W912DR-17-B-0014-0006.pdf

PDF 5 MB Posted

Attached to
CANINE TRAINING FACILITY JJRTC Federal contract opportunity
Solicitation number
W912DR-17-B-0014
Issued by
Department of the Army Corps of Engineers Engineering District Baltimore

About this file

Amendment 0006

View the file

Other files for this federal contract opportunity

Other files attached to CANINE TRAINING FACILITY JJRTC, newest first.
File Type Posted
D1_BID_ABSTRACT.pdf PDF
C-5_17B0014 0005 - Copy —
C-5_17B0014_0005_-_Copy_(2).7z 7Z file
19_Sept-17_Site_Visit_Sign_in_Sheet.pdf PDF
W912DR-17-B-0014-0004.pdf PDF
W912DR-17-B-0014-0003.pdf PDF
W912DR-17-B-0014-0003.pdf PDF
Site_Visit_Sheet__Sign_In_Sheet.pdf PDF
W912DR-17-B-0014-0001.pdf PDF
B3_Final_JUSTIFICATION_AND_APPROVAL_K9_Brand_Name.pdf PDF
JJRTC_CANINE_W912DR-17-B-0014.pdf PDF
Show all 11

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

The purpose of this amendment is to do the follow ing :

1. Update Plans & Specifications ( Please see attachment)

2. Respond to RFI Questions ( Please see attachment)

3. Extend bid opening date to 10/16/17 11AM EST

1. CONTRACT ID CODE PAGE OF PAGES

1 2

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 06-Oct-2017

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912DR-17-B-0014

X 9B. DATED (SEE ITEM 11)

24-Aug-2017

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

09-Oct-2017

CODE

U.S. ARMY CORPS OF ENGINEERS, BALTIMORE

10 SOUTH HOWARD STREET

BALTIMORE MD 21201

W912DR 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W912DR-17-B-0014

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

SUMMARY OF CHANGES

SECTION 00010 - SOLICITATION CONTRACT FORM

The required response date/time has changed from 12-Oct-2017 10:00 AM to 16-Oct-2017 11:00 AM.

(End of Summary of Changes)

W912DR-17-B-0014 5 Oct 2017

AMENDMENT 5 changes:

1) Amendment Item 27 SHEET GC101 Issue Block: Insert the “Revision 1” triangle, “Revised Per Amendment” and “9/14/2017” in the “MARK”, “DESCRIPTION”, and “DATE” columns respectively.

2) Amendment Item 28 SHEET GC102: Delete this sheet dated 9/14/2017 and substitute therefor the attached like-numbered sheet dated 10/3/2017.

3) Amendment Item 29 SHEET GC103: Delete this sheet dated 9/14/2017 and substitute therefor the attached like-numbered sheet dated 10/3/2017.

4) Amendment Item 33 SHEET GC505: Delete this sheet dated 9/14/2017 and substitute therefor the attached like-numbered sheet dated 10/3/2017.

5) Amendment Item 25 SHEET CG101: Delete this sheet dated 9/14/2017 and substitute therefor the attached like-numbered sheet dated 10/3/2017

SPECIFICATIONS:

6) Section 01 33 29 SUSTAINABILITY REPORTING: Revise all occurrences of “SILVER” to read “CERTIFIED”.

7) Section 01 33 29 SUSTAINABILITY REPORTING Paragraph 1.6.3: In the first sentence after “….Section 6.3.2” add the following “and specification section 22 00 00, whichever is most efficient”.

8) Section 01 33 29 SUSTAINABILITY REPORTING Paragraph 1.6.3: Revise the second sentence to read “Implement IAQ plan during construction and perform air testing after construction ends and before occupancy to meet the requirements and earn the points for Indoor Air Quality Assessment credit, option 2.”

9) Section 01 33 29 SUSTAINABILITY REPORTING: Immediately following this Section insert the attached LEED Project Checklist.

10) Section 06 10 12 CONSTRUCTION OF NEW BLEACHER PAVILION Paragraph 1.1.

c, d, and e: Revise these to read

“c. Construct a new slab-on-grade and Pavilion to match the existing size.

The Contractor is responsible to verify the existing dimensions.

Construction shall be in accordance with this specification.

d. Provide a new 14' x 20' concrete slab on grade.

e. Provide a new 18' x 24' hip roof.”

11) Section 10 22 39 - FOLDING PANEL PARTITIONS Sub-paragraph 1.2.2.2: In the first sentence delete the words “…for perforated steel…”.

12) Section 10 22 39 - FOLDING PANEL PARTITIONS Paragraph 3.2.2 Acoustical Test: Delete this paragraph entirely.

13) Section 22 00 00 PLUMBING, GENERAL PURPOSE Paragraph 2.7.2: Delete this paragraph entirely and substitute therefor the following

“Provide single control pressure equalizing bathtub and shower faucets with body mounted from behind the wall with threaded connections. Provide ball joint self-cleaning shower heads. Provide shower heads which deliver a maximum of 1.5 GPM. Showerheads must meet the EPA WaterSense product definition specified in http://www.epa.gov/watersense/partners/product_program_specs.html and must be EPA WaterSense labeled products. Provide tubing mounted from behind the wall between faucets and shower heads. Provide separate globe valves or angle valves with union connections in each supply to faucet.”

14) Section 27 10 00 BUILDING TELECOMMUNICATION CABLING SYSTEM Paragraphs

2.5.2 and 2.5.3: Revise “duplex SC” to read “duplex LC” and revise the Submittal Register to reflect this change.

PLANS:

15) SHEET CS101: Delete this sheet as originally issued and substitute therefor the attached like-numbered sheet dated 10/3/2017.

16) SHEET CS501: Delete this sheet as originally issued and substitute therefor the attached like-numbered sheet dated 10/3/2017.

17) SHEET ES101: Delete this sheet as originally issued and substitute therefor the attached like-numbered sheet dated 9/22/2017.

18) SHEET ESD101: Delete this sheet as originally issued and substitute therefor the attached like-numbered sheet dated 9/22/2017.

