RFP No. W912PM-17-R-0001
SOF Special Tactics Facility, Phase 3
PN: 76514
Fort Bragg, North Carolina
Specifications – Volume 3 of 3 (Division 25 thru Division 41)
March 2017
SOF SPECIAL TACTICS FACILITY, PHASE 3 PN 76514 - Volume 3
PROJECT TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
DIVISION 25 - INTEGRATED AUTOMATION
25 10 10 UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END
AND INTEGRATION
DIVISION 26 - ELECTRICAL
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 23 00 SWITCHBOARDS AND SWITCHGEAR
26 24 13 SWITCHBOARDS
26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS
26 32 15.00 10 DIESEL-GENERATOR SET STATIONARY 100-2500 KW, WITH
AUXILIARIES
26 36 00.00 10 AUTOMATIC TRANSFER SWITCH AND BY-PASS/ISOLATION SWITCH
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING WITH LED
26 56 00 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 05 29.00 10 PROTECTIVE DISTRIBUTION SYSTEM (PDS) FOR SIPRNET
COMMUNICATION SYSTEMS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
31 00 00 EARTHWORK
31 05 22.00 06 GEOTEXTILES USED AS FILTERS
31 11 00 CLEARING AND GRUBBING
31 31 16 SOIL TREATMENT FOR SUBTERRANEAN TERMITE CONTROL
31 31 16.13 CHEMICAL TERMITE CONTROL
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 01 19 FIELD MOLDED SEALANTS FOR SEALING JOINTS IN RIGID
PAVEMENTS
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 23 AGGREGATE AND/OR GRADED-CRUSHED AGGREGATE BASE COURSE
32 12 10 BITUMINOUS TACK AND PRIME COATS
32 12 11 BITUMINOUS SURFACE TREATMENT
32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS
32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE
FACILITIES
32 16 13 CONCRETE SIDEWALKS AND CURBS AND GUTTERS
32 17 24.00 10 PAVEMENT MARKINGS
32 31 13 CHAIN LINK FENCES AND GATES
32 92 19 SEEDING
32 92 23 SODDING
32 93 00 EXTERIOR PLANTS
PROJECT TABLE OF CONTENTS Page 1
DIVISION 33 - UTILITIES
33 11 00 WATER DISTRIBUTION
33 16 15 WATER STORAGE STEEL TANKS
33 30 00 SANITARY SEWERS
33 40 00 STORM DRAINAGE UTILITIES
33 70 02.00 10 ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
DIVISION 41 - MATERIAL PROCESSING AND HANDLING EQUIPMENT
41 22 13.15 BRIDGE CRANES, OVERHEAD ELECTRIC, UNDER RUNNING
41 22 23.19 MONORAIL HOISTS
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 2
SECTION 01 42 00
SOURCES FOR REFERENCE PUBLICATIONS
11/14
PART 1 GENERAL
1.1 REFERENCES
Various publications are referenced in other sections of the specifications to establish requirements for the work. These references are identified in each section by document number, date and title. The document number used in the citation is the number assigned by the standards producing organization (e.g. ASTM B564 Standard Specification for Nickel Alloy Forgings). However, when the standards producing organization has not assigned a number to a document, an identifying number has been assigned for reference purposes.
1.2 ORDERING INFORMATION
The addresses of the standards publishing organizations whose documents are referenced in other sections of these specifications are listed below, and if the source of the publications is different from the address of the sponsoring organization, that information is also provided.
ACOUSTICAL SOCIETY OF AMERICA (ASA)
1305 Walt Whitman Road, Suite 300 Melville, NY 11747-4300 Ph: 516-576-2360 Fax: 631-923-2875 E-mail: asa@aip.org Internet: http://asa.aip.org
ALLIANCE FOR TELECOMMUNICATIONS INDUSTRY SOLUTIONS (ATIS)
1200 G Street, NW, Suite 500 Washington, D.C. 20005 Ph: 202-628-6380 Fax: 202-393-5453 E-mail: kconn@atis.org Internet: http://www.atis.org
AMERICAN ASSOCIATION OF STATE HIGHWAY AND TRANSPORTATION OFFICIALS
(AASHTO)
444 North Capital Street, NW, Suite 249 Washington, DC 20001 Ph: 202-624-5800 Fax: 202-624-5806 E-Mail: info@aashto.org Internet: http://www.aashto.org
AMERICAN CONCRETE INSTITUTE INTERNATIONAL (ACI)
38800 Country Club Drive Farmington Hills, MI 48331-3439 Ph: 248-848-3700 Fax: 248-848-3701 E-mail: bkstore@concrete.org Internet: http://www.concrete.org
SECTION 01 42 00 Page 1
AMERICAN CONCRETE PIPE ASSOCIATION (ACPA)
8445 Freeport Parkway, Suite 350 Irving, TX 75063-2595 Ph: 972-506-7216 Fax: 972-506-7682 E-mail: info@concrete-pipe.org Internet: http://www.concrete-pipe.org
AMERICAN GEAR MANUFACTURERS ASSOCIATION (AGMA)
1001 N. Fairfax Street, Suite 500 Alexandria, VA 22314-1587 Ph: 703-684-0211 Fax: 703-684-0242 E-mail: tech@agma.org Internet: http://www.agma.org
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
One East Wacker Drive, Suite 700 Chicago, IL 60601-1802 Ph: 312-670-2400 Fax: 312-670-5403 Bookstore: 800-644-2400 E-mail: aisc@ware-pak.com Internet: http://www.aisc.org
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
1899 L Street, NW,11th Floor Washington, DC 20036 Ph: 202-293-8020 Fax: 202-293-9287 E-mail: storemanager@ansi.org Internet: http://www.ansi.org/
AMERICAN RAILWAY ENGINEERING AND MAINTENANCE-OF-WAY ASSOCIATION
(AREMA)
4501 Forbes Blvd., Suite 130 Lanham, MD 20706 Ph: 301-459-3200 Fax: 301-459-8077 E-mail: bcaruso@arema.org Internet: http://www.arema.org
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE)
1801 Alexander Bell Drive Reston, VA 20191 Ph: 703-295-6300; 800-548-2723 E-mail: member@asce.org Internet: http://www.asce.org
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
1791 Tullie Circle, NE Atlanta, GA 30329 Ph: 800-527-4723 or 404-636-8400 Fax: 404-321-5478 E-mail: ashrae@ashrae.org Internet: http://www.ashrae.org
SECTION 01 42 00 Page 2
AMERICAN WATER WORKS ASSOCIATION (AWWA)
6666 West Quincy Avenue Denver, CO 80235-3098 Ph: 303-794-7711 E-mail: distribution@awwa.org Internet: http://www.awwa.org
AMERICAN WELDING SOCIETY (AWS)
13301 NW 47 Ave Miami, FL 33054
Ph: 888-WELDING, 305-824-1177, 305-826-6192 Fax: 305-826-6195 E-mail: customer.service@awspubs.com Internet: http://www.aws.org
ASME INTERNATIONAL (ASME)
Two Park Avenue, M/S 10E New York, NY 10016-5990 Ph: 800-843-2763 Fax: 973-882-1717 E-mail: customercare@asme.org Internet: http://www.asme.org
ASPHALT INSTITUTE (AI)
2696 Research Park Drive Lexington, KY 40511-8480 Ph: 859-288-4960 Fax: 859-288-4999 E-mail: info@asphaltinstitute.org Internet: http://www.asphaltinstitute.org
ASTM INTERNATIONAL (ASTM)
100 Barr Harbor Drive, P.O. Box C700 West Conshohocken, PA 19428-2959 Ph: 877-909-2786 Internet: http://www.astm.org
CALIFORNIA ENERGY COMMISSION (CEC)
Media and Public Communications Office 1516 Ninth Street, MS-29 Sacramento, CA 95814-5512 Ph: 916-654-5106 E-mail: appliances@energy.ca.gov Internet: http://www.energy.ca.gov/
CONSUMER ELECTRONICS ASSOCIATION (CEA)
