A.01.38_SOW_3_Culvert_Repair_Revised_Final_8-21-2018.pdf

PDF 7 MB Posted

Attached to
New Amendment for Repair-Replace Culverts Fort A. P. Hill, VA - W9123618B0027 Federal contract opportunity
Solicitation number
W9123618B0027
Issued by
Department of the Army Corps of Engineers Engineering District Norfolk

About this file

Scope of Work including Plans and Specifications

View the file

Other files for this federal contract opportunity

Other files attached to New Amendment for Repair-Replace Culverts Fort A. P. Hill, VA - W9123618B0027, newest first.
File Type Posted
B.01.02_-_Bid_Abstract_-_Culverts.pdf PDF
3_Culvert_-_Amendment_6_-_Release.pdf PDF
3_culvert_Amendment_5.pdf PDF
A.07.24_Amendment_0004_W9123618B0027.pdf PDF
A.01.25_Site_Visit_Sign-in_Sheet_Culverts.pdf PDF
A.07.24_Amendment_0002_W9123618B0027.pdf PDF
A.07.23_Corrected_Bid_Schedule_for_FBO_W9123618B0027.pdf PDF
A.07.24_Amendment_0001_W9123618B0027.pdf PDF
18-B-0027.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

http://www.nao.usace.army.mil

REPAIR-REPLACE CULVERTS - FT AP HILL 21-AUG-2018

REPAIR - REPLACE CULVERTS

No.1032, No.1211 & No.1486 Fort A.P. Hill, Virginia

STATEMENT OF WORK

Project Number: 400 http://www.nao.usace.army.mil http://www.nao.usace.army.mil/ http://www.nao.usace.army.mil/

Statement of Work Contents

Chapter:

1- PROJECT OBJECTIVES

2- (NOT USED)

3- SITE PLANNING

4- SITE ENGINEERING

5- PROJECT SPECIFIC REQUIREMENTS

Appendix A: Applicable Criteria

Attachment Contents:

Attachment 2 SITE PHOTOS Attachment 3 INSTALLATION AREA MAP Attachment 4 VICINITY MAP & HAUL ROUTE Attachment 5 PLANS & DETAILS & NOTES Attachment 6 CULVERT PIPELINE INSPECTION REPORTS Attachment 7 REAL PROPERTY ASSESSMENT REPORT Attachment 8 JOINT PERMIT APPLICATION Attachment 9 NATION WIDE PERMIT Attachment 10 ARMY RADIATION AUTHORIZATION Attachment 11 VA DEQ PLAN SUBMITTERS CHECKLIST Attachment 12 VIRGINIA RESPONSIBLE LAND DISTURBER CERTIFICATE

Attachment

Attachment

01 11 00

1A

1B

FORT A.P. HILL INSTALLATION ACCESS REGULATION

SPECIFICATIONS:

01 14 00 01 30 00 01 32 01.00 10 01 33 00 01 35 26 01 45 00.00 10 01 45 00.15 10 01 50 00 01 57 19 01 58 00 01 78 00

SUMMARY OF WORK

WORK RESTRICTIONS

ADMINISTRATIVE REQUIREMENTS

PROJECT SCHEDULE

SUBMITTAL PROCEDURES

GOVERNMENT SAFETY REQUIREMENTS

QUALITY CONTROL

RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)

TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS

TEMPORARY ENVIRONMENTAL CONTROLS

PROJECT IDENTIFICATION

CLOSEOUT SUBMITTALS

SOW-2

CHAPTER 1

PROJECT OBJECTIVES

1-1 PROJECT OBJECTIVES

The project objective is to procure a construction contract to remove, replace and rehabilitate existing drainage structures at three separate locations within the South Post area of Fort A.P.

