Weather/Sound Enclosure and Subbase Fuel Tank Package
Industrial Generator Set Accessories
Applicable to the following:
20--40REOZJC
50/60REOZJD
80/100/150/180/200REOZJF
125/180REOZJG
40/50/230--275REOZJE
300REOZJ
Weather Enclosure Standard Features D Internal-mounted silencer and flexible exhaust connector.
D Lift base or tank-mounted, steel construction with hinged doors.
D Fade-, scratch-, and corrosion-resistant Kohlerr Power Armort cream beige automotive-grade textured finish.
D Enclosure has four large access doors which allow for easy maintenance.
D Lockable, flush-mounted door latches.
D Vertical air inlet and outlet discharge to redirect air and reduce noise.
D Certified to withstand 241 kph (150 mph) wind load rating.
Sound Enclosure Standard Features D Includes all of the weather enclosure features with the addition of acoustic insulation material.
D Lift base or tank-mounted, steel or aluminum construction with hinged doors. Aluminum enclosures are recommended for high humidity and/or high salt/ coastal regions.
D Acoustic insulation that meets UL 94 HF1 flammability classification and repels moisture absorption.
D Sound attenuated enclosure that uses up to 51 mm (2 in.) of acoustic insulation.
Subbase Fuel Tank Features D The fuel tank has a Power Armor Plust textured epoxy-based rubberized coating.
D The above-ground rectangular secondary containment tank mounts directly to the generator set, below the generator set skid (subbase).
D Both the inner and outer tanks have emergency relief vents.
D Flexible fuel lines are provided with subbase fuel tank selection.
D The secondary containment generator set base tank meets UL 142 tank requirements. The inner (primary) tank is sealed inside the outer (secondary) tank. The outer tank contains the fuel if the inner tank leaks or ruptures.
D State tanks with varying capacities are an available option. Florida Dept. of Environmental Protection (FDEP) File No. EQ-634 approved.
Enclosure with Standard Subbase Fuel Tank
Enclosure with State Code Subbase Fuel Tank
Available Approvals and Listings
- UL 2200 Listing
- CSA Certified
- IBC Seismic Certification
- California OSHPD Approval
- cUL Listing (fuel tanks only) NOTE: Some models may have limited third-party approvals, see your local distributor for details.
G6-99 5/14aa Page 1
G6-99 5/14aa Page 2
Weather and Sound Enclosure
ADV-7429-
Hinged doors for ease of servicing
Lockable, flush-mounted door latches prevent tampering
Fixed air flow inlet grille
Rodent guards and skid end caps prevent animal entry
Oil drain and radiator drains
Fade-, scratch-, and corrosion- resistant Power Armort finish
Vertical air discharge through an air outlet grille
Enclosed exhaust silencer for improved safety and noise reduction
Acoustic insulation meeting UL 94 HF1 flammability classification
Alternator access panel
Note: 20--40REOZJC models shown, other models are similar. Refer to the respective ADV drawings for details.
Enclosure Features
D Available in steel (14 gauge) formed panel, solid construction. Preassembled package offering corrosion resistant, dent resilient structure mounting directly to lift base or fuel tank.
D Power Armort automotive-grade finish resulting in advanced corrosion and abrasion protection as well as enhanced edge coverage and color retention.
D Internal exhaust silencer offering maximum component life and operator safety.
NOTE: Installing an additional length of exhaust tail pipe may increase backpressure levels. Please refer to the generator set spec sheet for the maximum backpressure value.
D Interchangeable modular panel construction. Allows complete serviceability or replacement without compromising enclosure design.
D Cooling/combustion air intake with a horizontal air inlet.
Sized for maximum cooling airflow.
D Service access. Multi-personnel doors for easy access to generator set control and servicing of the fuel fill, fuel gauge, oil fill, and battery.
D Cooling air discharge. Weather protective design featuring a vertical air discharge outlet grille. Redirects cooling air up and above enclosure to reduce ambient noise.
Additional Sound Enclosure Features
D Available in steel (14 gauge) or aluminum 3.2 mm (0.125 in.)
formed panel, solid construction.
D Attenuated design. Acoustic insulation UL 94 HF1 listed for flame resistance offering up to 51 mm (2 in.)
mechanically restrained acoustic insulation.
D Cooling air discharge. The sound enclosures include acoustic insulation with urethane film.
G6-99 5/14aa Page 3
Subbase Fuel Tank
ADV-7430-
Low fuel level switch
Additional fitting for optional accessory
Basin drain
Emergency outer tank relief vent
Removable fuel return diptube
Removable engine supply diptube
Fuel level gauge
Fuel fill with lockable cap and 203 mm (8 in.) riser
Normal vent
Electrical stub-up area open to bottom
Fuel leak detection switch
Emergency inner tank relief vent
Note: 20--40REOZJC models shown, other models are similar. Refer to the respective ADV drawings for details.
Power Armor Plust coating for advanced corrosion and abrasion protection
Standard Subbase Fuel Tank Features
D Extended operation. Usable tank capacity offers full load standby operation of up to 72 hours.
D Power Armor Plust textured epoxy-based rubberized coating that creates an ultra-thick barrier between the tank and harsh environmental conditions like humidity, saltwater, and extreme temperatures, and provides advanced corrosion and abrasion protection.
D UL listed. Secondary containment generator set base tank meeting UL 142 requirements.
D NFPA compliant. Designed to comply with the installation standards of NFPA 30 and NFPA 37.
D Integral external lift lugs. Enables crane with spreader-bar lifting of the complete package (empty tank, mounted generator set, and enclosure) to ensure safety.
D Emergency pressure relief vents. Vents ensure adequate venting of the inner and outer tank under extreme pressure and/or emergency conditions.
D Normal vent with cap. Vent is raised above lockable fuel fill.
D Low fuel level switch. Annunciates a 50% low fuel level condition at generator set control.
D Leak detection switch. Annunciates a contained primary tank fuel leak condition at generator set control.
D Electrical stub-up.
G6-99 5/14aa Page 4
State Code Subbase Fuel Tank
ADV-7594-B
Low fuel level switch
Additional fitting for optional accessory
Basin drain
Emergency outer tank relief vent
Removable fuel return diptube
Removable engine supply diptube
Fuel level gauge
Fuel fill with lockable cap and 51 mm (2 in.) riser
Normal vent
Electrical stub-up area open to bottom
Fuel leak detection switch
Emergency inner tank relief vent
Note: 20--40REOZJC models shown, other models are similar. Refer to the respective ADV drawings for details.
Additional fitting for optional accessory
Top fluid containment drain
Power Armor Plust coating for advanced corrosion and abrasion protection
State Code Subbase Fuel Tank Features
D State tank designed to comply with the installation standards of the Florida Dept. of Environmental Protection (FDEP) File No. EQ-634.
D Includes all of the Standard Subbase Fuel Tank Features.