1919 South Eads St.
Arlington, VA 22202 Ph: 866-858-1555 or 703-907-7634 Fax: 866-858-2555 or 703-907-7693 E-mail: standards@CE.org Internet: http://www.CE.org
CRANE MANUFACTURERS ASSOCIATION OF AMERICA (CMAA)
8720 Red Oak Boulevard, Suite 201 Charlotte, NC 28217-3992 Ph: 704-676-1190
SECTION 01 42 00 Page 3
Fax: 704-676-1199 Internet: http://www.mhi.org/cmaa
ELECTRICAL GENERATING SYSTEMS ASSOCIATION (EGSA)
1650 South Dixie Highway, Suite 400 Boca Raton, FL 33432-7462 Ph: 561-750-5575 Fax: 561-395-8557 Internet: http://www.egsa.org
ELECTRONIC COMPONENTS INDUSTRY ASSOCIATION (ECIA)
2214 Rock Hill Rd., Suite 170 Herndon, VA 20170 Ph: 571-323-0294 Fax: 571-323-0245 E-mail: emikoski@ecaus.org Internet: http://www.ecianow.org/
FM GLOBAL (FM)
270 Central Avenue P.O. Box 7500 Johnston, RI 02919-4923 Ph: 877-364-6726 Fax: 401-275-3029 E-mail: servicedesk.myrisk@fmglobal.com Internet: http://www.fmglobal.com
FOREST STEWARDSHIP COUNCIL (FSC)
212 Third Avenue North Suite 445 Minneapolis, MN 55401 Ph: 612-353-4511 E-mail: info@us.fcs.org Internet: https://us.fsc.org/
GREEN SEAL (GS)
1001 Connecticut Avenue, NW Suite 827 Washington, DC 20036-5525 Ph: 202-872-6400 Fax: 202-872-4324 Internet: http://www.greenseal.org
ILLUMINATING ENGINEERING SOCIETY (IES)
120 Wall Street, 17th Floor New York, NY 10005-4001 Ph: 212-248-5000 Fax: 212-248-5018 E-mail: IES@IES.org Internet: http://www.IES.org
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
445 and 501 Hoes Lane Piscataway, NJ 08854-4141 Ph: 732-981-0060 or 800-701-4333 Fax: 732-562-9667 E-mail: onlinesupport@ieee.org Internet: http://www.ieee.org
SECTION 01 42 00 Page 4
INSULATED CABLE ENGINEERS ASSOCIATION (ICEA)
P.O. Box 1568 Carrollton, GA 30112 E-mail:
http://www.icea.net/Public_Pages/Contact/Email_Contact.html Internet: http://www.icea.net
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
3050 Old Centre Ave. Suite 102 Portage, MI 49024 Ph: 269-488-6382 Internet: http://www.netaworld.org
INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC)
3, rue de Varembe P.O. Box 131 CH-1211 Geneva 20, Switzerland Ph: 41-22-919-02-11 Fax: 41-22-919-03-00 Internet: http://www.iec.ch
INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)
1, ch. de la Voie-Creuse Case Postale 56 CP 56 - CH-1211 Geneva 20 Switzerland Ph: 41-22-749-01-11 Fax: 41-22-733-34-30 E-mail: central@iso.ch Internet: http://www.iso.org
INTERNET ENGINEERING TASK FORCE (IETF)
c/o Association Management Solutions, LLC (AMS) 48377 Fremont Blvd., Suite 117 Fremont, California 94538 Ph: 510-492-4080 Fax: 510-492-4001 E-mail: ietf-info@ietf.org Internet: http://www.ietf.org/
L.H. BAILEY HORTORIUM (LHBH)
Dept of Plant Biology c/o Cornell University 440 Mann Library Building Ithaca, NY 14853 Ph: 607-255-1052 Fax: 607-254-5407 Internet: http://plantbio.cals.cornell.edu/hortorium
LONMARK INTERNATIONAL (LonMark) 550 Meridan Ave.