Hill. Work will require the removal of two 36-inch existing corrugated metal pipe culverts and the (in-place) rehabilitation of a 54-inch diameter concrete pipe culvert. The existing culverts consist of corrugated metal and concrete pipe conduits (36- inch diameters) and a 54-inch concrete pipe conduit. Visual and CCTV inspections of the storm drain culverts has reflected that the physical condition and the useful service lives’ of the metal culverts have been expended. See Attachment No. 6 of this statement of work for CCTV results and conduit condition assessments of culverts to be replaced or upgraded by this project. Perforation of the metal pipe and the erosion of the pipe invert due to corrosion are plainly visible. Misalignment of pipe, joint separation, loss of circular roundness and bulging of pipe walls are evident. The 36-inch concrete pipe segment has longitudinal cracking at the crown of the pipe and severe joint misalignment. The existing metal culverts have been deemed to be inadequate to continue to safely pass storm water discharges thru heavily used paved roadways (Custer Trail and North Range Road) and an un-named gravel surfaced roadway within the controlled access training range area near Lower Delos Lake area of Fort A.P. Hill. The upstream concrete wing wall and drainage apron along with the downstream end of the pipe culvert beneath North Range Road (approximately 1350 ft. east of entrance drive to Range 18) has collapsed into a severely eroded deep ravine created by the erosive storm water which has resulted in the washout of the roadway embankment toe. Surface runoff from Custer Trail has resulted in the moderate scattered erosion of the downstream roadway embankment in the immediate areas surrounding the culvert installation area. These roadways are critical to the Fort A.P. Hill’s training mission and also serve as quick access for emergency and firefighting equipment, vehicles and personnel to the various range training areas.

All new culverts shall be of durable non-corroding/non-rusting long lasting materials (min. 75 year anticipated) service life material is required for this project. The interiors of the new drainage culverts and relined concrete culvert shall be smooth wall finish. The spiral wound steel reinforced pipeline liner shall be of a polyethylene (PE) resin based material similar in grade to HDPE new sewer and drainage pipe. Joints for new replacement culverts thru the roadway embankments shall soil tight with welded couplers that provide extreme joint tightness for the life of the project.

In addition to removing existing damaged culverts and installing new steel reinforced ribbed polyethylene and/or new concrete pipe culverts, improvements will be made to reduce the outlet-discharge channel flow invert and discharge channel bank erosion at each installation by installing erosion control stone rip rap in the discharge channel a hardened discharge apron consisting of Class I rip-rap stone. [This will not be a requirement for Culvert No. 1486 rehabilitation.] Where culverts are removed and new culverts are installed the roadway embankment will be reconstructed with suitable, approved fill materials placed and compacted per drawing details and specifications. Reconstructed roadway embankment slopes shall be topped with rich approved topsoil and seeded with FAPH approved seed mixture, fertilized, irrigated and maintained until accepted by the Government. The sections of improved (paved) roadways that had been removed to facilitate the removal of existing culverts and replacement

SOW-3

with new culverts shall be repaved. The stone surfaced roadway crossing the Pneumansend Creek near the Lower Delos Lake shall be graded and topped with gravel stone per details shown on the drawings.

Culvert location markers shall be installed near the termination points of each culvert location that are highly visible and sufficiently high to protrude above growth and brush that may vegetate the roadway embankments and occasional accumulated snowfall or snow drifts.

The culverts to be removed, replaced or relined with a steel reinforced spiral wound liner are listed on the Fort A. P. Hill inventory of drainage structures as follows:

• No. 1032 EXIST 36’’ CMP [REPLACE W/ 36”SRPE PIPE]

• No. 1211* EXIST 36” CMP [REPLACE W/ 36”SRPE PIPE]

• No. 1486 EXIST 54” CONC PIPE [RELINE w/LINER]

*(existing culvert No. 1211 is of composite construction with corrugated steel pipe at both ends and a 98 lineal ft. concrete pipe center section)

Culverts No. 1032 and No. 1211 shall have existing concrete upstream concrete wing- wall and end-wall replaced with new upstream and downstream inlet and outlet structures under this contract. Approach and discharge channels for the new culverts shall be shaped, graded and lined with erosion control stone that will prevent roadway embankment toe and channel invert and slope erosion.