State Code Subbase Fuel Tank Options
Bottom Clearance
- I-beams, provides 106 mm (4.2 in.) of ground clearance
Fuel in Basin Options
- Fuel in basin switch, Florida Dept. of Environmental Protection (FDEP) File No. EQ-682 approved
Fuel Fill Options
- Fill pipe extension to within 152 mm (6 in.) of bottom of fuel tank.
- 18.9 L (5 gallon) spill containment with 95% shutoff
- 18.9 L (5 gallon) spill containment
- 18.9 L (5 gallon) spill containment fill to within 152 mm (6 in.)
of bottom of fuel tank
- 28.4 L (7.5 gallon) spill containment, Florida Dept. of Environmental Protection (FDEP) File No. EQ-345 approved
- 28.4 L (7.5 gallon) spill containment with 95% shutoff, Florida Dept. of Environmental Protection (FDEP) File No.
EQ--345/ EQ-257 approved
Fuel Supply Options
- Fire safety valve (installed on fuel supply line)
- Ball valve (installed on fuel supply line)
High Fuel Level Switch
- High fuel level switch
- High fuel level switch, Florida Dept. of Environmental Protection (FDEP) File No. EQ-682 approved
Normal Vent Options
- 3.7 m (12 ft.) above grade (without spill containment)
- 3.7 m (12 ft.) above grade (with spill containment)
Tank Marking Options
- Decal, Combustible Liquids -- Keep Fire Away (qty. 2)
- Decal, NFPA 704 identification (qty. 2)
- Decal, tank number and safe fuel fill height (qty. 2)
- Decal, tank number and safe fuel fill height, NFPA 704 identification
G6-99 5/14aa Page 5
Enclosure and Subbase Fuel Tank Specifications
Fuel Tank Capacity, L (gal.)
Est. Fuel Supply Hours at 60 Hz with Full Load, Nominal/Actual
Enclosure and Subbase Fuel Tank
Fuel Tank Height, mm (in.)
Sound Pressure at 60 Hz with Full Load at 7 m (23 ft.), Weather/
Sound dB(A)
Max. Dimensions, mm (in.) Max. Weight, kg (lb.) *
Length Width Height With Steel Enclosure
With Aluminum Enclosure
20REOZJC without IBC Seismic Certification
No Tank 0
2320 (91.3) 1077 (42.4)
1438 (56.6) 943 (2080) 830 (1830) 152 (6)
78/65 295 (78) 24/41 1722 (67.8) 1167 (2572)* 1053 (2322)* 305 (12)
424 (112) 36/58 1824 (71.8) 1201 (2647)* 1087 (2397)* 406 (16)
621 (164) 48/86 1976 (77.8) 1251 (2759)* 1138 (2509)* 559 (22)
20REOZJC with IBC Seismic Certification
No Tank 0
2320 (91.3) 1077 (42.4)
1384 (54.6) 943 (2080) 830 (1830) 100 (4)
78/65 295 (78) 24/41 1671 (65.8) 1272 (2806)* 1159 (2556)* 254 (10)
428 (113) 36/59 1773 (69.8) 1321 (2913)* 1208 (2663)* 358 (14)
625 (165) 48/86 1925 (75.8) 1393 (3073)* 1280 (2823)* 508 (20)
20REOZJC with State Code Fuel Tank[
439 (116) 24/61
2896 (114) 1077 (42.4)
1671 (65.8) 1362 (3003)* 1249 (2753)* 358 (14)
78/65556 (147) 48/77 1849 (72.8) 1459 (3217)* 1346 (2967)* 432 (17)
958 (253) 72/133 2103 (82.8) 1514 (3338)* 1401 (3088)* 686 (27)
30REOZJC without IBC Seismic Certification
No Tank 0
2320 (91.3) 1077 (42.4)
1438 (56.6) 1007 (2220) 894 (1970) 152 (6)
78/65 295 (78) 24/27 1722 (67.8) 1230 (2712)* 1117 (2462)* 305 (12)
424 (112) 36/40 1824 (71.8) 1264 (2787)* 1151 (2537)* 406 (16)
621 (164) 48/58 1976 (77.8) 1315 (2899)* 1202 (2649)* 559 (22)
30REOZJC with IBC Seismic Certification
No Tank 0
2320 (91.3) 1077 (42.4)
1384 (54.6) 1007 (2220) 894 (1970) 100 (4)
78/65 295 (78) 24/27 1671 (65.8) 1336 (2946)* 1223 (2696)* 254 (10)
428 (113) 36/40 1773 (69.8) 1385 (3053)* 1271 (2803)* 358 (14)
625 (165) 48/58 1925 (75.8) 1457 (3213)* 1344 (2963)* 508 (20)
30REOZJC with State Code Fuel Tank[
439 (116) 24/41
2896 (114) 1077 (42.4)
1671 (65.8) 1424 (3139)* 1311 (2889)* 358 (14)
78/65556 (147) 48/52 1849 (72.8) 1521 (3353)* 1408 (3103)* 432 (17)
958 (253) 72/90 2103 (82.8) 1576 (3474)* 1463 (3224)* 686 (27)
40REOZJC without IBC Seismic Certification
No Tank 0
2320 (91.3) 1077 (42.4)
1438 (56.6) 966 (2130) 853 (1880) 152 (6)
78/65 424 (112) 24/32 1824 (71.8) 1223 (2697)* 1110 (2447)* 406 (16)
621 (164) 48/48 1976 (77.8) 1274 (2809)* 1161 (2559)* 559 (22)
946 (250) 72/73 2230 (87.8) 1555 (3429)* 1442 (3179)* 813 (32)
40REOZJC with IBC Seismic Certification
No Tank 0
2320 (91.3) 1077 (42.4)
1384 (54.6) 966 (2130) 853 (1880) 100 (4)
78/65 428 (113) 24/33 1773 (69.8) 1344 (2963)* 1231 (2713)* 358 (14)
625 (165) 48/48 1925 (75.8) 1416 (3123)* 1303 (2873)* 508 (20)
958 (253) 72/74 2179 (85.8) 1736 (3826)* 1622 (3576)* 762 (30)
40REOZJC with State Code Fuel Tank[
439 (116) 24/34 2896 (114) 1077 (42.4)
1671 (65.8) 1451 (3199)* 1338 (2949)* 358 (14) 78/65
958 (253) 48/74 2103 (82.8) 1575 (3472)* 1462 (3222)* 686 (27)
Note: Data in table is for reference only, refer to the respective ADV drawings for details.
Note: Refer to TIB-114 for generator set sound data.
* Max. weight includes the generator set (wet) using the largest alternator option, enclosure with acoustic insulation added, silencer, and tank (no fuel).
[ State code fuel tank specifications (height and weight) include I-beam option.
G6-99 5/14aa Page 6
Enclosure and Subbase Fuel Tank Specifications (continued)
Fuel Tank Capacity, L (gal.)
Est. Fuel Supply Hours at 60 Hz with Full Load, Nominal/Actual
Enclosure and Subbase Fuel Tank
Fuel Tank Height, mm (in.)