19) SHEET EP601: Delete this sheet as originally issued and substitute therefor the attached like-numbered sheet dated 9/22/2017.

GENERAL:

Attached For Information Only are Questions and Answers dated 10/5/2017

ATTACHMENTS:

- LEED Project Checklist -SHEET CG101 dated 10/3/2017 -SHEET CS101 dated 10/3/2017

-SHEET CS501 dated 10/3/2017 -SHEET GC102 dated 10/3/2017 -SHEET GC103 dated 10/3/2017 -SHEET GC505 dated 10/3/2017 -SHEET ES101 dated 9/22/2017 -SHEET ESD101 dated 9/22/2017 -SHEET EP601 dated 9/22/2017 -Questions and Answers

LEED v4 for BD+C: New Construction and Major Renovation Project Checklist Canine Training Facility and Kennels

10/4/2017 Y ? N

1 Credit 1

2 0 14 16 3 8 2 13 16 Credit 16 Y Prereq Required

1 Credit 1 Y Prereq Required

2 Credit 2 3 2 Credit 5

5 Credit 5 2 Credit 2

5 Credit 5 2 Credit 2

1 Credit 1 1 1 Credit Building Product Disclosure and Optimization - Material Ingredients 2

1 Credit 1 2 Credit 2

1 Credit Green Vehicles 1

13 3 0 Indoor Environmental Quality 16 7 0 3 10 Y Prereq Required

Y Prereq Required Y Prereq Required

1 Credit 1 2 Credit 2

1 1 Credit 2 2 1 Credit 3

1 Credit 1 1 Credit Construction Indoor Air Quality Management Plan 1

3 Credit 3 2 Credit 2

2 Credit 2 1 Credit 1

1 Credit 1 2 Credit 2

2 1 Credit 3

4 0 7 11 1 Credit 1

Y Prereq Required 1 Credit 1

Y Prereq Required

Y Prereq Building-Level Water Metering Required 1 0 5 Innovation 6 2 Credit 2 5 Credit 5

1 5 Credit 6 1 Credit 1

2 Credit 2

1 Credit Water Metering 1 2 1 0 Regional Priority 4 1 Credit Regional Priority: Green Vehicles 1

9 2 22 33 1 Credit Regional Priority: Site Development- protect or restore habitat 1

Y Prereq Required 1 Credit Regional Priority: Surrounding density and diverse uses 1

Y Prereq Required Credit Regional Priority: Specific Credit 1

Y Prereq Required

Y Prereq Required 42 14 53 TOTALS Possible Points: 110 5 1 Credit 6

2 2 14 Credit 18

1 Credit 1

2 Credit 2

3 Credit 3

1 Credit 1

2 Credit 2

Site Development - Protect or Restore Habitat

Building Product Disclosure and Optimization - Sourcing of Raw Materials

Project Name:

Date:

Location and Transportation

Sensitive Land Protection

LEED for Neighborhood Development Location

Bicycle Facilities

Construction and Demolition Waste Management Planning

Materials and Resources Storage and Collection of Recyclables

Construction and Demolition Waste Management

Minimum Indoor Air Quality Performance

Building Product Disclosure and Optimization - Environmental Product Declarations

Integrative Process

Construction Activity Pollution Prevention

High Priority Site

Surrounding Density and Diverse Uses

Sustainable Sites

Building Life-Cycle Impact Reduction

Green Power and Carbon Offsets

Heat Island Reduction

Outdoor Water Use Reduction

Indoor Water Use Reduction

Outdoor Water Use Reduction

Indoor Water Use Reduction

Enhanced Commissioning

Building-Level Energy Metering

Water Efficiency

Fundamental Commissioning and Verification

Demand Response

Renewable Energy Production

Enhanced Refrigerant Management

Optimize Energy Performance

Advanced Energy Metering

Certified: 40 to 49 points, Silver: 50 to 59 points, Gold: 60 to 79 points, Platinum: 80 to 110

Access to Quality Transit

Reduced Parking Footprint

Open Space

Site Assessment

Interior Lighting

Daylight

LEED Accredited Professional

Innovation

Rainwater Management

Light Pollution Reduction

Environmental Tobacco Smoke Control

Energy and Atmosphere

Minimum Energy Performance

Fundamental Refrigerant Management

Cooling Tower Water Use

Acoustic Performance

Quality Views

Enhanced Indoor Air Quality Strategies

Low-Emitting Materials

Indoor Air Quality Assessment

Thermal Comfort

1 2 3 4 5

D R

A W

N

B

Y

D E

S I G

N

B

Y

S B

M T

B

Y

S I Z

E

F I L

E

N

A M

E

I S

S U

E

D

A T

E

C O

N T

R A

C

N

O

S O

L I C

I T

A T

I O

N

N

O

U S

A

R M

Y

C

O R

P

F

E

N G

I N

E E

R S

C K

D

B

Y

US Army Corps of

Engineers ® x

D

C

B

A

F I L E

M

B E

R

P L

A

L E

P L

T

E

A U

G U

Baltimore District

X X

X

B A

L T

I M

O R

E

D

I S

T R

I C

T

B A

L T

I M

O R

E

M

A R

Y L

A N

D

M I L

I T

A R

Y

D

E S

I G

N

B

R A

N C

H

E N

G I N

E E

R I N

G

D

I V

I S

I O

N

C A

N I N

E

T

R A

I N

I N

G

F

A C

I L I T

K

N

N E

L S

M A

R K

D E

S C

R I P

T I O

N D

A T

E A

P P

R

P

M

E

S

D

W G

L A

U R

R

Y L

A N

D

U S

G A

ES101

E L

E C

T R

I C

A L

S I T

E

P

L A

N

E S

D

W G

ESD101

L

E C

T R

I C

I T

E

D

E M

O L

I T

I O

N

P

L A

N

Y E

C M

W D

Y E

C M

W D

Y E

C M

W D

H O

W N

1 2 3 4 5

D R

A W

N

B

Y

D E

S I G

N

B

Y

S B

S I Z

E

F I L

E

N

A M

E

I S

S U

E

D

A T

E

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

M

Y

C

O R

E

N G

I N

E E

R S

C K

D

B

Y

US Army Corps of

Engineers ® x

D

C

B

A

F I

M

B E

R

P L

A

L E

P L

T

E

A U

G U

Baltimore District

X X

X

B A

L T

I M

O R

E

D

I S

T R

I C

T

B A

L T

I M

O R

E

M

A R

Y L

A N

D

M I L

I T

A R

Y

D

E S

I G

N

B

R A

N C

H

E N

G I N

E E

R I N

G

D

I V

I S

I O

N

C A

N I N

E

T

R A

I N

I N

G

F

A C

I L I T

N

N E

L S

M A

R K

D E

S C

R I P

T I O

N D

A T

E A

P P

R

P

M

E

S D

D

W G

L A

U R

R

Y L

A N

D

U S

G A

60A

RTU-6

GENERAL NOTES:

1. REFER TO SHEETS E000 AND E001 FOR ELECTRICAL

SYMBOLS, ABBREVIATIONS, AND GENERAL NOTES.

DRAWING NOTES:

(ALL DRAWING NOTES ENCLOSED IN 'O')

1. PRIMARY POWER SUPPLY FROM BALTIMORE GAS AND

ELECTRIC COMPANY ("BGE" OR "UTILITY")

2. 480V, 3Ø, BGE STEPDOWN XFMR. XFMR TO BE SIZED AND

INSTALLED BY UTILITY. CONTRACTOR SHALL PROVIDE

CONCRETE PAD FOR BGE XFMR PLACEMENT.

COORDINATE WITH BGE FOR XFMR PAD REQUIREMENTS.

3. CONTRACTOR SHALL PROVIDE EMPTY CONDUIT FROM

XFMR TO CT CABINET FOR UTILITY-INSTALLED

CONDUCTORS. COORDINATE WITH BGE FOR

SECONDARY CONDUIT SIZE REQUIREMENTS.

4. 3#4/0 AWG AND 1#4 AWG GND IN 2" CONDUIT.

5. CONTRACTOR SHALL FURNISH AND INSTALL A UTILITY

APPROVED CT CABINET. CTs WITHIN THE CT CABINET

SHALL BE INSTALLED BY BGE.

6. 175kW GENERATOR. SEE OPTION 1 BELOW FOR

ADDITIONAL INFORMATION.

7. 300A ATS. SEE OPTION 1 BELOW FOR ADDITIONAL

INFORMATION.

8. 300A MTS. SEE OPTION 2 BELOW FOR ADDITIONAL

INFORMATION.

9. CONNECTION POINT FOR 175kW PORTABLE GENERATOR.

SEE OPTION 2 BELOW FOR ADDITIONAL INFORMATION.

10. UTILITY INSTALLED METER.

11. REFER TO PANEL SCHEDULES FOR WIRE AND CONDUIT

SIZES.

12. EXISTING 150kW GENERATOR TO BE REUSED.

13. SEE TRANSFORMER FEEDER SCHEDULE BELOW FOR

WIRE SIZES.

14. 600A ATS. SEE OPTION 2 BELOW FOR ADDITIONAL

INFORMATION.

15. 2 SETS 4#400 kCMIL AND 1#3 AWG GND IN 4" CONDUIT.

16. 4#400 kCMIL AND 1#3 AWG GROUND IN 4" CONDUIT.

17. 2 SETS 4#350 kCMIL AND 1#4 AWG GND IN 3-1/2" CONDUIT.

18. IF OPTION 1 IS SELECTED PANEL MP2 SHALL BE

POWERED VIA PANEL DP2. SEE PANEL SCHEDULES FOR

ADDITIONAL INFORMATION.

19. 480V, 3-PHASE,4-WIRE SMART METER. METER SHALL BE

CONFIGURED AND INSTALLED AS INDICATED IN

SPECIFICATION 26 20 00.

OPTIONS

ONE OF THE FOLLOWING OPTIONS WILL BE SELECTED BY THE

CUSTOMER TO PROVIDE BACKUP POWER UNDER THE

CONTRACT. CONTRACTOR SHALL COORDINATE WITH THE

CUSTOMER THROUGH THE COR. CONTRACTOR IS SOLELY

RESPONSIBLE FOR MAKING THE NECESSARY CHANGES TO

PROVIDE A COMPLETE AND WORKING GENERATOR BACKUP

SYSTEM WHETHER OR NOT SHOWN ON THE PLANS.

OPTION 1 - PROVIDE PADMOUNTED 175kW, 480V, 3Ø, DIESEL, STANDBY GENERATOR WITH 300A ATS TO

PROVIDE BACKUP POWER TO THE ENTIRE FACILITY. (i.e., BOTH BUILDINGS)

OPTION 2 - PROVIDE BACKUP POWER TO PANEL MP2 ONLY

USING THE EXISTING 150KW, 120/208V, 3Ø DIESEL,

STANDBY GENERATOR AND A NEW 600A ATS. PROVIDE A

CONNECTION POINT FOR A PORTABLE, 175kW, 480V, 3Ø

DIESEL GENERATOR THAT WILL PROVIDE GENERATOR

POWER TO THE ENTIRE FACILITY. CONTRACTOR SHALL

ENSURE THAT THE 150kW GENERATOR THAT SUPPORTS

THE KENNEL BUILDING IS NOT RUNNING WHEN THE

PORTABLE GENERATOR IS HOOKED UP AND SUPPLYING

POWER TO THE ENTIRE FACILITY. ONLY ONE OF THE TWO

GENERATORS SHALL BE RUNNING WHEN EMERGENCY

POWER IS NEEDED.