San Jose, CA 95126 Ph: 408-938-5266 Fax: 408-790-3838 Internet: http://www.lonmark.org
MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS
INDUSTRY (MSS)
127 Park Street, NE
SECTION 01 42 00 Page 5
Vienna, VA 22180-4602 Ph: 703-281-6613 E-mail: info@mss-hq.com Internet: http://mss-hq.org/Store/index.cfm
MATERIAL HANDLING INDUSTRY OF AMERICA (MHI)
8720 Red Oak Blvd., Suite 201 Charlotte, NC 28717-3992 Ph: 704-676-1190 Fax: 704-676-1199 Internet: http://www.mhi.org
MODBUS ORGANIZATION, INC (MODBUS)
PO Box 628 Hopkinton, MA 01748 Ph: 508-435-7170 Fax: 508-435-7172 Internet: http://www.modbus.org
NATIONAL ELECTRICAL CONTRACTORS ASSOCIATION (NECA)
3 Bethesda Metro Center, Suite 1100 Bethesda, MD 20814 Ph: 301-657-3110 Fax: 301-215-4500 Internet: http://www.necanet.org/
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
1300 North 17th Street, Suite 900 Arlington, VA 22209 Ph: 703-841-3200 Internet: http://www.nema.org/
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
1 Batterymarch Park Quincy, MA 02169-7471 Ph: 617-770-3000 Fax: 617-770-0700 Internet: http://www.nfpa.org
NATIONAL SECURITY TELECOMMUNICATIONS AND INFORMATION SYSTEMS
SECURITY (NSTISS)
CNSS Secretariat National Security Agency 9800 Savage Road, Ste 6716 Fort George G. Meade, MD 20755-6716 Ph: 410-854-6805 Fax: 410-854-6814 E-mail: cnss@radium.ncsc.mil Publication available on the internet: http://www.dtic.mil/dtic/
NSF INTERNATIONAL (NSF)
789 North Dixboro Road P.O. Box 130140 Ann Arbor, MI 48105 Ph: 734-769-8010 or 800-NSF-MARK Fax: 734-769-0109 E-mail: info@nsf.org Internet: http://www.nsf.org
SECTION 01 42 00 Page 6
OPC FOUNDATION (OPC)
16101 N. 82nd Street Suite 3B Scottsdale, AZ 85260-1868 Ph: 480-483-6644 Fax: 480-483-7202 Internet: http://www.opcfoundation.org
RESEARCH COUNCIL ON STRUCTURAL CONNECTIONS (RCSC)
E-Mail: boltcouncil@gmail.com Internet: http://www.boltcouncil.org
SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
400 Commonwealth Drive Warrendale, PA 15096 Ph: 724-776-4970 Fax: 877-606-7323 E-mail: customerservice@sae.org Internet: http://www.sae.org
SOCIETY OF CABLE TELECOMMUNICATIONS ENGINEERS (SCTE)
140 Philips Road Exton, PA 19341-1318 Ph: 800-542-5040 or 610-363-6888 Fax: 610-363-5898 E-Mail: information@scte.org http://www.scte.org
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
1320 N. Courthouse Rd., Suite 200 Arlington, VA 22201 Ph: 703-907-7700 Fax: 703-907-7727 Internet: http://www.tiaonline.org
TREE CARE INDUSTRY ASSOCIATION (TCIA)
136 Harvey Road, Suite 101 Londonderry, NH 03053 Ph: 603-314-5380 Fax: 603-314-5386 Internet: http://tcia.org/
TURFGRASS PRODUCERS INTERNATIONAL (TPI)
2 East Main Street East Dundee, IL 60118 Ph: 847-649-5555 Fax: 847-649-5678 E-mail: info@turfgrasssod.org Internet: http://www.turfgrasssod.org
U.S. ARMY (DA)
U.S. Army Publishing Directorate Ph: 703-614-3634 Internet: http://www.apd.army.mil
U.S. ARMY CORPS OF ENGINEERS (USACE)
CRD-C DOCUMENTS available on Internet:
http://www.wbdg.org/ccb/browse_cat.php?c=68
SECTION 01 42 00 Page 7
Order Other Documents from:
USACE Publications Depot Attn: CEHEC-IM-PD 2803 52nd Avenue Hyattsville, MD 20781-1102 Ph: 301-394-0081 Fax: 301-394-0084 E-mail: pubs-army@usace.army.mil Internet: http://www.publications.usace.army.mil/ or http://www.hnc.usace.army.mil/Missions/Engineering/TECHINFO.aspx
U.S. DEPARTMENT OF AGRICULTURE (USDA)
Order AMS Publications from:
AGRICULTURAL MARKETING SERVICE (AMS)
Seed Regulatory and Testing Branch 801 Summit Crossing Place, Suite C Gastonia, NC 28054-2193 Ph: 704-810-8871 Fax: 704-852-4189 E-mail: seed.ams@usda.gov Internet: http://www.ams.usda.gov/lsg/seed.htm Order Other Publications from:
U.S. Department of Agriculture, Rural Utilities Program USDA Rural Development, Room 4051-S Mail Stop 1510 1400 Independence Avenue SW Washington, DC 20250-1510 Phone: (202) 720-9540 TTY: (800) 877-8339 (Federal Relay Service) Fax: (202) 720-1725 Internet: http://www.rurdev.usda.gov/utilities_lp.html
U.S. DEPARTMENT OF DEFENSE (DOD)
Order DOD Documents from:
Room 3A750-The Pentagon 1400 Defense Pentagon Washington, DC 20301-1400 Ph: 703-571-3343
FAX: 215-697-1462
E-mail: customerservice@ntis.gov Internet: http://www.ntis.gov Obtain Military Specifications, Standards and Related Publications from:
Acquisition Streamlining and Standardization Information System
(ASSIST)
Department of Defense Single Stock Point (DODSSP) Document Automation and Production Service (DAPS) Building 4/D 700 Robbins Avenue Philadelphia, PA 19111-5094 Ph: 215-697-6396 - for account/password issues Internet: http://assist.daps.dla.mil/online/start/; account registration required Obtain Unified Facilities Criteria (UFC) from:
Whole Building Design Guide (WBDG) National Institute of Building Sciences (NIBS) 1090 Vermont Avenue NW, Suite 700 Washington, CD 20005
SECTION 01 42 00 Page 8
Ph: 202-289-7800 Fax: 202-289-1092 Internet: http://www.wbdg.org/references/docs_refs.php
U.S. ENVIRONMENTAL PROTECTION AGENCY (EPA)
Ariel Rios Building 1200 Pennsylvania Avenue, N.W.