Sound Pressure at 60 Hz with Full Load at 7 m (23 ft.), Weather/ Sound dB(A)
Max. Dimensions, mm (in.) Max. Weight, kg (lb.) *
Length Width Height With Steel Enclosure
With Aluminum Enclosure
40REOZJE
No Tank 0
2320 (91.3) 1077 (42.4)
1451 (57.1) 1188 (2620) 1085 (2393) 0 (0)
78/67 432 (114) 24/30 1857 (73.1) 1446 (3190)* 1343 (2963)* 406 (16)
715 (189) 36/51 2111 (83.1) 1522 (3357)* 1419 (3130)* 660 (26)
1071 (283) 48/76 2365 (93.1) 1612 (3555)* 1509 (3328)* 914 (36)
40REOZJE with State Code Fuel Tank
473 (125) 24/33
2896 (114.0) 1077 (42.4)
1832 (72.1) 1613 (3558)* 1510 (3331)* 381 (15)
78/67886 (234) 48/63 2061 (81.1) 1753 (3867)* 1650 (3640)* 610 (24)
1302 (344) 72/92 2340 (92.1) 1914 (4220)* 1811 (3993)* 889 (35)
50REOZJD without IBC Seismic Certification
No Tank 0
2320 (91.3) 1077 (42.4)
1438 (56.6) 1027 (2265) 914 (2015) 152 (6)
78/66 424 (112) 24/26 1824 (71.8) 1285 (2832)* 1171 (2582)* 406 (16)
621 (164) 36/38 1976 (77.8) 1335 (2944)* 1222 (2694)* 559 (22)
946 (250) 48/58 2230 (87.8) 1555 (3429)* 1442 (3179)* 813 (32)
50REOZJD with IBC Seismic Certification
No Tank 0
2320 (91.3) 1077 (42.4)
1384 (54.6) 1027 (2265) 914 (2015) 100 (4)
78/66 428 (113) 24/26 1773 (69.8) 1405 (3098)* 1292 (2848)* 358 (14)
625 (165) 36/38 1925 (75.8) 1477 (3258)* 1364 (3008)* 508 (20)
958 (253) 48/58 2179 (85.8) 1736 (3826)* 1622 (3576)* 762 (30)
50REOZJD with State Code Fuel Tank[
439 (116) 24/26
2896 (114) 1077 (42.4)
1824 (71.8) 1529 (3371)* 1416 (3121)* 358 (14)
78/66958 (253) 48/58 2103 (82.8) 1653 (3644)* 1540 (3394)* 686 (27)
1408 (372) 72/86 2332 (91.8) 1804 (3977)* 1691 (3727)* 914 (36)
50REOZJE
No Tank 0
2320 (91.3) 1077 (42.4)
1451 (57.1) 1188 (2620) 1085 (2393) 0 (0)
78/67 432 (114) 24/24 1857 (73.1) 1446 (3190)* 1343 (2963)* 406 (16)
715 (189) 36/41 2111 (83.1) 1522 (3357)* 1419 (3130)* 660 (26)
1071 (283) 48/61 2365 (93.1) 1612 (3555)* 1509 (3328)* 914 (36)
50REOZJE with State Code Fuel Tank
473 (125) 24/27
2896 (114.0) 1077 (42.4)
1832 (72.1) 1613 (3558)* 1510 (3331)* 381 (15)
78/67886 (234) 48/50 2061 (81.1) 1753 (3867)* 1650 (3640)* 610 (24)
1302 (344) 72/74 2340 (92.1) 1914 (4220)* 1811 (3993)* 889 (35)
60REOZJD without IBC Seismic Certification
No Tank 0
2320 (91.3) 1077 (42.4)
1438 (56.6) 1164 (2566) 1051 (2316) 152 (6)
78/68 492 (130) 24/26 1824 (71.8) 1438 (3170)* 1324 (2920)* 457 (18)
783 (207) 36/41 2103 (82.8) 1514 (3338)* 1401 (3088)* 686 (27)
946 (250) 48/50 2230 (87.8) 1555 (3429)* 1442 (3179)* 813 (32)
60REOZJD with IBC Seismic Certification
No Tank 0
2320 (91.3) 1077 (42.4)
1384 (54.6) 1164 (2566) 1051 (2316) 100 (4)
78/68 492 (130) 24/26 1773 (69.8) 1566 (3452)* 1452 (3202)* 406 (16)
795 (210) 36/42 2052 (80.8) 1687 (3719)* 1574 (3469)* 635 (25)
958 (253) 48/50 2179 (85.8) 1736 (3826)* 1622 (3576)* 762 (30)
60REOZJD with State Code Fuel Tank[
556 (147) 24/29
2895 (114) 1077 (42.4)
1849 (72.8) 1616 (3563)* 1503 (3313)* 432 (17)
78/68958 (253) 48/50 2103 (82.8) 1767 (3896)* 1654 (3646)* 686 (27)
1408 (372) 72/74 2332 (91.8) 1918 (4228)* 1805 (3978)* 914 (36)
G6-99 5/14aa Page 7
Fuel Tank Capacity, L (gal.)
Sound Pressure at 60 Hz with Full Load at 7 m (23 ft.), Weather/ Sound dB(A)
Fuel Tank Height, mm (in.)
Enclosure and Subbase Fuel Tank
Est. Fuel Supply Hours at 60 Hz with Full Load, Nominal/Actual
Fuel Tank Capacity, L (gal.)
Sound Pressure at 60 Hz with Full Load at 7 m (23 ft.), Weather/ Sound dB(A)
Fuel Tank Height, mm (in.)
Max. Weight, kg (lb.) *Max. Dimensions, mm (in.)
Est. Fuel
Supply Hours at 60 Hz with Full Load, Nominal/Actual
Fuel Tank Capacity, L (gal.)
Sound Pressure at 60 Hz with Full Load at 7 m (23 ft.), Weather/ Sound dB(A)
Fuel Tank Height, mm (in.)