Upon excavating the roadway embankments necessary to remove failed and failing culverts and the reconstruction of the roadway embankments it will be necessary to reconstruct the shoulders of the roadways such that the concentration of storm water is controlled and discharged or dissipated without eroding the embankment slopes. The natural drainage channels shall be lined with erosion control stone to prevent scour and erosion damage at the storm water discharge points. The replacement storm water culvert piping shall have at least a 75-year service life expectancy with routinely scheduled periodic phased inspections, timely recordation of pipe condition and evaluation, maintenance, and repair cycles when deemed necessary by recommendations from the recurring periodic culvert and storm drainage system inspection evaluations and reports prepared by FAPH Environmental and DPW offices.

Culvert No.1486 shall be rehabilitated in place. The CCTV evaluation and the interior of the concrete pipe is such that it is an excellent candidate for in-line relining with a size on size reinforced high density polyethylene (HDPE) product that is specifically manufactured for use in extending the service lives of existing drainage piping. The relining of the 54-inch reinforced concrete culvert will provide many additional years to the expected service life of this culvert.

The roadway pavement replacement section shall be based upon the daily use of roadway by government, contractor, commercial, private, military and Army training vehicles (pneumatic wheeled) to access various training ranges. It is anticipated that roadways will be used (small percentage) by Army MRAP type of vehicles, both with two and three axle variants with the three axle variant having gross vehicle weights up to 79,240 pounds. The replacement paved roadway sections that are to be installed after roadway embankment material is place and compacted per specifications shall be adequate for HL-93 wheel loading traffic.

The proposed work shall be divided into three separate stand-alone work items and shall be priced individually. The three work areas for culvert replacement and relining have been designated as Base Bid Item, Option Item No. 1 and Option Item No. 2 and Contract Line Items (CLIN's).

Base Bid Item

Option Item No. 1

Option Item No. 2

Culvert 1032

Culvert 1211

Culvert 1486

Culverts No’s. 1032 and 1211 require full replacement. Culvert No.1486 shall be rehabilitated by the insertion of a steel reinforced HDPE plastic pipe liner spirally wound into a circular pipe from within the base of the existing concrete intake chamber. This work shall be accomplished with live flows within the existing host pipe.

CLIN 1

CLIN 2

CLIN 3

SOW-4

Requirements stated and shown on the drawings in this statement of work are minimums. The contractor is encouraged to evaluate project requirement and recommend innovative, creative, and cost effective construction solutions which meet or exceed these requirements. The Contractor is encouraged to develop and utilize solutions that will expedite construction and shorten the construction schedule and restore the roadways to a fully operational status.

1-2 SCOPE. Project objective requirements and construction services shall comply with the, specifications, drawings, sketches, details and requirements contained in this Statement of Work (SOW). The technical criteria contained and cited in this SOW establish minimum standards for construction quality. The objective of this solicitation is to facilitate permanent repairs to critical components of storm drainage system and conduits beneath North Range Road, un-named roadway crossing Pneumansend Creek and Custer Trail that was temporarily repaired in an expedient manner following severe storm events spawned by remnants of subtropical storm that resulted in historical rainfall precipitation in short time durations. Objective is also to procure a permanently finished an operationally ready to use repaired and restored storm drainage system The project location is located on Government-owned land at Fort A.P. Hill, Virginia.

Utilizing information herein this contract shall consist of the preparation and execution of his work plans for the replacement and upgrade of old and damaged drainage system located near the U.S. Route 301 overpass of Wilcox Drive and Custer Trail, the failed culvert beneath North Range Road and the relining of interior existing 54-inch concrete culvert thru embankment adjacent to Lower Delos Pond. (See Attachment No. 4 for project locations).

Incidental work includes (but is not limited to) installation of traffic control devices and signage for re-routing or by-pass of daily traffic, temporary removal of roadway guard rails, temporary support of buried communication lines, installation of sediment and erosion control features, the clearing and careful removal of accumulated felled trees, limbs and forest litter) deposited in existing natural drainage swales, placement of erosion control stone, installation of storm water control and discharge features (drop inlet, paved ditches/swales/ flumes, spill outs, end walls, energy dissipaters,(as required) soil(earthen) embankment stabilization matting, embankment retention systems, temporary support for exposed fiber optic and communication lines, etc.