100A 125A 30A350A

225A MCB

METER

CT

CABINET

N E

L

SPD SPD

MDP

225A, 480/277V, 3Ø, 4W

G

N E

L

SPD SPD

225A MCB

N E

L

SPD SPD

G

XFMR

T1

PANEL LP1

277/480V

100A MCB

XFMR

T2

SPD

OPTION 1 OPTION 2

7 8

PANEL DP1

120/208V

250A MCB

PANEL RP1

120/208V

100A MCB

PANEL TC1

120/208V

100A MCB

PANEL MP1

120/208V

100A MCB

PANEL RP1A

120/208V

100A MCB

SPD

PANEL DP2

120/208V

250A MCB

PANEL RP2

120/208V

225A MCB

PANEL LP2

120/208V

100A MCB

PANEL MP2

120/208V

350A MCB

4 164

METER 19

EP601

E L

E C

T R

I C

O W

I

I A

G R

A M

M W

D

M W

D Y

E C

M W

D

1 2 3 4 5

D R

A W

N

B

Y

D E

S I G

N

B

Y

S B

S I Z

E

F I L

E

N

A M

E

I S

S U

E

D

A T

E

C O

N T

R A

S O

L I C

I T

A T

I O

N

N

O

M

Y

C

O R

E

N G

I N

E E

R S

C K

D

B

Y

US Army Corps of

Engineers ® x

D

C

B

A

F I

M

B E

R

P L

A

L E

P L

T

E

A U

G U

Baltimore District

X X

X

B A

L T

I M

O R

E

D

I S

T R

I C

T

B A

L T

I M

O R

E

M

A R

Y L

A N

D

M I L

I T

A R

Y

D

E S

I G

N

B

R A

N C

H

E N

G I N

E E

R I N

G

D

I V

I S

I O

N

C A

N I N

E

T

R A

I N

I N

G

F

A C

I L I T

N

N E

L S

M A

R K

D E

S C

R I P

T I O

N D

A T

E A

P P

R

E

P

D

W G

L A

U R

R

Y L

A N

D

U S

G

Questions and Answers For Information Only

W912DR-17-B-0014

Oct 5, 2017

1 Due to the bid opening being extended to Oct 12, 2017 and the great amount of interest in this project, please let us know when the next site visit will be held.

The next site visit will be held on 9/19/17. The accompanying amendment will provide additional site visit information.

2 Due to the many questions received from other regarding the name registration to the government for the site visit as note to be on 8/26/16, please clarify when the next scheduled site visit will be held..

Please see response to RFI 1

3 Will Warner be able to bid this project if we missed a Mandatory meeting, I notice that there is a full set of drawings that will allow us to provide a complete and competitive bid. Also with Google Earth we will be able to see the layout of the building/land etc. If a second bid walk will be entertained, please advise.

Please see response to RFI 1

4 Ref: Spec: 2.19 (Interface the base wide fire alarm Network) Please provide information regarding the Fire panel. There is nothing to indicate what network is the Fire Panel. What Base Panel and Network is existing?

Bid as shown. See sheet FA-601 and drawing notes on ET102 and ET103. Refer to specification Section 28 31 76, paragraph 1.7 for existing supervising station control panel brand and model number.

5 Section 600 of the solicitation states that the project is restricted to Small Business, please advise if this solicitation is set aside or open completion.

This solicitation is being advertised as full & open competition

Is this job is tax exempt and will the government issue a tax exempt certificate for materials to be installed on this project?

No.

7 Can the self performance criteria relaxed from 20% to 10%? No

8 Section 3.4.1 requires SSHO, CQCM and additional personnel as per the matrix. It’s not clear if the superintendent can also act as SSHO. Also, can the matrix requirement be fulfilled by subcontractors Foremen if they satisfy the qualifications?

See Section 01 35 26 sub-paragraph 1.6.1.1.1. and Section 01 45 00.00 10 paragraph 3.4.3 "These individuals…..are directly employed by the prime contractor…."

9 Site demolition plans call for existing structures demolition, please provide architectural demo plans or as-built drawings of these buildings.

Documents identify existing buildings for total demolition. Existing plans do not exist and architectural demo plans are not relevant when nothing is remaining other than items specified for salvage.

10 On spec SECTION 06 10 12 CONSTRUCTION OF NEW BLEACHER PAVILION;

para 1.1 SCOPE REQUIREMENTS states “Provide new foundation, slab on grade, and, finish grading as designed, represented, and indicated on drawings” then it further states “design and construction shall be a performance based requirement specifically to provide a new pavilion mostly replicating the existing”. Since plans doesn’t provide information on existing pavilion to replicate nor drawings for the new pavilion; please provide existing pavilion as-builts, sketches of new pavilion as a basis for contractor design, and required dimensions of the new pavilion.

Yes, SECTION 06 10 12, paragraph 1.1 states that both design and construction shall be a performance based requirement specifically to provide a new pavilion mostly replicating the existing one. There is no requirement for an exact replication of existing pavilion canopy. Minimum design requirements for new pavilion are in the section as necessary to achieve “mostly replicating” existing pavilion. Design criteria define columns, hip roof, materials, fascia height, etc. Site design, slab on grade, foundation, piers, size of slab and finish grading is represented on Drawings. Drawings of existing pavilion are not required.

11 Is this job a re-bid? No

12 There is a discrepancy concerning the existing contours between the grading plan sheet CG101 and both the demo plan and erosion and sediment control plans labeled CD101 and GC101-103 respectively. Which of the plans should be used to determine the existing contours? In addition, if the grading plan is to be used for its existing contours, will an updated plan for GC102 be provided to show a tie in for the proposed trap 1 into the existing contours as shown on CG101, the grading plan?

There was an anomaly with the existing surface tin at the time of plotting the bid set; however, after a review, the anomaly did not show up on any of the sheets we looked at. The existing surface on all of the sheets appears to match.

13 Are there any specific specs pertaining to the Security/Access Control systems? Is there an existing Security/Access Control system being used onsite currently? If not, is there a particular manufacturer being requested for this new security/access control work? Or do they just want a system that will meet what the drawings indicate?

1. No.

2. Yes.

3. See reply to No. 2 above.

4. Bid as shown.

14 Please verify that there are to be (2) Cat6 (RG-45) data drops per furniture and classroom desk/cubical. This is common practice.

Bid as shown.

# Question Answer

W912DR-17-B-0014

Oct 5, 2017

# Question Answer

15 There is (1) “AV” symbol in classroom 124. What is the purpose of this location (what cables/equipment are needed here)?