With Aluminum Enclosure
With Steel EnclosureHeightWidthLength
Est. Fuel Supply Hours at 60 Hz with Full Load, Nominal/Actual
80REOZJF without IBC Seismic Certification
No Tank 0
2821 (111.1) 1156 (45.5)
1575 (62) 1483 (3269) 1351 (2979) 152 (6)
83/69791 (209) 24/30 1930 (76) 1766 (3894)* 1635 (3604)* 508 (20)
1317 (348) 48/50 2235 (88) 1882 (4150)* 1751 (3860)* 813 (32)
80REOZJF with IBC Seismic Certification
No Tank 0
2821 (111.1) 1156 (45.5)
1525 (60) 1483 (3269) 1351 (2979) 102 (4)
83/69757 (200) 24/28 1880 (74) 1851 (4080)* 1719 (3790)* 457 (18)
1313 (347) 48/50 2185 (86) 2108 (4647)* 1976 (4357)* 762 (30)
80REOZJF with State Code Fuel Tank[
814 (215) 24/31 3400 (133.9) 1156 (45.5)
1855 (73) 1996 (4400)* 1864 (4110)* 432 (17) 83/69
1571 (415) 48/60 2185 (86) 2236 (4929)* 2104 (4639)* 762 (30)
100REOZJF without IBC Seismic Certification
No Tank 0 2821 (111.1)
1156 (45.5)
1575 (62) 1592 (3510) 1461 (3220) 152 (6)
82/69791 (209) 24/25 1930 (76) 1875 (4134)* 1744 (3844)* 508 (20)
1696 (448) 48/54 3400 (133.9) 2235 (88) 2070 (4564)* 1939 (4274)* 813 (32)
100REOZJF with IBC Seismic Certification
No Tank 0 2821 (111.1)
1156 (45.5)
1525 (60) 1592 (3510) 1461 (3220) 102 (4)
82/69757 (200) 24/24 1880 (74) 1960 (4320)* 1828 (4030)* 457 (18)
1699 (449) 48/54 3400 (133.9) 2185 (86) 2345 (5170)* 2214 (4880)* 762 (30)
100REOZJF with State Code Fuel Tank[
814 (215) 24/26 3400 (133.9) 1156 (45.5)
1855 (73) 2105 (4641)* 1974 (4351)* 432 (17) 82/69
1571 (415) 48/50 2185 (86) 2345 (5170)* 2214 (4880)* 762 (30)
125REOZJG
No Tank 0
3532 (139.0) 1153 (45.4)
1753 (69) 1651 (3632) 1515 (3333) 0 (0)
87/731128 (298) 24/30 2236 (88) 2400 (5280)* 2264 (4981)* 483 (19)
2207 (583) 48/58 2667 (105) 2751 (6052)* 2615 (5753)* 914 (36)
125REOZJG with State Code Fuel Tank[
1196 (316) 24/31 4414 (173.8) 1153 (45.4)
2236 (88) 2382 (5240)* 2446 (4941)* 483 (19) 87/73
2252 (595) 48/60 2591 (102) 2654 (5839)* 2500 (5511)* 838 (33)
150REOZJF
No Tank 0
3532 (139.0) 1153 (45.4)
1753 (69) 1860 (4101) 1724 (3800) 0 (0)
86/751128 (298) 24/25 2236 (88) 2609 (5752)* 2473 (5452)* 483 (19)
2207 (583) 48/49 2667 (105) 2960 (6526)* 2824 (6226)* 914 (36)
150REOZJF with State Code Fuel Tank[
1196 (316) 24/27 4414 (173.8) 1153 (45.4)
2236 (88) 2591 (5712)* 2455 (5412)* 483 (19) 86/75
2252 (595) 48/50 2591 (102) 2890 (6361)* 2727 (6012)* 838 (33)
Note: Data in table is for reference only, refer to the respective ADV drawings for details.
Note: Refer to TIB-114 for generator set sound data.
* Max. weight includes the generator set (wet) using the largest alternator option, enclosure with acoustic insulation added, silencer, and tank (no fuel).
G6-99 5/14aa Page 8
Fuel Tank Capacity, L (gal.)
Est. Fuel Supply Hours at 60 Hz with Full Load, Nominal/Actual
Enclosure and Subbase Fuel Tank
Fuel Tank Height, mm (in.)
Sound Pressure at 60 Hz with Full Load at 7 m (23 ft.), Weather/
Sound dB(A)
Max. Dimensions, mm (in.) Max. Weight, kg (lb.) *
Length Width Height With Steel Enclosure
With Aluminum Enclosure
180REOZJF
No Tank 0
4094 (161.2) 1338 (52.7)
2057 (81) 1928 (4250) 1780 (3925) 0 (0)
87/721514 (400) 24/29 2540 (100) 2861 (6307)* 2713 (5981)* 483 (19)
2869 (758) 48/55 2946 (116) 3255 (7176)* 3107 (6850)* 889 (35)
180REOZJF with State Code Fuel Tank[
1556 (416) 24/30 5008 (197.2) 1338 (52.7)
2585 (102) 3162 (6971)* 3014 (6646)* 457 (18) 87/72
2896 (765) 48/56 2890 (114) 3488 (7690)* 3340 (7363)* 762 (30)
180REOZJG
No Tank 0
4094 (161.2) 1338 (52.7)
2057 (81) 1928 (4250) 1780 (3925) 0 (0)
85/721514 (400) 24/31 2540 (100) 2861 (6307)* 2713 (5981)* 483 (19)
2869 (758) 48/58 2946 (116) 3255 (7176)* 3107 (6850)* 889 (35)
180REOZJG with State Code Fuel Tank[
1556 (416) 24/32 5008 (197.2) 1338 (52.7)
2585 (102) 3162 (6971)* 3014 (6646)* 457 (18) 85/72
2896 (765) 48/59 2890 (114) 3488 (7690)* 3340 (7363)* 762 (30)
200REOZJF
No Tank 0
4094 (161.2) 1338 (52.7)
2057 (81) 2309 (5090) 2161 (4764) 0 (0)
87/751514 (400) 24/26 2540 (100) 3242 (7147)* 3094 (6821)* 483 (19)
2869 (758) 48/49 2946 (116) 3636 (8016)* 3488 (7690)* 889 (35)
200REOZJF with State Code Fuel Tank[
1575 (416) 24/27 5008 (197.2) 1338 (52.7)
2585 (102) 3543 (7811)* 3395 (7485)* 457 (18) 87/75
2896 (765) 48/50 2890 (114) 4050 (8930)* 3721 (8203)* 762 (30)
230REOZJE
No Tank 0 4121 (162.3) 1338 (52.7)
2157 (84.9) 2654 (5850) 2540 (5600) 0 (0) 87/75
1787 (472) 24/29 2659 (104.7) 3561 (7850)* 3447 (7600)* 762 (30)
230REOZJE with State Code Fuel Tank[
2101 (555) 24/34 5009 (197.2) 1338 (52.7)
2792 (109.9) 3895 (8587)* 3782 (8337)* 635 (25) 87/75
3573 (944) 48/58 5325 (209.7) 3071 (120.9) 4504 (9930)* 4391 (9680)* 914 (36)
250REOZJE
No Tank 0 4121 (162.3) 1338 (52.7)
2157 (84.9) 2699 (5950) 2585 (5700) 0 (0) 89/75
1787 (472) 24/26 2659 (104.7) 3606 (7950)* 3493 (7700)* 762 (30)
250REOZJE with State Code Fuel Tank[
2101 (555) 24/31 5009 (197.2) 1338 (52.7)
2792 (109.9) 3940 (8687)* 3827 (8437)* 635 (25) 89/75
3573 (944) 48/53 5325 (209.7) 3071 (120.9) 4550 (10030)* 4436 (9780)* 914 (36)
275REOZJE
No Tank 0 4121 (162.3) 1338 (52.7)
2157 (84.9) 2835 (6250) 2722 (6000) 0 (0) 89/75
1787 (472) 24/24 2659 (104.7) 3742 (8250)* 3629 (8000)* 762 (30)
275REOZJE with State Code Fuel Tank[
2101 (555) 24/28 5009 (197.2) 1338 (52.7)
2792 (109.9) 4076 (8987)* 3963 (8737)* 635 (25) 89/75
3573 (944) 48/48 5325 (209.7) 3071 (120.9) 4686 (10330)* 4572 (10080)* 914 (36)
Note: Data in table is for reference only, refer to the respective ADV drawings for details.
