Thomas Gorge Contactor Call Meeting Notes
Contractors Questions/Answers
Requested Information:
Length of pig tail and fuel line Connection type of pig tail and fuel like
Notes:
System can be either 12 or 24 volt system Don’t need a battery charger for the system; still need the alternator so batteries can be charged The generator will have its fuel supplied by an existing fuel take on the barge Generator’s secondary containment system purpose is for catching spill, drips, and leaks the generator may produce over its life time Fuel connections must work with existing system, or the fuel tank may be modified at the contractors’ expense to allow for the fuel connection to work with the existing tank.
Enclosure type shale be a weather enclosure that fully encloses the generator Exhaust shall be wrapped to prevent burns on contact with the exhaust system.
Sight visit shale be scheduled for Tuesday January, 14, 2020 Contract solicitation period shall be extended to sometime within the 20 – 24 of January 2020