Bid as shown.

16 Please verify that the speakers in the classrooms 122/124 and associated cabling is the responsibility of the customer. EC is to rough-in conduit only?

Bid as shown.

17 Are the desks in classrooms 122/124 to receive data drop outlets? If so, how many per desk?

Bid as shown. The drops that are along the wall will be used for laptop connections at that the desks.

18 Drawing ESD101, note 4 states that existing fiber/copper from Hazen entrance security building to be pulled back to Handhole HH-3 and re-routed to Comms Room 115. Are these existing cables long enough to reach the Comms Room 115? Are these cables in good condition (re-usable)?

Bid as shown.

19 For the above question #6, what kind and what quantities are these existing fiber/copper cables that are being re-routed?

See Amendment 6

20 Drawing EST101 notes 2 and 4 state to run fiber and copper backbone cable in “separate innerducts” in PVC pipe. Who is responsible for providing and installing this “innerduct” (Electrical Contractor or Telecom/Low-Voltage Contractor? What size is this innerduct supposed to be?

1. Coordinate innerduct installation requirements with General Contractor.

2. Bid as shown.

21 Will a generator/transfer switch/rollup generator connection point sec section be provided?

See Amendment 5

Is the existing generator to be relocated per option #2 in area noted (#15) on drawing ES101?

Yes, note 15 on sheet ES101 applies to both generator options.

Where is the rollup generator connection to be located per option #2?

The Generator connection point should be located on the project north exterior wall centered between the electrical room and Comms room doors.

Will a pole base detail be provided? Exterior lighting is to be furnished and installed by B.G.E.

Lighting control panel is listed in spec but location is not identified on drawings?

The location for the lighting control panel shall be in Elec room 114.

Please provide a LEED scorecard. See Amendment 6.

Is enhanced Cx required? If so, the Cx agent cannot be a first tier subcontractor and the Cx agent needed to have been involved during the design process.

The Contractor shall provide commissioning in accordance with specification SECTION 01 91 00.15

TOTAL BUILDING COMMISSIONING.

Drawing EL201 is missing from the drawings. Will this drawing be provided? Please advise.

Sheet EL201 was incorrectly bookmarked . Sheet EL201 is in the advertised set. Scroll down 1 sheet below EL103 to view.

No lighting schedule is attached with the drawings. Will this schedule be provided?

Sheet EL201, which has the Lighting Schedule, is in the advertised set. Scroll down 1 sheet below EL103 to view.

Is MC Cable allowed to be installed at all on this project? Will MC Cable be allowed in concealed walls or concealed ceiling for branching?

MC Cable is Prohibited for concealed locations, except as allowed below.

Allowed for branch circuits only in the following dry locations:

• New construction and renovations in exposed locations. No MC cable is prohibited for concealed locations.

Is this project tax exempt? No.

Spec Section 084JJ3-2.J — Aluminum-Framed Entrances & Storefront

— A. Spec calls for an ”Impact Resistant” system. Details #3/AE607 show the glass plane to the front of the frame. The four major manufacturers only offer impact resistant ”center glazed” profiles. Is the Center glazed system acceptable? Please advise. B. The sill detail indicates extension legs at the bottom extending to the pre-cast. There is no profile available as shown. Would a brake metal closure be acceptable at the sill?

Please advise.

Placement of glazing within frame (outside, centered, interior) is not stated as a requirement in documents.

Bid as shown.

Spec Section 085113 — Aluminum Windows — A. This section calls for a narrow profile fixed pre- glazed window assembly. Which windows on the project are to be this system? Please advise. B.

IF this section is required, are they subject to the ”impact resistant“ rating as well? Please advise.

Narrow profile is not referenced or identified in specification or drawings. Bid as shown.

W912DR-17-B-0014

Oct 5, 2017

# Question Answer

Sill details #S1 thru S7/AE606 — A. No profiles with leg extensions are available as shown. These aluminum framings systems need to be dead loaded and anchored at the sills. Some type of load bearing solid construction is required at all sills. Please provide revised details for proper support of these aluminum system.

Details are representative, and not based on any particular manufacture, specifically identifying requirements coordinating differing trades. Details are standard masonry opening in cavity wall assembly.

Masonry is clearly located at jambs, which is where windows get attached to structure. Method of attachment, using clips, angles, or plats is in Section 08 51 13 Paragraph 3.1, and 3.1.3. Frame profiles to be as specified. Bid as shown.

please confirm whether the existing contours shown on the grading plan are correct and if they are why they are different from the existing contours as shown on the erosion and sediment control plans.

See answer to RFI 12.

there are three details for the concrete sidewalk shown:

Specification Division 3, 3.7.2 that says there is a minimum of 4" of concrete; sheet B-501 detail calling for 6" of concrete and 6" of RDM Base course; sheet CS501 site detail calling for 6" of concrete and 6" of porous fill. Which of these details to be followed?

The concrete details provided on sheet B-501 and B-503 pertain to the drivable concrete pavement in the corridor between the buildings. The Detail on Sheet CS-501 pertains to all sidewalk.

will the contractor have the site fully available to work on or will there be dogs and their training equipment in use concomitantly?

Yes. The contractor will have the site fully available. There will be no user occupancy during construction.

what are the available hours of operation under which the contractor will be allowed to access the site for the job?

Further, will Saturday work be allowed?

See 01 14 00 Work Restrictions.

will the training yard remained fenced off, and will it actively be used during construction?

No. The fence around the training yard does not have to remain enclosed. The training yard will not be occupied by the user during construction.

Section 10 22 39, Heading 1.2.2.2 requires an NRC Rating of 0.65-0.75 and specifies perforated steel panel faces in order to achieve this standard. However, the holes in the panel faces reduce the effective STC to less than 48, as is also required in this paragraph, and would preclude any possibility of passing the Acoustical Sound Test referenced at heading 3.3.2.

Therefore, the question is which of these criterion—perforated panels or the required STC Rating--can be adjusted and/or deleted.

See Amendment.