Note: Refer to TIB-114 for generator set sound data.
* Max. weight includes the generator set (wet) using the largest alternator option, enclosure with acoustic insulation added, silencer, and tank (no fuel).
G6-99 5/14aa Page 9
300REOZJ
No Tank 0 4121 (162.3) 1338 (52.7)
2157 (84.9) 2835 (6250) 2722 (6000) 0 (0) 89/75
2067 (546) 24/24 2735 (107.7) 3770 (8311)* 3656 (8061)* 838 (33)
300REOZJ with State Code Fuel Tank[
2101 (555) 24/25 5009 (197.2) 1338 (52.7)
2792 (109.9) 4076 (8987)* 3963 (8737)* 635 (25) 89/75
4065(1074) 48/48 5588 (220.0) 3071 (120.9) 4644 (10238)* 4530 (9988)* 914 (36)
Note: Data in table is for reference only, refer to the respective ADV drawings for details.
Note: Refer to TIB-114 for generator set sound data.
* Max. weight includes the generator set (wet) using the largest alternator option, enclosure with acoustic insulation added, silencer, and tank (no fuel).
2008, 2009, 2010, 2011, 2012, 2013, 2014 by Kohler Co. All rights reserved.
DISTRIBUTED BY:
G6-99 5/14aa Page 10
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-457-4441, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KOHLERPower.com
Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specificationswithout notice andwithout any obligation or liability whatsoever. Contact your local Kohlerr generator set distributor for availability.
A
12345678
B
C
D
12345678
A
B
C
D
TITLE
SCALE
DWG NO.
CAD NO. SHEET
DRAWN
CHECKED
APPROVED
MAX.
THIRD ANGLE
PROJECTION
POWER SYSTEMS, KOHLER, WI 53044 U .S.A.
THIS DRAWING IN DESIGN AND DETAIL IS KOHLER CO.
PROPERTY AND MUST NOT BE USED EXCEPT IN
CONNECTION WITH KOHLER CO. WORK. ALL RIGHTS OF
DESIGN OR INVENTION ARE RESERVED.
1521 [59.9 ]
4094 [161.2 ]
[47.0 ]
[51.2 ]
[2.1 ] 100
[3.9 ] [31.5 ]
[22.0 ]
[3.1 ]
[25.5 ]
[22.0 ]
D O O R
C L E A R A N C E
T Y P
[20.6 ]
761 [30.0 ]
1339 [52.7 ] 4108 [161.7 ]
2472 [97.3 ]469 [18.5 ]
PRO-EMETRIC
DIMENSION PRINT 230-300KW JD
0.06 1 of 4
ADV-7644 D
UNLESS OTHERWISE SPECIFIED -
1) DIMENSIONS ARE IN MILLIMETERS
2) TOLERANCES ARE:
X.XX 0.25
X.X 1.0
X 1.5 SURFACE FINISH
ANGLES 0 30'
APPROVALS DATE
DJV
10-24-08
CWF 10-24-08
SLJ 10-24-08
REV DATE ON COMPOSITE DWGS, SEE PART NO. FOR REVISION LEVEL BY
E 10-31-12 SHEET 2 WAS SHEET1, ADDED SHEET 1 [CT28612] CEK
F 2-5-13 (A-1) 1-4 WAS 1-2, SEE SHEET 3 AND 4 [CT32174] SAM
230-300 MODEL
JOHN DEERE TIER III
NOTE:
1. IF STANDARD TANK IS ORDERED, ENCLOSURE MOUNTS DIRECTLY TO TANK
2. IF STATE TANK IS ORDERED, TANK MOUNTS BELOW SKID
3. TANK MAY EXTEND BEYOND ENCLOSURE (DISCHARGE END ONLY)
4. FOR STUB-UP ACCESS DURING INSTALLATION THE REAR
ENCLOSURE PANEL SHOULD BE REMOVED.
OIL/COOLANT DRAIN
(BOTH SIDES)
AIR INTAKE
AIR INTAKE
ENGINE EXHAUST
AIR DISCHARGE
MODEL
ENCLOSURE WEIGHT
KG [LBS]
STEEL WEATHER 363 [800]
STEEL SOUND 386 [850]
ALUMINIUM SOUND 238 [525]
B
C
D
12345678
A
B
C
D
TITLE
SCALE
DWG NO.
CAD NO. SHEET
DRAWN
CHECKED
APPROVED
MAX.
THIRD ANGLE
PROJECTION
POWER SYSTEMS, KOHLER, WI 53044 U .S.A.
THIS DRAWING IN DESIGN AND DETAIL IS KOHLER CO.
PROPERTY AND MUST NOT BE USED EXCEPT IN
CONNECTION WITH KOHLER CO. WORK. ALL RIGHTS OF
DESIGN OR INVENTION ARE RESERVED.B 10-7-10 (D-6) 523 WAS 588, (C-6) 761 WAS 713, (B-2)
4121.4 WAS 4100.0 [90099-5] RJS
SAM
(A-1) 2-4 WAS 2-2, SEE SHEET 3 AND 4 [CT32174]
[3.1 ]
[25.5 ]1194 [47.0 ]
1300 [51.2 ]1965.0 [77.36]
1521.0 [59.88 ]
4094.0 [161.18 ]
53 [2.1 ] 100 [3.9 ]
800 [31.5 ]
[22.0 ]
[22.0 ]
D O O R
C L E A R A N C E
T Y P
[20.6 ]
761 [30.0 ]
1338 [52.7 ]
4121 [162.3 ]
859 [33.8 ]
DOOR OPENING
D O O R
O P E N I N G
PRO-EMETRIC
DIMENSION PRINT 230-300KW JD
0.06 2 of 4
ADV-7644 D
UNLESS OTHERWISE SPECIFIED -
1) DIMENSIONS ARE IN MILLIMETERS
2) TOLERANCES ARE:
X.XX 0.25
X.X 1.0
X 1.5 SURFACE FINISH
ANGLES 0 30'
APPROVALS DATE
DJV
10-24-08
CWF 10-24-08
SLJ 10-24-08
REV DATE ON COMPOSITE DWGS, SEE PART NO. FOR REVISION LEVEL BY
A 3-9-10 (A-8) 200 WAS 'A',(A-7)4094 WAS 'B',1965 WAS
"C",(D-4)TABLE REMOVED, (D-3) NEW TABLE ADDED,
(D-6) 916 WAS 919,(B-6) 859 WAS 863 [89197] PKD
C 3-16-11 (A-8) 260.0 WAS 200.0 [91189] SAM
D 6-20-11 (C-3) STUB-UP NOTE ADDED [91752]
E 10-31-12 SHEET2 WAS SHEET 1, ADDED SHEET 1 [CT28612] CEK
F 2-5-13 SAM
230-300 MODEL
JOHN DEERE TIER III
IBC/ OSHPD
NOTE:
1. IF STANDARD TANK IS ORDERED, ENCLOSURE MOUNTS DIRECTLY TO TANK
2. IF STATE TANK IS ORDERED, TANK MOUNTS BELOW SKID
3. TANK MAY EXTEND BEYOND ENCLOSURE (DISCHARGE END ONLY)
4. FOR STUB-UP ACCESS DURING INSTALLATION THE REAR
ENCLOSURE PANEL SHOULD BE REMOVED.
DIMENSIONS IN [] ARE IN ENGLISH EQUIVALENTS.
AIR DISCHARGE
ENGINE EXHAUST
OIL/COOLANT DRAIN
(BOTH SIDES
AIR INTAKE
AIR INTAKE
12X 25.4 [1.00]
MODEL
ENCLOSURE WEIGHT
KG [LBS]
STEEL WEATHER 363 [800]
STEEL SOUND 386 [850]
ALUMINIUM SOUND 238 [525]
B
C
D
12345678
A
B
C
D
TITLE
SCALE
DWG NO.
CAD NO. SHEET
DRAWN
CHECKED
APPROVED
MAX.
THIRD ANGLE
PROJECTION
POWER SYSTEMS, KOHLER, WI 53044 U .S.A.
THIS DRAWING IN DESIGN AND DETAIL IS KOHLER CO.
PROPERTY AND MUST NOT BE USED EXCEPT IN
CONNECTION WITH KOHLER CO. WORK. ALL RIGHTS OF
DESIGN OR INVENTION ARE RESERVED.
KEM
230-300 MODEL
JOHN DEERE TIER III
NOTE:
1. IF STANDARD TANK IS ORDERED, ENCLOSURE MOUNTS DIRECTLY TO TANK
2. IF STATE TANK IS ORDERED, TANK MOUNTS BELOW SKID
3. TANK MAY EXTEND BEYOND ENCLOSURE (DISCHARGE END ONLY)
4. FOR STUB-UP ACCESS DURING INSTALLATION THE REAR
ENCLOSURE PANEL SHOULD BE REMOVED.
OIL/COOLANT DRAIN
(BOTH SIDES)
AIR INTAKE
AIR INTAKE
AIR DISCHARGE
D O O R
C L E A R A N C E
T Y P
D O O R
C L E A R A N C E
T Y P
761 [30.0 ]
1339 [52.7 ]
53 [2.1 ]
1194 [47.0 ]
1300 [51.2 ]
78 [3.1 ]648 [25.5 ]
[22.0 ]
4108 [161.7 ]4108 [161.7 ]
100 [3.9 ]
[31.5 ]
[22.0 ]
4094 [161.2 ]
1521 [59.9 ]
469 [18.5 ] 2472 [97.3 ]
859 [33.8 ]
DOOR OPENING
D O O R
O P E N I N G
1811 [71.3 ]
P L E N U M
P A S S
T H R O U G H
779 [30.7 ]
PLENUM
112 [4.4 ]
100 [3.9 ]
103 [4.1 ]
PRO-EMETRIC
DIMENSION PRINT 230-300KW JD
0.06 3 of 4
ADV-7644 D
UNLESS OTHERWISE SPECIFIED -
1) DIMENSIONS ARE IN MILLIMETERS
2) TOLERANCES ARE:
X.XX 0.25
X.X 1.0
X 1.5 SURFACE FINISH
ANGLES 0 30'
APPROVALS DATE
SAM 2-5-13
KEM 2-5-13
2-5-13
REV DATE ON COMPOSITE DWGS, SEE PART NO. FOR REVISION LEVEL BY
F 2-5-13 SHEET 3 AND CA AQMD MODEL ADDED, SEE SHEET 4
[CT32174]
DJV
CA AQMD READY ENCLOSURES
(NO SILENCER)
EXHAUST OUTLET
SCALE 0.400
MODEL
ENCLOSURE WEIGHT
KG [LBS]
STEEL WEATHER 302 [665]
STEEL SOUND 325 [715]
ALUMINIUM SOUND 177 [390]
B
C
D
12345678
A
B
C
D
TITLE
SCALE
DWG NO.
CAD NO. SHEET
DRAWN
CHECKED
APPROVED
MAX.
THIRD ANGLE
PROJECTION
POWER SYSTEMS, KOHLER, WI 53044 U .S.A.
THIS DRAWING IN DESIGN AND DETAIL IS KOHLER CO.
PROPERTY AND MUST NOT BE USED EXCEPT IN
CONNECTION WITH KOHLER CO. WORK. ALL RIGHTS OF
DESIGN OR INVENTION ARE RESERVED.
KEM
SHEET 4 AND CA AQMD MODEL ADDED, SEE SHEET 3
[CT32174]
230-300 MODEL
JOHN DEERE TIER III
IBC/ OSHPD
NOTE:
1. IF STANDARD TANK IS ORDERED, ENCLOSURE MOUNTS DIRECTLY TO TANK
2. IF STATE TANK IS ORDERED, TANK MOUNTS BELOW SKID
3. TANK MAY EXTEND BEYOND ENCLOSURE (DISCHARGE END ONLY)
4. FOR STUB-UP ACCESS DURING INSTALLATION THE REAR
ENCLOSURE PANEL SHOULD BE REMOVED.
DIMENSIONS IN [] ARE IN ENGLISH EQUIVALENTS.
AIR DISCHARGE
OIL/COOLANT DRAIN
(BOTH SIDES
AIR INTAKE
AIR INTAKE
12X 25.4 [1.00]
D O O R
C L E A R A N C E
T Y P
761 [30.0 ]
1521 [59.9 ]
2018 [79.4 ]
4094 [161.2 ]
53 [2.1 ]
1300 [51.2 ]
1194 [47.0 ]
100 [3.9 ]
[31.5 ]
[22.0 ]
[22.0 ] 648 [25.5 ] 78 [3.1 ]
4121 [162.3 ]1338 [52.7 ]859 [33.8 ]
DOOR OPENING
D O O R
O P E N I N G
1822 [71.7 ]
1811 [71.3 ]
779 [30.7 ]
PLENUM
P L E N U M
P A S S
T H R O U G H
112 [4.4 ]
100 [3.9 ] 4
103 [4.1 ]
PRO-EMETRIC
DIMENSION PRINT 230-300KW JD
0.06 4 of 4
ADV-7644 D
UNLESS OTHERWISE SPECIFIED -
1) DIMENSIONS ARE IN MILLIMETERS
2) TOLERANCES ARE:
X.XX 0.25
X.X 1.0
X 1.5 SURFACE FINISH
ANGLES 0 30'
APPROVALS DATE
SAM 2-5-13
KEM 2-5-13
2-5-13
REV DATE ON COMPOSITE DWGS, SEE PART NO. FOR REVISION LEVEL BY
F 2-5-13
SAM
CA AQMD READY ENCLOSURES
(NO SILENCER)
EXHAUST OUTLET
SCALE 0.300
MODEL
ENCLOSURE WEIGHT
KG [LBS]
STEEL WEATHER 302 [665]
STEEL SOUND 325 [715]
ALUMINIUM SOUND 177 [390]
Model:230REOZJE
� Kohler Co. provides one-source responsibility for the generating system and accessories.
