20’ FEET

20’-0” MAX

TYPICAL 120’ FEET

LIGHTNING PROTECTION PLAN & GROUND LOOP SYSTEMS

SCALE: N.T.S

v v v v vv v v

32' FEET

GENERAL NOTES:

1.ALL MEASUREMENTS ARE TO BE FIELD VERIFIRD.

2.PROVIDE UL MASTER LABEL SYSTEM.

3.THE LIGHTNING PROCTECTION SYSTEM (LPS)SHALL REQUIRE

AN INSPECTION PRIOR To ACCEPTANCE(PER UFC

3-575-01)THE SYSTEM SHALL BE INSPECTED BY A

COMMERCIAL, THIRD PARTY INSPECTOR WHO IS CERTIFIED

AND IS COMPLAINT WITH AFI-32-1065 AND NFPA 780.

4.MAXIMUM OF 20 FEET BETWEEN LPS AIR TERMINALS.

5.GROUNDING ROD IS TO A MINIMUM 30"INCHES DEEP.

6.GROUNDING ROD MUST TEST UNDER 25 OHMS

7.MAXIMUM OF 100'BETWEEN GROUND ROD LOCATIONS.

8.HEIGHT OF AIR TERMINAL IS BASE ON MEETING THE

REQUIREMENTS PER INDUSTRY STANDARDS AND IS BEING

SHOWN FOR REFERNCE. THIS IS CONSIDERD A TYPICAL

DETAIL.

GL

GLGL

GL

LPS LPS LPS LPS LPS

GLGL

C-2 DETAIL

C-1 DETAIL

STATIC BAR

GR

GR

GRGRGR

GR

GR

GR

TYPICAL

TYPICAL

DOOR

AT

AT

ATATATAT

LEGEND:

(AT) AIR TERMINAL

(GR) GROUND ROD CONNECTION

(GL) GROUND LOOP CONNECTION

(V) VENT

(LPS) LIGHTNING PROTECTION SYSTEM

SHEET

IDENTIFICATION

E-101