Portable Chiller Specs‐100 Ton:
‐Chiller to meet Buy America Act and be UL listed
‐Capacity: 1,200,000 BTU/H or 100 Tons
‐Voltage/Phase: 460 Volt/3PH
‐Air cooled with scroll compressors
‐EPA complaint refrigerant
‐Multi Stage, adjustable down to 25% capacity
‐Integrated, properly sized pump package with isolation valves for throttling chilled water flow.
‐Chiller and associated equipment fully mounted and secured on a properly sized air ride trailer that will handle weight capacity and dimensions of all equipment.
‐Integrated flow switch
‐Isolation valves, pressure gauges, and thermometers on chilled water inlet and outlet (or integrated digital thermometers within chiller).
‐Integrated bypass to provide operation of local or remote pumps.
‐Integrated stand‐alone control system.
‐Equipped with properly sized quick connect fittings on chilled water inlet and outlet with quick connect caps
‐Properly sized fused disconnects for chiller and pump package.
Portable Chiller Specs‐50 Ton:
‐Chiller to meet Buy America Act and be UL listed
‐Capacity: 600,000 BTU/H or 50 Tons
‐Voltage/Phase: 208‐230 Volt/3PH
‐Air cooled with scroll compressors
‐EPA complaint refrigerant
‐Multi Stage, adjustable down to 25% capacity
‐Integrated, properly sized pump package with isolation valves for throttling chilled water flow.
‐Chiller and associated equipment fully mounted and secured on a properly sized air ride trailer that will handle weight capacity and dimensions of all equipment.
‐Integrated flow switch
‐Isolation valves, pressure gauges, and thermometers on chilled water inlet and outlet (or integrated digital thermometers within chiller).
‐Integrated bypass to provide operation of local or remote pumps.
‐Integrated stand‐alone control system.
‐Equipped with properly sized quick connect fittings on chilled water inlet and outlet with quick connect caps
‐Properly sized fused disconnects for chiller and pump package.