The non-secure nature of the application The costs required to meet the NIC required rating and The expense of engaging an independent testing agency Can the acoustical sound test referenced in 3.3.2 be deleted?

See Amendment.

Heading 2.2.5 calls out marker boards for the folding panels but these are not shown on the drawings. Please advise as to the quantity and location of these items.

Marker boards are integrated as part of panel surface along length of both sides. Bid as shown.

Heading 2.3.1 mentions Doors. Is this a reference to the storage closet doors which will conceal the panels when retracted, or passage door(s?) to allow an individual to go from Room 122-124 without going into the hall? If passage doors are required, please provide the location and quantity.

Folding panel partitions do not specify or indicate passage doors through partition. Bid as shown.

it is suggested that a manually operated partition be considered for this project, given that electric wall require two people to operate; one to man the switches mounted on opposite sides of the room, while one person acting on his own, can normally set up or retract a manually-operated partition in the time it takes to find a second operator. Further, and in a worst case scenario, an electric partition is rendered inoperable if there is only one person in the building

Bid as shown.

Per 1.7.1-Dust Control: Is there a close fire hydrant available that can be used to provide dust misting during the demolition work? If so, is there any metering or cost associated with its use?

One of the first construction activities will be to install the new water line on the west side of the project. The Contractor must install a new fire hydrant on the north side of this line. This hydrant can be used after it is installed. Spec 01 50 00 Paragraph 3.3.1 states that: "(Contractor) must install and maintain all necessary supply lines... On site utilities, if available, will be provided at no cost to the Contractor." Coordinate with the Contracting Officer whether a meter is required.

W912DR-17-B-0014

Oct 5, 2017

# Question Answer

Per Part 3 3.1- Existing Facilities to be Removed: Can the demolition materials be recycled at a LEEDS Approved Recycling Facility, instead of the onsite salvage/recycling of lumber, millwork items, carpet, ceiling tiles, locksets, mechanical hardware, fixtures, etc. prior to the gross demolition ?

Requirements for waste management, salvage, and demolition of construction and demolition waste control are as specified. Actual method, at site or off site is contractor’s means and method.

Plan page P-402 shows a mixing valve at the water heater in the Mechanical Room. There was not a spec for this in the specification. Can you please provide a spec and the GPM’s required so we can get this sized correctly?

Provide Thermostatic Mixing Valves as Specified in Section 22 00 00 para 2.4.4.

The floor sinks that are located in the Kennels do not show trap primers and or any vent piping. These drains are connected to the sanitary system and will require that these drains be vented, and that they either have a trap primer or a deep seal trap. Please advise on how you would like us to proceed with each of these items.

Per 22 00 00, para 2.7.1 - Drains shall be equipped with a barrier-type floor drain trap seal protection device conforming to ASSE 1072 and shall be used in conjunction with code-approved trap. This is a combination waste and vent system. This term refers to a system of waste piping in which the horizontal wet venting of the floor drains is accomplished by means of a common waste and vent pipe that is oversized to provide free movement of air above the waste flow line of the drain. See Section 915 of the

IPC.

Will this project require hair traps for the kennel floor sinks and the dog wash?

Hair traps will not be provided for the kennel drains.

See specification 11 31 13 for Canine Grooming Tub requirements.

Who is providing the door hardware?

All wire in conduit?

is this a standalone or an extension to an existing enterprise system?

Vendor preference for access software/hardware?

Are we providing wire and consulting on junction boxes/conduit needed?

How many users and how many cardholders will there be?

Card type needed?

Badging station needed?

How many Workstations required?

Remote access for users? Who will provide?

Will the integrator be provided remote access for troubleshooting/programming?

Response and requirements for each question is provided within Contract Documents. Door hardware Provide per Section 08 71 00, and as scheduled. All wire in conduit & empty conduit required. Quantity of workstations as indicated on Interior design drawings.

Bid as shown.

All wire in conduit?

Are we providing wire?

Out of the 16 cameras, how many thermal?

Vendor preference on cameras?

Video management system preference?

Is this a standalone or an extension to an existing enterprise system?

Video retention required in days, and resolution and frame rate required?

Continuous, motion based or continuous with motion tagging recording required?

Assuming all IP technology?

Are the access and video required to be integrated?

How many workstations required if separate from access control?

Any analytics needed?

Remote access for users? If yes who will provide?

Will the integrator be provided remote access for troubleshooting/programming?

Rack mounted server or tower? Are we to provide the rack?

UPS needed? If so how many hours of power are required?

Provide conduit only camera and security system. Bid as shown.

Who will provide network switches and are we utilizing POE?

Server and workstations provided by integrator?

Provide conduit only for camera and security system.

Bid as shown.

Drawing EL201 is missing from the drawings. Will this drawing be provided? Please advise.

See response to RFI #28

No lighting schedule is attached with the drawings. Will this schedule be provided?

See response to RFI #29

W912DR-17-B-0014

Oct 5, 2017

# Question Answer

Is MC Cable allowed to be installed at all on this project? Will MC Cable be allowed in concealed walls or concealed ceiling for branching?

MC Cable is Prohibited for concealed locations, except as allowed below.

Allowed for branch circuits only in the following dry locations:

• New construction and renovations in exposed locations. No MC cable is prohibited for concealed locations.

Is this project tax exempt? No.

Where is RTU-6 located on this project? The unit is not shown on the drawings. Please advise if a footage allowance should be given to power the unit.

The location of this equipment is shown on the mechanical roof plan.

Is this project to be one lump sum or broken out per building? See Bid Schedule

Is this project to be one lump sum or broken out per building? See Bid Schedule

Is the use of ENT in the slab permitted for branch wire? ENT use is prohibited.

Can nonmetallic sheathed cable be used? (3.1.10 & 3.1.11 found in spec book)

Nonmetallic-Sheathed Cable is prohibited for this building.

Just want to clarify on main service, on EP601 it shows it being a 225AMP service is that correct?

225A, 480/277V

On EL102 note 4 states to refer to sheet EL201 for additional light fixture information, but that sheet is not included in drawings.

See response to RFI #28

Please provide the name of the control company that has the current contract for this facility.