� The generator set and its components are prototype-tested, factory-built, and production-tested.
� The 60 Hz generator set offers a UL 2200 listing.
� The generator set accepts rated load in one step.
� The 60 Hz generator set meets NFPA 110, Level 1, when equipped with the necessary accessories and installed per NFPA standards.
� The generator set complies with ISO 8528-5, Class G2, requirements for transient performance in all generator set configurations. Select the Decision-Maker� 550 controller for improved voltage regulation and ISO 8528-5, Class G3, compliance.
� The 60 Hz generator set engine is certified by the Environmental Protection Agency (EPA) to conform to Tier 3 nonroad emissions regulations.
� A one-year limited warranty covers all systems and components. Two-, five-, and ten-year extended warranties are also available.
� Alternator features:
� The unique Fast-Response� II excitation system delivers excellent voltage response and short-circuit capability using a permanent magnet (PM)-excited alternator.
� The brushless, rotating-field alternator has broadrange reconnectability.
� Other features:
� Controllers are available for all applications. See controller features inside.
� The low coolant level shutdown prevents overheating (standard on radiator models only).
� Integral vibration isolation eliminates the need for under-unit vibration spring isolators.
Diesel208--600 V
Standard Features
Ratings Range 60 Hz
Standby: kW 225--230 kVA 281--288
Prime: kW 200--205 kVA 250--256
G5-339 (230REOZJE) 2/09
Generator Set Ratings
130�C Rise Standby Rating
105�C Rise Prime Rating
Alternator Voltage Ph Hz kW/kVA Amps kW/kVA Amps
4UA9
120/208 3 60 225/281 781 200/250 694
127/220 3 60 225/281 738 200/250 656
120/240 3 60 225/281 677 200/250 601
139/240 3 60 225/281 677 200/250 601
220/380 3 60 225/281 427 200/250 380
240/416 3 60 225/281 390 200/250 347
277/480 3 60 225/281 338 200/250 301
347/600 3 60 225/281 271 200/250 241
4UA13
120/208 3 60 230/288 798 205/256 711
127/220 3 60 230/288 754 205/256 672
120/240 3 60 230/288 692 205/256 616
139/240 3 60 230/288 692 205/256 616
220/380 3 60 230/288 437 205/256 389
240/416 3 60 230/288 399 205/256 356
277/480 3 60 230/288 346 205/256 308
347/600 3 60 230/288 277 205/256 247
RATINGS: All three-phase units are rated at 0.8 power factor. All single-phase units are rated at 1.0 power factor. Standby Ratings: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is nooverload capability for this rating. Ratingsare inaccordancewith ISO-3046/1, BS5514,AS2789, andDIN 6271. Prime Power Ratings: Prime power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in accordance with ISO-8528/1, overload power in accordance with ISO-3046/1, BS 5514, AS 2789, and DIN 6271. For limited running time and base load ratings, consult the factory. Obtain the technical information bulletin (TIB-101) on ratings guidelines for the complete ratings definitions. The generator set manufacturer reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. GENERAL GUIDELINES FOR DERATION: Altitude: Derate 0.5% per 100 m (328 ft.) elevation above 1000 m (3300 ft.).
Temperature: Derate 1.0% per 10�C (18�F) temperature above 25�C (77�F).
G5-339 (230REOZJE) 2/09
Alternator Specifications
Specifications Alternator
Manufacturer Kohler
Type 4-Pole, Rotating-Field
Exciter type Permanent magnet (PM) Brushless, Permanent-Magnet
Leads: quantity, type 12, Reconnectable
Voltage regulator Solid State, Volts/Hz
Insulation: NEMA MG1
Material Class H
Temperature rise 130�C, Standby
Bearing: quantity, type 1, Sealed
Coupling Flexible Disc
Amortisseur windings Full
Voltage regulation, no-load to full-load
Permanent magnet (PM) alternator ±2% Average
550 controller (with 0.5% drift due to temperature variation) 3-Phase Sensing, ±0.25%
Unbalanced load capability 100% of Rated Standby Current
One-step load acceptance 100% of Rating
Peak motor starting kVA: (35% dip for voltages below)
480 V 4UA9 (12 lead) 700
480 V 4UA13 (12 lead) 960
� NEMA MG1, IEEE, and ANSI standards compliance for temperature rise and motor starting.
� Sustained short-circuit current of up to 300% of the rated current for up to 10 seconds.
� Sustained short-circuit current enabling downstream circuit breakers to trip without collapsing the alternator field.
� Self-ventilated and dripproof construction.
� Vacuum-impregnated windings with fungus-resistant epoxy varnish for dependability and long life.
� Superior voltage waveform from a two-thirds pitch stator and skewed rotor.
� Fast-Response� II brushless alternator with brushless exciter for excellent load response.