1-2.1 Special Utilities and Supplementary Construction. All utilities shall be carefully located, protected and temporarily supported where and when required during work efforts within the project limits. Two known fiber optic lines and one copper line are buried in South shoulder of the North Range Road roadway. Same utilities may be located in the shoulder areas of Custer Trail. Contractor to coordinate his proposed work and excavation with utility suppliers prior to any subsurface excavation activities.

1-2.2 Demolition Considerations and Requirements. Demolition and removal of existing materials and metal culvert piping shall be performed as necessary to properly install new storm water culvert piping and storm drainage appurtenances. Contractor shall remove accumulated forest debris and clean out downstream channel areas where Culvert No. 1211 has collapsed into the Custer Trail roadway embankment wash out area. Demolition shall include but not be limited to: removal of trees and vegetation, soil, SOW-5 pavements, sloughed and eroded embankment materials, sediment deposits, felled trees from power line right of way clearing (in natural drainage channels) and buried underground utilities.

Demolition materials shall be disposed of off Government property. Utility appurtenances and utility piping (drainage structures and failed culverts) shall not be abandoned in place, but shall be removed from project site in entirety. Recyclable materials such as metal culvert pipe and demolition concrete shall be disposed of at a commercial recycle facility by the contractor.

Contractor shall provide weight tickets from recycle facility that indicate weight of metal and concrete delivered to the facility. The weight tickets shall be provided to the COR. Removal of damaged pavements shall be complete where required including surface and base course layers. Trees to be removed shall have stumps and roots grubbed and removed completely.

Open voids shall be backfilled with suitable approved fill material, compacted and covered with topsoil to match proposed grades. Materials disposed of off Government property shall be recycled whenever possible. The Contractor shall obtain demolition and disposal permits from appropriate agencies.

1-3 APPLICABLE CRITERIA. Applicable standards and construction criteria references are listed in Appendix A to the Statement of Work. Criteria shall be taken from the most current references as of the date of issue of this document. Referenced codes and standards are minimum acceptable criteria. Administrative, contractual, and procedural features of the contract shall be as described in other sections of this document.

1-4 CONSTRUCTION QUALITY. The main objectives of this solicitation are to replace existing failed drainage structures and culverts at various locations within Fort A.P. Hill with a quality drainage system and pavement. And to restore involved roadways to a fully operational status as quickly as possible. All work shall be done in accordance with requirements of criteria documents listed in Attachments and Appendix A of this document.

SOW-6

CHAPTER 3

SITE PLANNING

3-1 SCOPE OF WORK. Site features and failed/deficient culvert locations are fixed. New culverts shall replace existing culverts at Range Road and Custer Trail. Culvert beneath roadway embankment crossing Pneumansend Creek shall be relined. Road embankments that are disrupted by the removal of existing culverts and placement of new culverts shall be reconstructed and restored to support Army vehicle and commercial vehicle roadway traffic.

Restored roadway shoulders shall be graded such that sheet flow is directed to a central collection point then directed via a spillouts, paved flumes and energy dissipaters. Due to the sensitive nature of the watershed the footprint (of the repaired and reconstructed roadway embankments) shall not exceed the limits of existing roadway embankment (prior to loss of embankments at culvert outfall discharge points). New culverts shall be fitted with end walls, wing walls at channelized storm water discharge points. Project work area for proposed road repairs and culvert replacement are shown in Attachments No. 2 and No. 5. Reconstruction of damaged (wash outs) roadway embankments will be required The eroded wash out areas shall be prepared and re-graded by the placement and compaction of suitable fill materials to restore existing approximate grades. The reconstructed eroded areas will also support the new culvert piping and end wall structures and outlet drainage aprons. Existing natural drainage swales in the vicinity of the roadway embankment shall be cleaned and cleared of excessive sediment, trees, brush, forest litter and other vegetation that inhibit the safe(and non-erosive) discharge of storm water. In instances where the existing drainage channels have irregular/undulating grades due to deep scour erosion the eroded areas shall be filled with suitable material and compacted to establish a flattened uniformly sloping grade, the re-graded channel shall be protected by the placement of erosion control stone covering the channel bottom and side slopes.