Bid as shown.

Can AISC Certified fabrication Plant be waived (Spec. 051200 item 1.3)?

Yes. However, provide evidence of having at least 3 years of experience similar in size and complexity.

Can AISC Certified Erector be waived (Spec. 051200 item 1.3)? Yes. However, provide evidence of having at least 3 years of experience similar in size and complexity.

Does the SSPC Paint 20 or SSPC Paint 29 (zinc rich primer - Spec. 051200 item 2.6.2) apply to the Administration building structural steel?

If yes, can we submit an alternate deduct to supply our standard red alkyd shop primer instead?

It is universal to the project. A gray alkyd shop primer is acceptable in lieu of SSPC Paint 20/29.

Coordinate with Architectural final finishes.

Does the SSPC Paint 20 or SSPC Paint 29 (zinc rich primer - Spec. 051200 item 2.6.2) apply to the Kennel building structural steel? If yes, can we submit an alternate deduct to supply our standard red alkyd shop primer instead ?

It is universal to the project. A gray alkyd shop primer is acceptable in lieu of SSPC Paint 20/29.

Coordinate with Architectural final finishes.

Does the SSPC SP6 (Commercial Blast Cleaning - Spec. 051200 item 2.6.2.1) apply to the Administration building structural steel?

If yes, can we submit an alternate deduct to used SSPC – SP3 (Power Tool Cleaning) instead?

It is universal to the project. An alternative deduct, SSPC - SP3 is acceptable.

Please provide a generator specification for the 175KW generator.

See Amendment

Please provide an ATS specification for the automatic transfer switch.

See Amendment

On drawing EP601 the under option 2 the transfer switch for the roll up generator is labeled ATS however under option notes it is depicted to furnish a manual transfer switch for the entire facility to be used with a portable generator. Please clarify the type of transfer switch.

Note 8 on drawing EP601 states that the transfer switch for the roll up generator is a manual transfer switch.

Please clarify the KW size of the portable generator. The size of the portable generator would be the same as the new generator in option 1 175kw.

Please clarify the size of the transfer switch to be used with the portable generator.

300A

Amendment 5 stated new drawings with 9-12-17 issue date, but when I open it shows issue date as August 2017. Was this a typo or are there new drawings issued on 9-12?

Issue Blocks contain the date 9/14/17. See Amendment 6 for changes GC102 and GC103. Also change to Issue Block for GC101.

76 Is Standalone intrusion detection system required? Provide conduit only system. Bid as shown.

Specs 271000, 2.4.5.1 and 2.5.2, Fiber Optics Hardware: Panels required are Duplex LC and Connectors/Modules are SC. SC Connectors will not fit on LC Panels, please specify.

See amendment.

In Open Office Area 110: How Many Cat6 Cables are needed per Cubicle at Junction Box?

See sheet ET102, note 1. Bid as shown.

How Many Strands of Fiber and Copper Pairs are existing that need to be pulled from the Hazen Entrance Security Building to HH-3 and re-pulled to Comm Room 115?

See amendment.

W912DR-17-B-0014

Oct 5, 2017

# Question Answer

What Type of Rack (Wall, floor) is needed for Elec Room 404A in Kennel Building to house Data Cables? And How Many?

No racks are required in Rm 404A. Bid as shown.

Subject E&S Requirements; Ref: Dwg. GC101, 102 & 103

It is respectfully noted the drawings state: The MDE Inspector has the right to amend or add E&S Requirements at any time during the project. The Contractor will comply with the MDE Inspector’s requirements at no additional cost to the Government. It is understood factors may arise and need to be addressed in the field which will differ from the design drawings; however, since this is not a design-build bid, please advise how the Government wishes for the contractor to account for this. Is there an allowance which should be utilized for this within contractor proposals – in order to allow contractors an equal opportunity for this ambiguous statement?

This is a standard MDE note. The Contractor will be responsible for upkeep and control of disturbance activities around the site. Bid as shown.

Chain Link Fence; Ref: Dwg. CS101, Note #16

It is respectfully noted the drawings state: Regarding the chain link fence. Removal all barb wire and top arms, and replace with top caps per spec. Inspect any existing fence to remain. Any defect found in the fence (such as, but not limited to: Posts, Cables, Wire Mesh, Gates, and Post Foundations) must be repaired to the satisfaction of the COR at no additional cost to the Government.

Since this is not a design-build bid, please advise how the Government wishes for the contractor to account for this matter.

Is there an allowance which should be utilized for this within contractor proposals – in order to allow contractors an equal opportunity for the ambiguity of this statement?

See CS101 in Amendment 6

Relocated Equipment; Ref: Dwg. CD101, Note #19

It is respectfully noted the drawings state: …The contractor must get prior approval from the COR if a piece of Training Yard Equipment must be moved. Training Yard Equipment can be stored within the Training Yard, but must be protected from damage. The contractor will be responsible for moving all equipment back to their original location….

Please identify all equipment that will need to be relocated and then moved back to their original locations.

Existing Training Yard Equipment is scheduled to remain. Specific pieces will be relocated outside Limits Of Disturbance (LOD), but not all. Contract includes Existing Training Yard Equipment to remain.

Therefore, answer specifically depends on contractor’s means and method, if a piece of Training Yard Equipment must be moved……. Refer also to Section 02 40 20 Paragraph 3.7 e.

Street Signage; Ref: Dwg. CU101, General Note #6

It is respectfully noted the drawings state: The contractor shall repair all pavements in accordance with the detail shown on Sheet B501. The contractor shall coordinate with the COR for any required street signs due to utility trenching.

The contractor is responsible for temporary traffic control per Section 01 50 00, para 2.2. Anticipate what controls will be needed and bid as shown.

Justification and approval of proprietary item custom kennel

Gates & equipment to Mason Company for $158,384.50. Can

You provide us a copy of this proposal from Mason Company

And enable us to verify the scope of work included in their proposal?

Bidder to contact Mason Company on all details pertaining to proprietary equipment defined in the J&A.

Specification section 089200 – Sun Shades - Can you provide a list of acceptable

Manufacturer’s?

