Attach_1_ESE-SIT-0001_-_Fence_Sensor_Platform_Requirements.pdf

PDF 1 MB Posted

Attached to
Construct Global ASNT Platform Federal contract opportunity
Solicitation number
W912JB-19-B-5008
Issued by
Department of the Army Michigan Army National Guard

About this file

Attach 1 ESE-SIT-0001-Fence Sensor Platform Req

View the file

Other files for this federal contract opportunity

Other files attached to Construct Global ASNT Platform, newest first.
File Type Posted
Attach_4_Footprint_Diagrams_05252016.pdf PDF
SANGB_Vetting_Access_Request_-.pdf PDF
Attach_3_Global_ASNT_Platform_Dimensions_032116.pdf PDF
Attach_5_Utility_Map.pdf PDF
Attach_2_Global_ASNT-10_May_2018.pdf PDF
W912JB19B5008.pdf PDF
Attach_0_VGLZ182012_-_Const_GASNT_SoW_(updated).pdf PDF
Attach_1_GASNT_Fencing_Details.docx DOCX document
Attach_6_Selgridge_GANST_Points_2019.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ESE-SIT-0001

12 JANUARY 2017

2 5

. Each FDB shall be grounded with a grounding rod, which will be commonly bonded with power and sensor ground in the FDB on a common ground bus (Commonly ground means to ground the FDB door, the sensor, and the power on the same grounding bus/strip). In addition, when securing a ground bus/strip verify that all paint and or foreign substance that would preclude continuity of the signal path has been removed. The FDB ground wire shall be attached to the grounding rod by exothermic welding. Ensure that clear, secured Plexiglas anti-shock shield covers are installed over 110v or higher electrical supply and exposed wires.

. Security alarm monitoring facilities containing major concentrations of security equipment such as consoles shall be provided with a lightning protection system including air terminals, down conductors, surge arrestors and station grounds, all connected to a common facility grounding system. IDE located outdoors, such as an Environmentally Control Enclosure, shall be grounded and provided proper lightning protection.

. Surge protection shall be provided for exterior sensor equipment, Field Distribution Boxes, and camera equipment. Surge protection shall be on input and output circuits of field equipment boxes to protect transponders and power supplies.

. Interior sensor surge protection devices will be grounded to an existing facility ground provided the ground is thoroughly checked for integrity. If a proper facility ground is not available, a code compliant ground shall be installed in accordance with the National Electric Code (NEC).

. The fault protection subsystem consists of a separate grounding conductor to provide protection to personnel and equipment from static charge buildup and electrical faults.

The fault protection subsystem shall provide a conductive path between the earth electrode subsystem and all exposed metal parts of electrical enclosures. Fault protection will be provided for exterior and interior equipment. It is provided by an equipment-grounding conductor routed from the equipment to the AC power distribution panel.

. This interior subsystem is that part of a ground system that is used to provide a ground reference plane for all signal paths. It is used essentially to control noise. A proper Signal Reference Subsystem shall be installed for security systems in accordance with MIL-HDBK-419A.

All security equipment cases or cabinets must be bonded to the equipotential planes by the shortest and most direct route.

. Bonding is essential in all circuits, both communications and power, as well as in lightning protection, where conductors must be joined. Welding, brazing, and clamping are common bonding methods. The engineer must specify bonding requirements per MIL-STD-188-124 and MIL-

HDBK-419A.

. Shielding prevents the security equipment or cabling from propagating interference and also protects it from similar effects by other electrical or electronic systems. It is the engineer’s responsibility to specify the proper type of shielding to be used for security equipment and cabling, and to adhere to standards in MIL-HDBK-419A.

The following paragraphs are intended to provide the security system designer, engineer or fencing contractor with a comprehensive reference for the sensor-compatible fence specification for

2 6 electronic security sensors. Experience in the fielding of these systems has demonstrated that conventional fence installation practices must be supplemented in several key areas to achieve the desired minimum performance standards. Refer to attached drawing FPB-ASSY-SC02-01R0C0, Sheets 1-5 for illustration of a Fence, IDS Sensor Platform used to support a fence sensor installation. ( : Softcopy drawings in CAD format can be obtained from: AFLCMC/HBU, Force Protection Branch, 3 Eglin Street, Hanscom AFB, MA.) The following guidance is intended to represent minimum requirements, and apply in part or in total to systems and subsystems identified in the remainder of this document. Specific sections should be referenced to ensure all sensor equipment requirements are considered.

If Anti-Ram Cabling is to be used in conjunction with the fence, the anti-ram cable shall not affect the fence sensor performance. The anti-ram cable shall be taut to ensure no movement in normal environmental conditions. The anti-ram system shall not add any nuisance alarms to the sensor. The anti-ram system shall not be able to be used as a climbing aide.