3-2 SITE VERIFICATION. Graphic and narrative descriptions of site opportunities and constraints have been provided in this Statement of Work document.

3-3 EXISTING CONDITIONS. Sketches of the damaged roadway embankment and culvert areas from field notes supplemented with existing Fort A.P. Hill resources and master plans of surrounding areas are included in this statement of work package. It should be noted that the sketches and features are approximate. Contractor shall provide equipment, materials and labor necessary to by-pass upstream storm water flows thru the project site (in a manner consistent with Commonwealth of Virginia Erosion and Sediment Control requirements) during existing culvert removal and new culvert replacement and restoration of roadway embankment.

3-4 EXCAVATION PERMITS. The Contractor shall notify "Miss Utility" and/or FAPH DPW before excavating or digging. A digging permit [FAPH (DPW) Form 20A, DPW Excavation Permit] shall be obtained from FAPH DPW prior to excavation. See copy of permit in Attachment 1A. Project work site is known to have buried communication lines within work limits. Contractor shall also notify local cable companies of his scheduled roadway embankment excavation and reconstruction. See Attachment 4, Drawing c-500, Note No. 4 for contact information

SOW-7

3-5 SITE ROAD REPAIR AND CULVERT REPLACEMENT PLAN. The contractor shall provide a complete work plan showing the various project sites and full extent of impacted areas. The site varies from open to wooded. Large specimen trees within work limits should be considered for retention.

Contractor's culvert replacement plan shall incorporate the trench excavation requirements covering sheeting and shoring as stipulated in the most recent issue of EM 385-1-1, SAFETY AND HEALTH REQUIREMENTS, published by the Department of the Army.

3-5.1 Drainage. The complete work plan shall include all storm water collection, conveyance and disposal piping/appurtenances and storm water management system design to be used during reconstruction of excavated or damaged roadway embankment and replacement of existing culverts and drainage structures.

3-6 GENERAL SITE DESIGN &CONSTRUCTION CRITERIA. The following are to be used as guidance for site construction. Criteria: Virginia Erosion and Sediment Control Handbook, Virginia Department of Transportation Specifications (latest issued edition), Virginia Department of Transportation Roads and Bridge Standards (latest edition), Virginia storm water management laws and regulations. Analyze the existing site conditions and incorporate features from references into the contactor’s work plans for each culvert replacement and culvert relining rehabilitation work areas.

3-7 TURF (EXPOSED GROUND COVER) ESTABLISHMENT PLAN. Turf establishment on disturbed and bare earth areas shall be in accordance with locally acceptable practices. The contractor shall establish a vegetative ground cover in the most expedient manner upon placing and shaping roadway embankments and culvert approach and discharge channels. No bare earth shall be left exposed without sufficient barren soil stabilization matting or other cover in place to prevent soil erosion. Planting or seeding shall occur only during periods when beneficial results can be obtained. The Contractor shall adhere to all protocols and requirements specified in the FAPH Seeding SOP in re-establishing an enduring permanent vegetative ground cover on all disturbed and new reconstructed embankment areas.

3-7.1 Turf. Turf consists of seed. Seed mixture for temporary and permanent ground cover shall comply with Virginia Erosion and Sediment Control Handbook by the FAPH Seeding SOP

3-7.1.1 Seed. State approved seed of the latest season's crop shall be provided in the original sealed packages bearing the producer's guaranteed analysis for percentages of mixture, purity, germination, hard seed, weed seed content, and inert material. Labels shall be in conformance with applicable State seed laws. Seed mixtures shall be proportioned by weight. Weed seed shall not exceed one percent by weight of the total mixture.