Government contracts are non-proprietary, meaning that products are performance based. There is not a particular fabricator, which is why sunshades are assembled with standard off shelf parts and pieces.

Assemblies are submitted for approval against indicate criteria.

Can AISC Certified Erector be waived Yes. However, provide evidence of having at least 3 years of experience similar in size and complexity.

W912DR-17-B-0014

Oct 5, 2017

# Question Answer

Does the SSPC Paint 20 or SSPC Paint 29 apply to the Administration building structural steel?

If yes, can we submit an alternate deduct to supply our standard red alkyd shop primer instead?

It is universal to the project. A gray alkyd shop primer is acceptable in lieu of SSPC Paint 20/29.

Coordinate with Architectural final finishes.

Does the SSPC Paint 20 or SSPC Paint 29apply to the Kennel building structural steel?

a) If yes, can we submit an alternate deduct to supply our standard red alkyd shop primer instead?

It is universal to the project. A gray alkyd shop primer is acceptable in lieu of SSPC Paint 20/29.

Coordinate with Architectural final finishes.

Can AISC Certified fabrication Plant be waived ? Yes. However, provide evidence of having at least 3 years of experience similar in size and complexity.

Does the SSPC SP6 apply to the Administration building structural steel?

If yes, can we submit an alternate deduct to used SSPC – SP3 (Power Tool Cleaning) instead? If yes, can we submit an alternate deduct to used SSPC – SP3 (Power Tool Cleaning) instead?

It is universal to the project. An alternative deduct, SSPC - SP3 is acceptable.

Does the SSPC SP6 apply to the Kennel building structural steel?

If yes, can we submit an alternate deduct to used SSPC – SP3 (Power Tool Cleaning) instead?

It is universal to the project. An alternative deduct, SSPC - SP3 is acceptable.

Please provide a generator specification for the 175KW generator.

See Amendment 5

Please provide an ATS specification for the automatic transfer switch

See Amendment 5

On drawing EP601 the under option 2 the transfer switch for the roll up generator is labeled ATS however under option notes it is depicted to furnish a manual transfer switch for the entire facility to be used with a portable generator. Please clarify the type of transfer switch

Note 8 on drawing EP601 states that the transfer switch for the roll up generator is a manual transfer switch.

Please clarify the KW size of the portable generator. The size of the portable generator would be the same as the new generator in option 1 175kw.

Please clarify the size of the transfer switch to be used with the portable generator.

300A

Fiber Optics Hardware Panels required are Duplex LC and Connector/Modules are SC. SC Connectors will not fit on LC Panels, please clarify and specify.

See amendment

How many CAT6 cables are needed per cubicle in the junction box

See sheet ET102, note 6. Bid as shown.

How many Strands of Fiber and Copper pairs are existing that need to be pulled from Hazen Entrance security Building to HH-3 and re-pulled to Comm room 115?

See Amendment

What type of rack (wall, floor) is needed for elec.room 404A in Kennel Building to house data cables? And how many?

No racks are required in Rm 404A. Bid as shown.

Where does the Sidewalk Detail on CS501 apply? It conflicts with the details on B-503 which state that reinforcement within the sidewalk is reserved for those labeled with (R).

See answer to RFI 36.

Due to the simple nature of the steel required for this project, would the Corp entertain deleting the requirement to have the fabricator and erector certified?

See response to RFI 65 and 66.

Specs 271000, 2.4.5.1 and 2.5.2, Fiber Optics Hardware: Panels required are Duplex LC and Connectors/Modules are SC. SC Connectors will not fit on LC Panels, please specify.

See response to RFI 77.

In Open Office Area 110: How Many Cat6 Cables are needed per Cubicle at Junction Box? See response to RFI 99.

What type of Rack (Wall, floor) is needed for Elec Room 404A in Kennel Building to house Data Cables? And How Many? See response to RFI 101.

Could not find prevailing wage rates in the Specifications.

Please issue. See solicitation.

Spec Section 11 31 13 EQUIPMENT lists many items that are marked as (Option) next to the product name. Drawing Q-601 has a Note #2 which says “Provide Scheduled Option Item Per Bid Schedule, Refer to Bid Schedule”. There are 5 different pieces of Equipment marked as Note 2 in the BID SCH column. There are no Options on the PRICE SCHEDULE (Section 00010 Solicitation Contract Form). Please clarify if we are to include or exclude the items listed as “Option” in the specifications.

See CLIN 0007 on the Bid Schedule.

W912DR-17-B-0014

Oct 5, 2017

# Question Answer

SECTION 06 10 12 calls for the CONSTRUCTION OF NEW BLEACHER PAVILION, with a 2’ overhang. There is a small rectangle labeled BLEACHER PAVILION on dwg CS101, but no dimensions are given. Can you tell us the dimensions of the new Conc Slab-on-Grade, and the overall dimensions of the roof?

See Amendment 6

We hereby request that the bid due time be changed from 10AM until 2PM. It has been our experience that early morning bids result in fewer quotes and less subcontractor and supplier See Amendment 6

Please confirm if dehumidification for RTU-2,3,4&5 is required?

The way the leaving air temperature of these units is currently scheduled, there doesn’t appear to be any dehumidification for these DOAS units. The capacities suggest that the air is being cooled from 91F directly to 74F without hitting dew point and being reheated. Please confirm if the units are to be cooled to lower than 74F and then reheated for dehumidification purposes or if they are simply supposed to be cooled from 91F to 74F with no reheat.

Bid as shown. Provide RTU-2, 3, 4, and 5 with the airflow and minimum cooling capacity indicated on the schedule on M-601. Refer to M-806 and M-807 for control schematic, sequence of operation, and points lists.

JJRTC K9 Technical Amendment 10.5.2017.pdf
NARRATIVE
LEED PROJECT CHECKLIST
SHEET CG101
SHEET CS101
SHEET CS501
SHEET GC102
SHEET GC103
SHEET GC505
SHEET ES101
SHEET ESD101
SHEET EP601
QUESTIONS and ANSWERS DATED 10/5/2017