Application Data
Engine
Engine Specifications
Manufacturer John Deere
Engine model 6090HF484
Engine type 4-Cycle, Turbocharged, Charge Air-Cooled
Cylinder arrangement 6 Inline
Displacement, L (cu. in.) 9.0 (548)
Bore and stroke, mm (in.) 118.4 x 136 (4.66 x 5.35)
Compression ratio 16.0:1
Piston speed, m/min. (ft./min.) 457 (1500)
Main bearings: quantity, type 7, Replaceable Insert
Rated rpm 1800
Max. power at rated rpm, kWm (BHP) 258 (346)
Cylinder head material Cast Iron
Crankshaft material Forged Steel
Valve material:
Intake Chromium-Silicon Steel
Exhaust Stainless Steel
Governor: type, make/model JDEC Electronic L14 Denso HP4
Frequency regulation, no-load to full-load Isochronous
Frequency regulation, steady state ±0.25%
Frequency Fixed
Air cleaner type, all models Dry
Exhaust
Exhaust System
Exhaust manifold type Dry
Exhaust flow at rated kW, m3/min. (cfm) 45.0 (1590)
Exhaust temperature at rated kW, dry exhaust, �C (�F) 401 (753)
Maximum allowable back pressure, kPa (in. Hg)
Min. 4 (1.2) Max. 10 (3.0)
Exhaust outlet size at engine hookup, mm (in.) 98 (3.86)
Engine Electrical
Engine Electrical System
Battery charging alternator: 24 Volt
Ground (negative/positive) Negative
Volts (DC) 24
Ampere rating 45
Starter motor rated voltage (DC) 24
Battery, recommended cold cranking amps (CCA):
Quantity, CCA rating each Two, 950
Battery voltage (DC) 12
G5-339 (230REOZJE) 2/09
Application Data
Fuel
Fuel System
Fuel supply line, min. ID, mm (in.) 11.0 (0.44)
Fuel return line, min. ID, mm (in.) 6.0 (0.25)
Max. lift, fuel pump: type, m (ft.) Electronic, 3 (10)
Max. fuel flow, Lph (gph) 240 (63.4)
Fuel prime pump Electronic
Fuel filter
Secondary 2 Microns @ 98% Efficiency
Primary 10 Microns
Water Separator Yes
Recommended fuel #2 Diesel
Lubrication
Lubricating System
Type Full Pressure
Oil pan capacity, L (qt.) 32.5 (34.4)
Oil pan capacity with filter, L (qt.) 33.4 (35.3)
Oil filter: quantity, type 1, Cartridge
Oil cooler Water-Cooled
Cooling
Radiator System
Ambient temperature, �C (�F) 50 (122)
Engine jacket water capacity, L (gal.) 16 (4.25)
Radiator system capacity, including engine, L (gal.) 36 (9.5)
Engine jacket water flow, Lpm (gpm) 265 (70)
Heat rejected to cooling water at rated kW, dry exhaust, kW (Btu/min.) 110.4 (6280)
Heat rejected to air charge cooler at rated kW, dry exhaust, kW (Btu/min.) 63.3 (3600)
Water pump type Centrifugal
Fan diameter, including blades, mm (in.) 863.6 (34.0)
Fan, kWm (HP) 9 (12.1)
Max. restriction of cooling air, intake and discharge side of radiator, kPa (in. H2O) 0.125 (0.5)
Operation Requirements
Air Requirements
Radiator-cooled cooling air, m3/min. (scfm)� 311.5 (11000)
Combustion air, m3/min. (cfm) 20.7 (730)
Heat rejected to ambient air:
Engine, kW (Btu/min.) 49.4 (2810)
Alternator, kW (Btu/min.) 21.4 (1220)
� Air density = 1.20 kg/m3 (0.075 lbm/ft3)
Fuel Consumption
Diesel, Lph (gph) at % load Standby Rating
100% 61.0 (16.1)
75% 46.8 (12.4)
50% 33.1 (8.7)
25% 19.7 (5.2)
Diesel, Lph (gph) at % load Prime Rating
100% 53.3 (14.1)
75% 40.9 (10.8)
50% 29.2 (7.7)
25% 17.4 (4.6)
Controllers
Decision-Maker� 550 Controller Audiovisual annunciation with NFPA 110 Level 1 capability.
Programmable microprocessor logic and digital display features.
Alternator safeguard circuit protection.
12- or 24-volt engine electrical system capability.
Remote start, remote annunciation, and remote communication options.
Refer to G6-46 for additional controller features and accessories.
Decision-Maker� 3+, 16-Light Controller Audiovisual annunciation with NFPA 110 Level 1 capability.
Microprocessor logic, AC meters, and engine gauge features.
12- or 24-volt engine electrical system capability.
Remote start, prime power, and remote annunciation options.
Refer to G6-30 for additional controller features and accessories.
Overall Size, L x W x H, mm (in.): 3000 x 1300 x 1689 (118.1 x 51.2 x 66.5)
Weight (radiator model), wet, kg (lb.): 2268--2449 (5000--5400)
© 2009 by Kohler Co. All rights reserved.
DISTRIBUTED BY:
Dimensions and Weights
NOTE: This drawing is provided for reference only and should not be used for planning installation. Contact your local distributor for more detailed information.
H
W L
G5-339 (230REOZJE) 2/09
Additional Standard Features � Alternator Protection (standard with 550 controller)
� Battery Rack and Cables
� Emission Compliant Engine
� Integral Vibration Isolation
� Oil Drain Extension
� Operation and Installation Literature
Available Options
Approvals and Listings
� CSA Approval
� IBC Seismic Certification
� UL 2200 Listing
Enclosed Unit
� Sound Enclosure and Subbase Fuel Tank Packages
� Weather Enclosure and Subbase Fuel Tank Packages
Open Unit
� Exhaust Silencer, Critical (kit: PA-354809)
� Exhaust Silencer, Hospital (kit: PA-365349)
� Flexible Exhaust Connector, Stainless Steel
Fuel System
� Auxiliary Fuel Pump
� Flexible Fuel Lines
� Fuel Pressure Gauge
� Subbase Fuel Tanks
Controller
� Common Failure Relay
� Communication Products and PC Software (550 controller only)
� Customer Connection
� Dry Contact (isolated alarm)
� Prime Power Switch (550 controller only)
� Remote Annunciator Panel
� Remote Audiovisual Alarm Panel
� Remote Emergency Stop
� Remote Mounting Cable
� Run Relay
Cooling System
� Block Heater (recommended for ambient temperatures below 0°C [32°F])
� Radiator Duct Flange
Electrical System
� Alternator Strip Heater
� Battery
� Battery Charger, Equalize/Float Type
� Battery Heater
� Line Circuit Breaker (NEMA type 1 enclosure)
� Line Circuit Breaker with Shunt Trip (NEMA type 1 enclosure)
� Safeguard Breaker (16-light controller)
Paralleling System
� Reactive Droop Compensator
� Voltage Adjust Control
� Voltage Regulator Relocation
Miscellaneous
� Air Cleaner, Heavy Duty
� Air Cleaner Restriction Indicator
� Crankcase Emissions Canister
� Engine Fluids (oil and coolent) Added
� Rated Power Factor Testing
� Rodent Guards
� Skid End Caps
Literature
� General Maintenance
� NFPA 110
� Overhaul
� Production
Warranty
� 2-Year Basic
� 2-Year Prime
� 5-Year Basic
� 5-Year Comprehensive
� 10-Year Major Components
Other Options
Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore 619159 Phone (65) 6264-6422, Fax (65) 6264-6455
KOHLER CO., Kohler, Wisconsin 53044 USA Phone 920-565-3381, Fax 920-459-1646 For the nearest sales and service outlet in the US and Canada, phone 1-800-544-2444 KohlerPower.com
| A 01 S&D B155 New Generator 230REOZJE (Enclosure Specifications) |
| A 01 S&D B155 New Generator 230REOZJE (Enclosure) |
| Sheet 1 |
| Views |
| new_view_9 |
| right_10 |
| right_11 |
| top_12 |
| Sheet 2 |
| Views |
| top_4 |
| new_view_5 |
| new_view_6 |
| new_view_7 |
| Sheet 3 |
| Views |
| new_view_14 |
| new_view_15 |
| new_view_16 |
| new_view_17 |
| new_view_23 |
| Sheet 4 |
| Views |
| new_view_19 |
| new_view_20 |
| new_view_21 |
| new_view_22 |
| new_view_24 |