canadian Safety Standard
ASME pressure vessel code
Refrigerant charge HFC-134a
AHRI certified
ASHRAE 90.1 - all versions compliant
Standard cooling (40 to 65F/4.4 to 18C)
2 pass evaporator
Factory installed flow switch - glycol fluid (15 cm/s)
Factory insulation - all cold parts 0.75"
Wide ambient (0 to 125F)
Aluminum fins with slits
Variable speed screw compressors required for part load operation
Adaptive Frequency Drive 3rd generation
Single point connection main line unit power-ancillary items require other power
Circuit breaker high fault rated panel
High amp short circuit rating 65,000 amps
Factory installed transformer
Line reactors (~30% TDD)
BACnet MS/TP interface (Tracer compatible)
Architectural louvered panels
Elastomeric isolators
2nd-5th year compressor parts
1st year labor warranty whole unit
Startup and training included
Attachments
| File | Type | Posted |
|---|---|---|
| -6643.docx | DOCX document | |
| VA250-15-Q-0462-002.docx | DOCX document | |
| VA250-15-Q-0462-001.pdf | ||
| VA250-15-Q-0462-000.docx | DOCX document |
On GovTribe
Work this opportunity on GovTribe
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity