Primary Switching Center (PSC)

RFQ is for the manufacture and delivery of two (2) each PSC, NSN 6110-01-493-3391, to APG, MD.

GENERAL EQUIPMENT DATA

NSN
6110-01-493-3391
Operating Temperature range
-25º F to +125º F
Storage Temperature range
-65º F to +150º F

Weight, Single PS * Comprised of:

- Primary Switch

- Housing

- Skidbase

* Cable and connector weights are not included 4,000 lbs

1,800 lbs 800 lbs 1,400 lbs

- SF6 (Sulfur Hexafluoride, Inorganic gas)
24 lbs (10.8 Kg)
Turnbuckle Hardware
40 lbs

Weight, Stacked Configuration (2 Primary Switches, each with Housing and Skid base, and 1 set of Stacking Hardware) 8,000 lbs

Length, Single PS Length, Stacked Configuration

104.00 in

104.00 in

Width, Single PS Width, Stacked Configuration

72.00 in

72.00 in

Height, Single PS
48.00 in
Height, Stacked Configuration
94.00 in

VOLTAGE RATINGS

Rating, kV

System Class
MAX
BIL
IEC
ANSI
12
15.5
15.5
95
24
27
29
125
36
38
38
150

AMPERAGE RATINGS FOR FAULT INTERRUPTERS AND LOAD INTERUPTERS

CATEGORY
VALUE
SHORT CIRCUIT
RMS SYMETRIC
16,000
FAULT INTERRUPTERS
CONTINUOUS
600
LOAD DROPPING
600
INTERRUPTING, RMS SYM.
16,000
DUTY-CYCLE FAULT
RMS ASYM
25,600
CLOSING, TEN-TIME
RMS SYM
16,000

LOAD

INTERRUPTER

SWITCHES

CONTINUOUS
600
LOAD DROPPING
600
INTERRUPTING, RMS SYM.
16,000
DUTY-CYCLE FAULT
RMS ASYM
25,600
CLOSING, TENTIME
RMS SYM
16,000
SHORT TIME, RMS
MOMENTARY, ASYM
25,600
ONE-SECOND, SYM
16,000