Washington, DC 20004 Ph: 202-272-0167 Internet: http://www2.epa.gov/libraries --- Some EPA documents are available only from:
National Technical Information Service (NTIS) 5301 Shawnee Road Alexandria, VA 22312 Ph: 703-605-6050 or 1-688-584-8332 Fax: 703-605-6900 E-mail: info@ntis.gov Internet: http://www.ntis.gov
U.S. FEDERAL AVIATION ADMINISTRATION (FAA)
Order for sale documents from:
Superintendent of Documents U.S. Government Printing Office (GPO) 710 North Capitol Street, NW Washington, DC 20401 Ph: 202-512-1800 Fax: 202-512-2104 E-mail: contactcenter@gpo.gov Internet: http://www.gpoaccess.gov Order free documents from:
Federal Aviation Administration Department of Transportation 800 Independence Avenue, SW Washington, DC 20591 Ph: 1-866-835-5322 Internet: http://www.faa.gov
U.S. FEDERAL COMMUNICATIONS COMMISSION (FCC)
445 12th Street SW Washington, DC 20554 Ph: 888-225-5322
TTY: 888-835-5322
Fax: 866-418-0232 Internet: http://www.fcc.gov Order Publications From:
Superintendent of Documents U.S. Government Printing Office (GPO) 710 North Capitol Street, NW Washington, DC 20401-0001 Ph: 202-512-1800 Fax: 866-418-0232 E-mail: gpoweb@gpo.gov Internet: http://www.gpoaccess.gov/
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
General Services Administration 1275 First St. NE Washington, DC 20417 Ph: 202-501-1231
SECTION 01 42 00 Page 9
Internet: http://www.gsaelibrary.gsa.gov/ElibMain/home.do Obtain documents from:
Acquisition Streamlining and Standardization Information System
(ASSIST)
Internet: https://assist.dla.mil/online/start/; account registration required
U. S. GREEN BUILDING COUNCIL (USGBC)
2101 L St NW, Suite 500 Washington, D.C. 20037 Ph: 800-795-1747 Internet: http://www.usgbc.org
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
8601 Adelphi Road College Park, MD 20740-6001 Ph: 866-272-6272 Fax: 301-837-0483 Internet: http://www.archives.gov Order documents from:
Superintendent of Documents U.S.Government Printing Office (GPO) 710 North Capitol Street, NW Washington, DC 20401 Ph: 202-512-1800 Fax: 202-512-2104 E-mail: contactcenter@gpo.gov Internet: http://www.gpoaccess.gov
UNDERWRITERS LABORATORIES (UL)
2600 N.W. Lake Road Camas, WA 98607-8542 Ph: 877-854-3577 E-mail: CEC.us@us.ul.com Internet: http://www.ul.com/ UL Directories available through IHS at http://www.ihs.com
UNI-BELL PVC PIPE ASSOCIATION (UBPPA)
2711 LBJ Freeway, Suite 1000 Dallas, TX 75234 Ph: 972-243-3902 Fax: 972-243-3907 E-mail: info@uni-bell.org Internet: http://www.uni-bell.org
PART 2 PRODUCTS
Not used
PART 3 EXECUTION
Not used
-- End of Section --
SECTION 01 42 00 Page 10
SECTION 25 10 10
UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END AND INTEGRATION
11/15
PART 1 GENERAL
1.1 SUMMARY
Provide a Utility Monitoring and Control System (UMCS) which performs supervisory monitoring and supervisory control of base-wide building control systems and utility control systems using CEA-709.1-D (LonWorks) with LonWorks Network Services (LNS) as indicated and shown. Integrate local CEA-709.1-D building control systems installed per Section 23 09 23.01
LONWORKS DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING CONTROL
SYSTEMS into the UMCS as specified and maintain the LNS database(s) for the entire network
1.1.1 System Requirements
Provide a UMCS as specified and indicated, and in accordance with the following characteristics:
1.1.1.1 General System Requirements
a. The system performs supervisory monitoring and control functions including but not limited to Scheduling, Alarm Handling, Trending, Overrides, Report Generation, and Electrical Demand Limiting as specified.
b. The system includes a Graphical User Interface which allows for graphical navigation between systems, graphical representations of systems, access to real-time data for systems, ability to override points in a system, and access to all supervisory monitoring and control functions.
c. All software used by the UMCS and all software used to install and configure the UMCS is licensed to and delivered to the installation.
d. All necessary documentation, configuration information, configuration tools, programs, drivers, and other software is licensed to and otherwise remains with the Government such that the Government or their agents are able to repair, replace, upgrade, and expand the system without subsequent or future dependence on the Contractor. Software licenses must not require periodic fees and must be valid in perpetuity.
e. Provide sufficient documentation and data, including rights to documentation and data, such that the Government or their agents can execute work to repair, replace, upgrade, and expand the system without subsequent or future dependence on the Contractor.
f. The UMCS interfaces directly to CEA-709.1-D field control system as specified and may interface to field control systems using other protocols via an M&C Software protocol driver or a Gateway.
g. For UMCS systems with Monitoring and Control Software functionality
SECTION 25 10 10 Page 1 implemented in Monitoring and Control (M&C) Controller Hardware, provide sufficient additional controller hardware to support the full capacity requirements as specified.
1.1.1.2 LonWorks Requirements
a. The UMCS must communicate using CEA-709.1-D over the Government furnished IP network in accordance with CEA-852-C as specified and must interface to CEA-709.1-D building control networks using LonWorks/IP Routers as specified.
b. All communication between the UMCS and LonWorks field control networks must be via the CEA-709.1-D protocol over the IP network in accordance with CEA-852-C.
c. Except for communication for device commissioning, configuration, and programming, all communication between the M&C Software and the field control system devices must be via SNVT.
1.1.2 General Cybersecurity Requirements
Address cybersecurity in accordance with DA AR 25-2.
1.1.3 Symbols, Definition and Abbreviations
Use symbols, definitions, and engineering unit abbreviations indicated in the contract drawings for displays, submittals and reports. For symbols, definitions and abbreviations not in the contract drawings use terms conforming at a minimum to IEEE Stds Dictionary and the ASHRAE FUN IP, as applicable.
1.1.4 System Units and Accuracy
Use English (inch-pound) units for displays, print-outs and calculations.
Perform calculations with an accuracy of at least three significant figures. For displays and printouts present values to at least three significant figures.
1.1.5 Data Packages/Submitals Requirements
Technical data packages consisting of computer software and technical data (meaning technical data which relates to computer software) which are specifically identified in this project and which may be defined/required in other specifications must be delivered strictly in accordance with the CONTRACT CLAUSES and in accordance with the Contract Data Requirements List, DD Form 1423. Data delivered must be identified by reference to the particular specification paragraph against which it is furnished. All submittals not specified as technical data packages are considered shop drawings under the Federal Acquisition Regulation Supplement (FARS) and must contain no proprietary information and must be delivered with unrestricted rights.
1.2 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
SECTION 25 10 10 Page 2
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE 135 (2012; Addenda AR 2013; Errata 1 2013; INT 1-9 2013; Errata 2 2013; INT 10-12 2014;
Errata 3-4 2014; Addenda AI-AY 2014; INT 13-17 2015; Errata 5 2015) BACnet—A Data Communication Protocol for Building Automation and Control Networks
ASHRAE FUN IP (2013; Addenda and Corrigendum 2013) Fundamentals Handbook, I-P Edition
CONSUMER ELECTRONICS ASSOCIATION (CEA)
CEA-709.1-D (2014) Control Network Protocol Specification
CEA-709.3 (1999; R 2004) Free-Topology Twisted-Pair Channel Specification
CEA-852-C (2014) Tunneling Component Network Protocols Over Internet Protocol Channels
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 1815 (2012) Electric Power Systems Communications-Distributed Network Protocol (DNP3)
IEEE C62.41 (1991; R 1995) Recommended Practice on Surge Voltages in Low-Voltage AC Power Circuits
IEEE Stds Dictionary (2009) IEEE Standards Dictionary: Glossary of Terms & Definitions
INTERNET ENGINEERING TASK FORCE (IETF)
IETF RFC 4361 (2006) Node-specific Client Identifiers for Dynamic Host Configuration Protocol Version Four (DHCPv4)
IETF RFC 7465 (2015) Prohibiting RC4 Cipher Suites
LONMARK INTERNATIONAL (LonMark)
LonMark Interoperability Guide (2005) LonMark Application-Layer Interoperability Guide and LonMark Layer 1-6 Interoperability Guide; Version 3.4
LonMark SNVT List (2003) LonMark SNVT Master List; Version
LonMark XIF Guide (2001) LonMark External Interface File Reference Guide; Revision 4.402
SECTION 25 10 10 Page 3
MODBUS ORGANIZATION, INC (MODBUS)
Modbus (2006) Modbus Application Protocol Specification; Version 1.1b and Modbus Messaging on TCP/IP Implementation Guide;
Version V1.0b
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
NEMA 250 (2014) Enclosures for Electrical Equipment (1000 Volts Maximum)
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 262 (2015) Standard method of Test for Flame Travel and Smoke of Wires and Cables for Use in Air-Handling Spaces
NFPA 70 (2014; AMD 1 2013; Errata 1 2013; AMD 2 2013; Errata 2 2013; AMD 3 2014; Errata 3-4 2014; AMD 4-6 2014) National Electrical Code
OPC FOUNDATION (OPC)
OPC DA (2002) OPC Data Access (DA) Specification;
Version 2.05a
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-568-C.1 (2009; Add 2 2011; Add 1 2012) Commercial Building Telecommunications Cabling Standard
TIA-606 (2012b) Administration Standard for the Telecommunications Infrastructure
TIA-607 (2011b) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
U.S. ARMY (DA)
DA AR 25-2 (2007; RAR 2009) Information Assurance
U.S. FEDERAL COMMUNICATIONS COMMISSION (FCC)
FCC EMC (2002) FCC Electromagnetic Compliance Requirements
FCC Part 15 Radio Frequency Devices (47 CFR 15)
UNDERWRITERS LABORATORIES (UL)
UL 1778 (2014; Reprint Aug 2015) Uninterruptible Power Systems
UL 60950 (2000; Reprint Oct 2007) Safety of Information Technology Equipment
SECTION 25 10 10 Page 4
1.3 DEFINITIONS
The following list of definitions may contain terms not found elsewhere in this Section but are included here for completeness. Some terms are followed with a protocol reference in parenthesis indicating to which protocol the term and definition applies. Inclusion of protocol-specific definitions does not create a requirement to support that protocol, nor does it relax any requirements to support specific protocols as indicated elsewhere in this section."
1.3.1 Alarm Generation
The process of comparing a point value (the point being alarmed) with a pre-defined alarm condition (e.g. a High Limit) and performing some action based on the result of the comparison.
1.3.2 Alarm Handling
see Alarm Routing
1.3.3 Alarm Routing
Alarm routing is M&C software functionality that starts with a notification that an alarm exists (typically as the output of an Alarm Generation process) and sends a specific message to a specific alarm recipient or device.
1.3.4 Application Generic Controller (AGC)(LonWorks)
A device that is furnished with a (limited) pre-established application that also has the capability of being programmed. Further, the ProgramID and XIF file of the device are fixed. The programming capability of an AGC may be less flexible than that of a General Purpose Programmable Controller
(GPPC).
1.3.5 Application Specific Controller (ASC)(LonWorks)
A device that is furnished with a pre-established built in application that is configurable but not re-programmable. An ASC has a fixed factory-installed application program (i.e Program ID) with configurable settings.
1.3.6 Binary
A two-state system or signal; for example one where an "ON" condition is represented by a high signal level and an "OFF" condition is represented by a low signal level. 'Digital' is sometimes used interchangeably with 'binary'.
1.3.7 Binding (LonWorks)
The act of establishing communications between CEA-709.1-D devices by associating the output of a device to the input of another so that information is automatically (and regularly) sent without being requested by the recipient.
SECTION 25 10 10 Page 5
1.3.8 Broadcast
Unlike most messages, which are intended for a specific recipient device, a broadcast message is intended for all devices on the network.
1.3.9 Building Control Network (BCN)
The network used by the Building Control System. Typically the BCN is a BACnet ASHRAE 135 or LonWorks CEA-709.1-D network installed by the building control system contractor.
1.3.10 Building Control System (BCS)
One type of Field Control System. A control system for building electrical and mechanical systems, typically HVAC (including central plants) and lighting. A BCS generally uses Direct Digital Control (DDC) Hardware and generally does NOT include its own local front end.
1.3.11 Building Point of Connection (BPOC)
A FPOC for a Building Control System. (This term is being phased out of use in preference for FPOC but is still used in some specifications and criteria. When it was used, it typically referred to a piece of control hardware. The current FPOC definition typically refers instead to IT hardware)
1.3.12 Channel (LonWorks)
A portion of the control network consisting of one or more segments connected by repeaters. Channels are separated by routers. The device quantity limitation is dependent on the topology/media and device type.
For example, a TP/FT-10 network with locally powered devices is limited to 128 devices per channel.
1.3.13 Configuration Property (LonWorks)
Controller parameter used by the application which is usually set during installation/testing and seldom changed. For example, the P and I settings of a P-I control loop. Also see 'Standard Configuration Property Type
(SCPT)'
1.3.14 Control Logic Diagram
A graphical representation of control logic for multiple processes that make up a system.
1.3.15 Explicit Messaging (LonWorks)
A non-standard and often vendor (application) specific method of communication between devices.
1.3.16 External Interface File (XIF) (LonWorks)
A file which documents a device's external interface, specifically the number and types of LonMark objects, the number, types, directions, and connection attributes of network variables, and the number of message tags.
SECTION 25 10 10 Page 6
1.3.17 Field Point Of Connection (FPOC)
The FPOC is part of the UMCS IP network and acts as the point of connection between the UMCS IP Network and the field control IP network. The FPOC is an IT device such as a switch, IP router, or firewall, typically managed by the site IT staff. (Note that the field control IP network may consist of a single IP device, or that integration may require installation of a field control network IP device.)
1.3.18 Field Control Network
The network used by a field control system.
1.3.19 Field Control System (FCS)
A building control system or utility control system.
1.3.20 Functional Profile (LonWorks)
A standard description, defined by LonMark International, of a LonMark Object used to classify and certify devices.
1.3.21 Gateway
A device that translates from one protocol to another. Devices that change only the transport mechanism of the protocol - "translating" from LonWorks over TP/FT-10 to LonWorks over IP for example - are not gateways as the underlying protocol (data format) does not change. Gateways are also called Communications Bridges or Protocol Translators.
1.3.22 General Purpose Programmable Controller (GPPC) (LonWorks)
Unlike an ASC or AGC, a GPPC is not furnished with a fixed application program and does not have a fixed ProgramID or XIF file. A GPPC can be (re-)programmed, usually using vendor-supplied software. When a change to the program affects the external interface (and the XIF file) the ProgramID will change.
1.3.23 JACE (Niagara Framework)
Java Application Control Engine. See Niagara Framework Supervisory Gateway
1.3.24 LonMark Object (LonWorks)
A collection of network variables, configuration properties, and associated behavior defined by LonMark International and described by a Functional Profile. It defines how information is exchanged between devices on a network (inputs from and outputs to the network).
1.3.25 LNS Plug-in (LonWorks)
Software which runs in an LNS compatible software tool, typically a network configuration tool. Device configuration plug-ins provide a 'user friendly' method to edit a device's configuration properties.
1.3.26 LonMark (LonWorks)
See LonMark International. Also, a certification issued by LonMark International to CEA-709.1-D devices.
SECTION 25 10 10 Page 7
1.3.27 LonMark International (LonWorks)
Standards committee consisting of independent product developers, system integrators and end users dedicated to determining and maintaining the interoperability guidelines for LonWorks. Maintains guidelines for the interoperability of CEA-709.1-D devices and issues the LonMark Certification for CEA-709.1-D devices.
1.3.28 LonWorks (LonWorks)
The term used to refer to the overall technology related to the CEA-709.1-D protocol (sometimes called "LonTalk"), including the protocol itself, network management, interoperability guidelines and products.
1.3.29 LonWorks Network Services (LNS) (LonWorks)
A network management and database standard for CEA-709.1-D devices.
1.3.30 LonWorks Network Services (LNS) Database (LonWorks)
The standard database created and used by LonWorks Network Services (LNS) compatible tools, such as LNS Network Configuration tools.
1.3.31 Monitoring and Control (M&C) Software
The UMCS 'front end' software which performs supervisory functions such as alarm handling, scheduling and data logging and provides a user interface for monitoring the system and configuring these functions.
1.3.32 Network Variable (LonWorks)
See 'Standard Network Variable Type (SNVT)'.
1.3.33 Network Configuration Tool (LonWorks)
The software used to configure the control network and set device configuration properties. This software creates and modifies the control network database (LNS Database).
1.3.34 Node (LonWorks)
A device that communicates using the CEA-709.1-D protocol and is connected to a CEA-709.1-D network.
1.3.35 Node Address (LonWorks)
The logical address of a node on the network, consisting of a Domain number, Subnet number and Node number. Note that the "Node number" portion of the address is the number assigned to the device during installation and is unique within a subnet. This is not the factory-set unique Node ID (see Node ID).
1.3.36 Node ID (LonWorks)
A unique 48-bit identifier assigned (at the factory) to each CEA-709.1-D device. Sometimes called the Neuron ID.
SECTION 25 10 10 Page 8
1.3.37 Override
To change the value of a point outside of the normal sequence of operation where this change has priority over the sequence. An override can be accomplished in one of two ways: the point itself may be Commandable and written to with a priority or there may be a separate point on the controller for the express purpose of implementing the override.
Typically this override is from the Utility Monitoring and Control System (UMCS) Monitoring and Control (M&C) Software. Note that this definition is not standard throughout industry.
1.3.38 Point, Calculated
A value within the M&C Software that is not a network point but has been calculated by logic within the software based on the value of network points or other calculated points. Calculated points are sometimes called virtual points or internal points.
1.3.39 Point, Network
A value that the M&C Software reads from or writes to a field control network.
1.3.40 Polling
A requested transmission of data between devices, rather than an unrequested transmission such as Change-Of-Value (COV) or Binding where data is automatically transmitted under certain conditions.
1.3.41 Program ID (LonWorks)
An identifier (number) stored in the device (usually EEPROM) that identifies the node manufacturer, functionality of device (application & sequence), transceiver used, and intended device usage.
1.3.42 Repeater
A device that connects two control network segments and retransmits all information received on one side onto the other.
1.3.43 Router (LonWorks)
A device that connects two channels and controls traffic between the channels by retransmitting signals received from one subnet onto the other based on the signal destination. Routers are used to subdivide a control network and to control bandwidth usage.
1.3.44 Segment
A 'single' section of a control network that contains no repeaters or routers. There is generally a limit on the number of devices on a segment, and this limit is dependent on the topology/media and device type. For example, a TP/FT-10 segment with locally powered devices is limited to 64 devices, and a BACnet MS/TP segment is limited to 32 devices.
1.3.45 Service Pin (LonWorks)
A hardware push-button on a device which causes the device to broadcast a
SECTION 25 10 10 Page 9 message containing its Node ID and Program ID. This broadcast can also be initiated via software.
1.3.46 Standard Configuration Property Type (SCPT) (LonWorks)
Pronounced 'skip-it'. A standard format type (maintained by LonMark International) for Configuration Properties.
1.3.47 Standard Network Variable Type (SNVT) (LonWorks)
Pronounced 'snivet'. A standard format type (maintained by LonMark International) used to define data information transmitted and received by the individual nodes. The term SNVT is used in two ways. Technically it is the acronym for Standard Network Variable Type, and is sometimes used in this manner. However, it is often used to indicate the network variable itself (i.e. it can mean "a network variable of a standard network variable type"). In general, the intended meaning should be clear from the context.
1.3.48 Subnet (LonWorks)
Consists of a logical grouping of up to 127 nodes, where the logical grouping is defined by node addressing. Each subnet is assigned a number which is unique within the Domain. See also Node Address.
1.3.49 Supervisory Controller
A controller implementing a combination of supervisory logic (global control strategies or optimization strategies), scheduling, alarming, event management, trending, web services or network management. Note this is defined by use; many supervisory controllers have the capability to also directly control equipment.
1.3.50 Supervisory Gateway
A device that is both a supervisory controller and a gateway.
1.3.51 TP/FT-10 (LonWorks)
A Free Topology Twisted Pair network (at 78 kbps) defined by CEA-709.3.
This is the most common media type for a CEA-709.1-D control network.
1.3.52 TP/XF-1250 (LonWorks)
A high speed (1.25 Mbps) twisted pair, doubly-terminated bus network defined by the LonMark Interoperability Guidelines. This media is typically used only as a backbone media to connect multiple TP/FT-10 networks.
1.3.53 UMCS Network
An IP network connecting multiple field control systems to the Monitoring and Control Software using one or more of: LonWorks (CEA-709.1-D and CEA-852-C), BACnet (ASHRAE 135 Annex J), Modbus or OPC DA.
1.3.54 User-defined Configuration Property Type (UCPT) (LonWorks)
Pronounced 'u-keep-it'. A Configuration Property format type that is defined by the device manufacturer.
SECTION 25 10 10 Page 10
1.3.55 User-defined Network Variable Type (UNVT) (LonWorks)
A network variable format defined by the device manufacturer. Note that UNVTs create non-standard communications (other vendor's devices may not correctly interpret it) and may close the system and therefore are not permitted by this specification.
1.3.56 Utility Control System (UCS)
One type of field control system. Used for control of utility systems such as an electrical substation, sanitary sewer lift station, water pump station, etc. Building controls are excluded from a UCS, however it is possible to have a Utility Control System and a Building Control System in the same facility, and for those systems to share components such as the FPOC. A UCS may include its own local front-end.
1.4 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance with Section 01 33 29.00 37 SUSTAINABILITY. Submit the following in accordance with Section 01 33 00.00 37 SUBMITTAL PROCEDURES and TABLE 1: PROJECT
SEQUENCING:
SD-02 Shop Drawings
UMCS Contractor Design Drawings; G, CA
UMCS Contractor Design Drawings as a single complete package: 3 hard copies and 1 copies on CDROM. Submit hardcopy drawings on A3 17 by 11 inches sheets, and electronic drawings in both PDF and Microstation format.
Draft As-Built Drawings; G
Draft As-Built Drawings as a single complete package: 3 hard copies and 1 copies on CDROM. Submit hardcopy drawings must on A3 17 by 11 inches sheets, and electronic drawings in both PDF and Microstation format.
Final As-Built Drawings; G
Final As-Built Drawings as a single complete package: 3 hard copies and 1 copies on CDROM. Submit hardcopy drawings on A3 17 by 11 inches sheets, and electronic drawings in both PDF and Microstation format.
SD-03 Product Data
Product Data Sheets; G, CA
Computer Software; G
The most recent versions of all computer software provided under this specification delivered as a Technical Data Package. Submit the user manuals for all software delivered for this project with
SECTION 25 10 10 Page 11 the software.
Enclosure Keys
Certificate of Networthiness Documentation; G
Documentation of existing Certificates of Networthiness or completed Certificate of Networthiness "Application Checklist" via email and on optical disk.
SD-05 Design Data
UMCS IP Network Bandwidth Usage Estimate; G
Four copies of the UMCS IP Network Bandwidth Usage Estimate.
SD-06 Test Reports
Pre-Construction QC Checklist; G, CA
Four copies of the Pre-Construction QC Checklist.
Post-Construction QC Checklist; G, CA
Four copies of the Post-Construction QC Checklist.
Existing Conditions Report; G, CA
Four copies of the Existing Conditions Report.
Start-Up and Start-Up Testing Report; G, CA
Four copies of the Start-Up and Start-Up Testing Report. The Start-Up and Testing report may be submitted as a Technical Data Package.
PVT Phase I Procedures; G, CA
Four copies of the PVT Phase I Procedures. The PVT Procedures may be submitted as a Technical Data Package.
PVT Phase I Report; G, CA
Four copies of the PVT Phase I Report. The PVT Phase I Report may be submitted as a Technical Data Package.
PVT Phase II Report; G, CA
Four copies of the PVT Phase II Report. The PVT Phase II Report may be submitted as a Technical Data Package.
SD-10 Operation and Maintenance Data
Operation and Maintenance (O&M) Instructions; G, CA
Four bound O&M Instructions and 1 copies of the Instructions in PDF format on optical disk. Index and tab bound instructions.
Submit instructions in PDF form as a single PDF file, or as multiple PDF files with a PDF file table of contents containing links to the other files. O&M Instructions may be submitted as a
SECTION 25 10 10 Page 12
Technical Data Package.
Preventive Maintenance Work Plan; G, CA
Four copies of the Preventive Maintenance Work Plan. The Preventive Maintenance Work Plan may be submitted as a Technical Data Package.
Basic Training Documentation; G, CA
Training manuals for Basic Training delivered for each trainee on the Course Attendance List with two additional copies delivered for archival at the project site. Submit two copies of the Course Attendance List with the archival copies. The Basic Training Documentation may be submitted as a Technical Data Package.
Advanced Training Documentation; G, CA
One set of training manuals delivered for each trainee on the Course Attendance List with two additional copies delivered for archival at the project site. Submit two copies of the Course Attendance List with the archival copies. The Advanced Training Documentation may be submitted as a Technical Data Package.
Refresher Training Documentation; G, CA
One set of training manuals delivered for each trainee on the Course Attendance List with two additional copies delivered for archival at the project site. Submit two copies of the Course Attendance List with the archival copies. The Refresher Training Documentation may be submitted as a Technical Data Package.
SD-11 Closeout Submittals
Closeout QC Checklist; G, CA
Four copies of the Closeout QC Checklist.
1.5 PROJECT SEQUENCING
TABLE I: PROJECT SEQUENCING specifies the sequencing of submittals as specified in paragraph SUBMITTALS (denoted by an 'S' in the 'TYPE' column) and activities as specified in PART 3 EXECUTION (denoted by an 'E' in the 'TYPE' column).
1.5.1 Sequencing for Submittals
The sequencing specified for submittals is the deadline by which the submittal must be initially submitted to the Government. Following submission there will be a Government review period as specified in Section 01 33 00.00 37 SUBMITTAL PROCEDURES. If the submittal is not accepted by the Government, revise the submittal and resubmit it to the Government within 14 days of notification that the submittal has been rejected. Upon re-submittal there will be an additional Government review period. If the submittal is not accepted the process repeats until the submittal is accepted by the Government.
SECTION 25 10 10 Page 13
1.5.2 Sequencing for Activities
The sequencing specified for activities indicates the earliest the activity may begin.
1.5.3 Abbreviations
In TABLE I the abbreviation AAO is used for 'after approval of' and 'ACO' is used for 'after completion of'.
TABLE I. PROJECT SEQUENCING
ITEM TYPE DESCRIPTION SEQUENCING
(START OF ACTIVITY or
DEADLINE FOR SUBMITTAL)
1 Notice to proceed
2 S Existing Conditions Report after #1
3 S Design Drawings after #1
4 S after #1Product Data Sheets and Certificate of Networthiness Documentation after #1
5 S UMCS IP Network Bandwidth Usage Estimate after #1
6 S Pre-construction QC Checklist after #1
7 E Install UMCS AAO #2 thru #6
8 E Start-Up and Start-Up Testing ACO #7
9 S Post-Construction QC Checklist ACO #8
10 S Computer Software ACO #8
11 S Start-Up and Start-Up Testing Report
ACO #8
12 S Draft As-Built Drawings ACO #8
13 S PVT Phase I Procedures before scheduled start of #14 and AAO #11
SECTION 25 10 10 Page 14
TABLE I. PROJECT SEQUENCING
ITEM TYPE DESCRIPTION SEQUENCING
(START OF ACTIVITY or
DEADLINE FOR SUBMITTAL)
14 E PVT Phase I AAO #13 and #12
15 S PVT Phase I Report ACO #14
16 S Preventive Maintenance Work Plan
AAO #11
17 S O&M Instructions AAO #11
18 S Basic Training Documentation AAO #11 and before scheduled start of #19
19 E Basic Training (PVT Phase II) AAO #16, #17 and #18
20 S PVT Phase II Report ACO #19
21 S Final As-Built Drawings AAO #20
22 S Advanced Training Documentation before schedule start of #23 and AAO #18
23 E Advanced Training ACO #19, AAO #22, and no later than 60 days ACO #19
24 S Refresher Training Documentation before #25 and AAO #18 and #22
25 E Refresher Training ACO #19 and AAO #24
26 S Closeout QC Checklist ACO #23
1.6 QUALITY CONTROL (QC) CHECKLISTS
The Contractor's Chief Quality Control (QC) Representative must complete the QC Checklist in APPENDIX A, and must submit the Pre-Construction QC Checklist, Post-Construction QC Checklist and Closeout QC Checklist as specified. The QC Representative must verify each item in the Checklist and initial in the provided area to indicate that the requirement has been met. The QC Representative must sign and date the Checklist prior to submission to the Government.
The APPENDIX A QC Checklist is available as an editable file at http://www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf.
SECTION 25 10 10 Page 15
1.7 OPERATION AND MAINTENANCE (O&M) INSTRUCTIONS
Provide UMCS Operation and Maintenance Instructions which include:
a. Procedures for the UMCS system start-up, operation and shut-down.
b. Final As-Built drawings.
c. Routine maintenance checklist, arranged in a columnar format: The first column listing all installed devices, the second column stating the maintenance activity or stating that no maintenance required, the third column stating the frequency of the maintenance activity, and the fourth column providing any additional comments or reference.
d. Qualified service organization list including points of contact with phone numbers.
e. Start-Up and Start-Up Testing Report.
f. Performance Verification Test (PVT) Procedures and Reports.
PART 2 PRODUCTS
2.1 EQUIPMENT REQUIREMENTS
2.1.1 Product Certifications
For computing devices, as defined in FCC Part 15, supplied as part of the UMCS provide devices which are certified to comply with the requirements of Class B computing devices.
2.1.2 Product Sourcing
For units of the same type of equipment, provide products of a single manufacturer. For each major component of equipment provide equipment with the manufacturer's name and the model and serial number in a conspicuous place. For materials and equipment, provide new standard unmodified products of a manufacturer regularly engaged in the manufacturing of such products.
2.1.3 General Requirements
Provide components that meet the following requirements:
a. Portions of the data communications equipment system installed in unconditioned spaces must operate properly in an environment with ambient temperatures between 32 and 120 degrees F and ambient relative humidity between 10 percent and 90 percent noncondensing.
b. Components must accept 100 to 125 volts AC (Vac), 60 Hz, single phase, three wire with a three-pronged, dedicated circuit outlet or be provided with a transformer to meet the component's power requirements.
c. The equipment must meet the requirements of NFPA 70, UL 60950, NFPA 262, FCC EMC, and FCC Part 15.
2.1.4 Nameplates
Provide nameplates of laminated plastic identifying the function, network
SECTION 25 10 10 Page 16 address, if applicable, and identifier of the device. Laminated plastic must be at least 0.125 inch thick, white with black center core.
Nameplates must be a minimum of 1 by 3 inch with minimum 0.25 inch high engraved block lettering.
2.1.5 Product Data Sheets
For all products (equipment) specified in PART 2 and supplied under this contract, submit copies of all manufacturer catalog cuts and specification sheets to indicate conformance to product requirements.
2.2 CONTROL HARDWARE
2.2.1 Control Protocol Routers
2.2.1.1 LonWorks/IP Router
Provide LonWorks/IP Routers which perform layer 3 routing of CEA-709.1-D packets over an IP network in accordance with CEA-852-C. The router must provide the appropriate connection to the IP network and connections to the CEA-709.3 TP/FT-10 or TP/XF-1250 network. LonWorks/IP Routers must support the Dynamic Host Configuration Protocol (DHCP; IETF RFC 4361) for IP configuration and the use of an CEA-852-C Configuration Server (for CEA-852-C configuration), but must not rely on these services for configuration. LonWorks/IP Routers must be capable of manual configuration via a console RS-232 port.
2.2.2 Monitoring and Control (M&C) Controller Hardware
Provide Monitoring and Control (M&C) Controller Hardware which is a microprocessor-based direct digital control hardware and which communicates over the UMCS IP network using: CEA-709.1-D in accordance with CEA-852-C and using only Standard Network Variable Types (SNVTs) as defined by the…