. Requirements specified herein are necessary for acceptable performance of approved security sensor systems for new and existing fences. Proper sensor performance is contingent on both the condition of the fence and proper installation practices. Further information on sensor use and installation are provided in other sections of this document.

. To assist the using and installing agencies in the proper design of sensor compatible security fences (referred to as Fence, IDS Sensor Platform), the Force Protection Branch has prepared standard drawings for Fence, IDS Sensor Platform construction, which are shown in attached drawing FPB-ASSY-SC02-01R0C0, Sheets 1-5 and Source Control Drawing FDTA155. ( :

Softcopy drawings in CAD format can be obtained from: AFLCMC/HBU, Force Protection Branch, 3 Eglin Street, Hanscom AFB, MA)

. Fence, IDS Sensored Platforms shall use materials conforming to Federal Specification RR-F191 series and the following specified components:

. All fence fabric shall comply with Federal Specification RR-F191 series (Chain Link Fence Fabric) with standard 2 square mesh, 9 gauge aluminized steel wire, minimum 7 foot height, one selvage is knuckled, the other, twisted. The twisted selvage should be at the top of the fence, with the knuckled selvage at the bottom. The Type II, aluminum-coated steel wire shall be used for permanent security applications, since it is less likely to require re-tensioning due to wear at a later date. Use of zinc-coated (galvanized) wire is acceptable for existing fences, and may be used for short-term applications otherwise Type II, aluminum-coated steel wire is required.

. Shall be round components and comply with Federal Specification RR-F191 series (Chain Link Fence Posts, Braces and Rails). Tables 2-1 and 2-2 provide required fence component sizes and strengths. Gateposts should be designed to support the gates proposed. Minimum requirements are given in FS RR-F191/3D. Gateposts supporting hardware for swing, rolling, cantilever or lift gates must also be isolated from fabric carrying posts. Gateposts shall be a minimum of 4” outer diameter (O.D.) and be sized according to Table 2-1. Corner, end and pull posts shall be of adequate height to accept barbed wire terminations. The overall height of these posts, when fitted with cap dome and anti-tamper spike shall be equal to the height of the line posts with the vertical outriggers. The fence system shall be designed and installed so that the distance between corner, end and pull post in any continuous fence run, do not exceed 100 meters.

2 7

Bottom or Brace Rails 1.660” Line Posts 2.875” Corner and end posts 6.625” Pull post and single Gate Posts – equal or less than 12’ Width 4.5” Double Gate Posts – equal or less than 24’ Width 4.5” Single Gate Posts – greater than 12’ and less than 18’ Width 6.625” Double Gate Posts – greater than 24’ and less than 36’ Width 6.625” Single Gate Posts – over 18’ Width 8.625” Double Gate Posts – over 36’ Width 8.625”

1 5/8” 1.660” .140” 30,000

2 ½” 2.875” .203” 30,000

4” 6” 8”

4.500” 6.625” 8.625”

.237”

.280”

.322”

30,000 30,000 30,000

. All post caps, barbed wire outriggers, tension/stretcher bars (3/16" x 3/4"), brace bands, tension bands, hinges and other fittings shall be pressed steel and galvanized. Aluminum fittings are not authorized.

. Three (3) tension wires shall be used in the standard fence design. The wires shall be stretched taut to help support the tension of the fence fabric and pass the tests identified in paragraph 2.6.5; in order to achieve success in these tests tension wires shall be tensioned to 500 pounds. The top tension wire shall be approximately 7.5 inches below the top of the fabric. The other two tension wires shall be located at approximately 31 and 56½ inches down, respectively, from the top of the fence fabric.

All tension wires shall be galvanized 7 gauge hardened steel spring wire. Tension wires shall be connected to corner, end and pull posts and will be limited to zone length. One end of each wire shall be secured to an appropriately sized brace band and the other with a turnbuckle. The tension wires shall be connected to the brace bands and turnbuckles using double barrel swages. If tension wires are spliced, swages shall be used.

. Fabric shall be firmly secured to line posts and rails with 9 gauge galvanized steel tie wire. Firmly secure fabric to tension wires with 9 gauge aluminized steel wire ties. The use of hog rings or aluminum wires of any gauge are not permitted.

a. . All footings shall be designed to sustain the projected lateral forces and point loads. The sizes in Table 2-3 are given as a minimum. Individual site conditions including soil

2 8 strength, wind and ice loading on the fabric and sensors will affect footing size. Consideration shall be allotted for radial loads imposed by curved horizontal alignments. Concrete footings will be cylindrical utilizing concrete column forms and will extend, as a minimum, to the depths identified in Table 2-3 or the depth calculated using the International Building Code (IBC) sections 1804 and 1805 and the UFC 3-301- 01 (Reference FPB-ASSY-SC02-001R0C0 SHEET5), whichever is greater, at all locations; when the frost line equals or exceeds the concrete footing depth identified from the calculations described above the footing shall extend a minimum of 3” below the frost line.

Line Pull

12” 18”

4’-0” 4’-0”

End and Corner 24” 4'-0" Gate 16" + Gate Post Diameter 4'-0"

b. . All footings shall be designed to sustain cold weather temperatures at the local area frost depth. Foundations for Line Posts, End Posts, Corner Posts Pull Posts, and Gate Posts shall be installed to a minimum depth of 7’6” or the depth calculated using the IBC sections 1804 and 1805 and the UFC 3-301-01 (Reference FPB-ASSY-SC02-001R0C0 SHEET 5), whichever is greater, in concrete formed using concrete column forms of the same diameters identified in Table 2-3.

c. . The strength of all concrete footings shall be no less than 3000 psi. The concrete shall be mixed, transported, handled and placed in accordance with Unified Facilities Guide Specification, Division 03 Concrete, Section 03 30 00 Cast-In-Place Concrete. The top of the post-footings shall be finished so that at the post the concrete is 1/2” to 1” above grade and sloped 1/2" down to the footing edge.

. The IDS sensor platform shall be configured with vertical outriggers, unless the VTW- 400 sensor system is intended to be used (Reference section 15 of this document) and shall have no top rail.

“Y” outrigger configuration may be used only if directed and approved by the Government and if this occurs, the specification shall be provided by the Government. Vertical outriggers require fabrication to include caps to fit the fence posts, breakaway cutouts, support-notches for barbed wire, and an anti-climbing spike. An example of an outrigger is shown in Figure 2-1 and fabrication dimensions can be found in the attached Source Control Drawing FDTA155. Vertical outriggers will be 37 ½” measured from the top of the post cap with an anti-climb spike extending another 5” at the top. Corner, pull, end and gate posts shall be equipped with top cap domes with an anti-climb spike.

. The barbed wire shall be 4-point, 15.5 gauge high tensile barbed, with 5" Barb Spacing and a minimum breaking load of 950 lbs. The barbs located within 4” of the outriggers shall be removed. Barbed wires will pass through the vertical outrigger notches and be connected to corner, end or pull posts and will be limited to zone length. Barbed wire shall be secured to pull, end, and corner posts using brace bands with a ratchet tensioner at one end and a turnbuckle at the other (Reference FPB-ASSY- SC02-001R0C0 SHEET 4). The barbed wire shall be secured using swages. If barbed wire requires splicing, swages shall be used. All barbed wire shall be tightened to 50-70 pounds upon installation and then adjusted appropriately at sensor installation. After the barbed wire is appropriately tightened for the sensor, the barbed wire shall be secured to all the vertical outriggers with 6” long, double-looped, 18 gauge stainless steel twist ties with the twists on the secure side of the outriggers.

2 9

. Installation standards for fences used to support security sensors exceed those required for standard chain link or cyclone fence installation. Installers are expected to comply with detailed instructions and testing requirements to create successful sensor platform fences.

. Fence alignment and layout become critical when marked changes of horizontal and vertical direction occur. The ideal security system platform fence is absolutely straight and level between any two vertical and horizontal points. Changes of direction that produce an angle of less than 65° on the secure side or unsecure side of the fence shall be avoided. If a situation arises where a smaller angle may occur, Government approval is required.

. Fabric shall be installed twisted selvage up and knuckled selvage down. The fabric shall extend below the bottom rail enough to have at least the first row of complete diamonds partially below the bottom rail and shall not touch the grade or concrete footings. It will be anchored to prevent intruders from lifting the fabric and creating an opening greater than 5”. Fabric shall be securely fastened using materials specified in 2.6.3.5 according to the following spacing:

All Posts 14" O.C.

All Rails 12" O.C.

All Tension Wires 15" O.C.

All ties will be twisted at least three (3) complete turns and be terminated on the secure (interior) side of the fabric. The ties shall be twisted to restrict any movement of the fence fabric at the contact point of the tie, fence fabric, tension wire, posts and rails. If possible, ties will cross two pickets at a knuckle. If not, the picket closest to the pipe or wire will be tied. The ties on line posts shall be placed 14” O.C. and a tie shall be placed within 4 inches from the top and bottom of the fabric. Fence fabric to line post wire ties shall be installed so that twisted ends are parallel to the fabric. All other fabric wire ties shall be installed so that the twisted ends are perpendicular to the fabric.

. Bottom rails are required with all sensored fences. Sensored fences do not contain a top rail. The top rail must be removed from existing fences. All bottom rails shall be a single continuous piece from post to post braced with in-line bottom rail clamps (boulevards) except at corner and end posts where bottom rail end caps with brace bands will be used.

Post caps and outriggers shall be tack welded or riveted to posts to prevent movement. Also brace bands at corner, pull, end, and line posts shall be tack welded prior to fabric placement to prevent bands from shifting. Welds shall be corrosion treated with galvanized paint.

Brace assemblies are required to counteract lateral forces and shall be located at each corner, end and pull post. In some cases, two braces will be required in a single panel. The configuration and installation shall be in such a way that the test requirements in paragraph 2.6.5 are met.

All fence bolted hardware shall have the threaded ends on the secure side of the fence to prevent tampering.

. Signs shall not be installed on the sensored fence. If required, ensure signs are securely fastened to a separate post or an animal control fence.

2 11

. Prior to conducting strength tests, all new and existing chain link fences intended for use as security sensor platforms shall be visibly inspected for:

loose or broken fabric loose posts broken, loose or missing ties proper tie spacing broken post or rails loose or missing hardware cracked or broken foundation concrete corrosion missing tack welds inadequate bracing and trusses out-of-plumb posts and fabric

Particular attention should be given during the testing portion of the inspection to any areas identified by this visual inspection. All broken or missing parts (including concrete) shall be replaced prior to conducting the tests described below.

. Prior to sensor installation, the following tests shall be performed to determine the acceptability of the fence for sensor installation. Tests shall not be conducted when the ground is frozen nor when the ambient air temperature is below 40°F.

. All posts shall be tested by applying a 50 lb. Force to the post at a height of 5 ft. above the ground from the base of the post and the results recorded. The post shall not deflect more than 1/2" at the point of application of the force. If deflection exceeds 1/2", the post shall be removed and a new post installed. Posts must be capable of resisting projected lateral forces as determined by the security system engineer and/or fencing contractor. Replace posts not achieving minimal acceptable requirements.

. All fence fabric panels shall be tested for integrity and capability for use with the sensor system. The test shall be conducted by applying 30 lbs of pull on the fabric and then 30 lbs of push at a point midway between the posts and at 5’ above grade. The deflection shall not exceed 2 inches from the "at-rest" position. The tension on the fabric when this is achieved will be about 1000 pounds. If the deflection exceeds this amount, the connections between the fabric and posts, rails, and top wire shall be checked to ensure that the fabric is attached to the bottom rails by appropriate ties at intervals not exceeding 12 inches and to the posts in at least five equally spaced locations to include the top and bottom of the fabric. If these requirements are not satisfied, new ties shall be installed at the proper interval and the test performed again. If the deflection still exceeds the allowable, the fabric shall be re-tensioned and ties installed per these specifications.

2 12

FPB-ASSY-SC02-01R0C0, Sheets 1-5

Source Control Drawing FDTA155

2 13

2 14

2 15

2 16

2 17

2 18

2 19

Do all fence components ordered meet specifications? (e.g., correctly sized posts, galvanized ties, bottom rails, fabric, etc.)

Have the foundation holes been excavated in the correct locations and are they of the correct diameter and depth?

Correct Depth is _______ inches.

Are the posts plumb and at the proper depth in the footing? Is the top of the post at the proper height?

Has the concrete cured? Is the foundation crowned at the post? Is there no visible cracking?

Do grounding rods meet ESE-SIT-0001 Section 2 grounding requirements? Are all grounding measurements recorded and attached to this document?

Have the brace rails been properly placed and have their clamps been tack welded in place on the posts?

Are the tension wires at the correct heights?

Is the fence fabric tensioned correctly? Is the fence fabric at the correct height and secured correctly with proper tie spacing?

Are the outriggers and dome caps with spike properly installed and secured with a weld or rivet? If the VTW-400 Sensor is to be used are VTW-400 Vertical Outriggers properly installed on the fence posts?

Is the barbed wire secured correctly to posts and outriggers and are the barbs within 4 inches of the outriggers removed?

Is the barbed wire installed and tensioned properly? (e.g., the barbed wire doesn’t sag or move in light wind)

Has the ground been brought to final grade to meet fence clearance requirements? (e.g., fabric does not touch grade)

Are all deviations documented and attached to this document?

Are Redline Drawings updated to reflect all in field changes?

System is ready to test.

QA MANAGER DATE