3-7.1.2 Temporary Turf Cover. When there are contract delays in the turfing operation or a quick cover is required to prevent erosion, the areas designated for turf shall be seeded with a temporary seed. When no other turfing materials have been applied, the quantity of one-half of the required soil amendments shall be applied and the area tilled.

SOW-8

3-7.1.3 Final Turf. The turf shall be installed during appropriate planting times and conditions recommended by the trade for the type and variety of turf specified. The turf operations shall be performed only during periods when beneficial results can be obtained. Drainage patterns shall be maintained. The turf shall be installed by using the methods as recommended by the trade for the type and variety of turf specified. Immediately after turfing, the area shall be protected against traffic or other use by erecting barricades and providing signage as required. The turf establishment period for establishing a healthy stand of turf shall begin on the first day of work under the turfing contract and shall end three months after the last day of the turfing operation. An unsatisfactory stand of turf shall be repaired as soon as turfing conditions permit.

3-7.2. Satisfactory Stand of Turf.

3-7.2.1 Seeded Roadway Embankment Areas. A satisfactory stand of turf from the seeding operation for a lawn area is defined as a minimum of 15 grass plants per square foot. Bare spots shall be no larger than 6 inches square. The total bare spots shall not exceed two (2) percent of the total seeded area.

3-7.2.2 Seeded Field Area. A satisfactory stand of turf from the seeding operation for a field area is defined as a minimum of 10 grass plants per square foot. The total bare spots shall not exceed two (2) percent of the total seeded area.

3.7.2.3 Maintenance during Establishment Period. The maintenance of the turfed areas shall include eradicating weeds, eradicating insects and diseases, protecting embankments and ditches from erosion, maintaining erosion control materials and mulch, protecting turf areas from traffic, mowing, watering, post-fertilization and replacing unsatisfactory turf areas.

Application of pesticides and insecticides for the control of insects and diseases shall be accomplished by a certified applicator.

SOW-9

CHAPTER 4

SITE ENGINEERING

4-1 SOILS.

4-1.1 Geotechnical Engineering: The Contractor shall retain a geotechnical engineer registered in the Commonwealth of Virginia to provide construction services that will included evaluation of the subgrade, suitability of fill material, and other earthwork related quality control services. It will be up to the contractor to evaluate the site, determine the pipe bedding, and verify the pavement design.

4-1.2 Soil Preparation and Compaction.

4-1.2.1 The Contractor and his or her professional geotechnical engineer consultant are responsible for determining the depth of stripping and/or over excavation necessary to provide a suitable subgrade. Contractor shall assume that 100cy of material will be unsuitable and require over excavation, disposal and replacement at each culvert location.

4-1.2.2 The near surface soils at this site primarily consist of moderately to highly plastic clays.

These existing soils are susceptible to moisture changes, and are subject to loss of strength and will become unstable for construction equipment during wet weather. Drying and reworking of these soils are likely to be difficult during wetter months. The Contractor shall expect construction activities to be curtailed during and after wet periods. Natural subgrade soils will require drying by aerating and disking to be able to compact and to develop a suitable subgrade for areas to receive compacted-controlled fill, pavement sections and slab on grades, etc. Over-excavating softened subgrade soils and replacing them with suitable granular fill can be considered if unfavorable weather conditions prevent the proper drying and compaction. However, this shall be performed at no additional cost to the Government. Any over-excavation due to the action of the Contractor, or done to expedite the Contractor’s construction, time, will be at no additional cost to the Government. Surface soils that are to be turfed shall be aerated by disking and augmented with additional organics and soil amendments to facilitate increased infiltration of storm water.

4-1.2.3 Soil compaction shall be achieved by equipment approved by the professional geotechnical engineer consultant. Fill or backfill materials shall be placed in maximum 6-inch compacted thickness lifts, and shall be moistened or aerated as necessary to provide the moisture content that will readily facilitate obtaining the compaction specified with the equipment used. Compact subgrade materials and each layer of fill beneath structures and pavement subbase to not less than 90 and 95 percent, and general grading materials to not less than 85 and 90 percent, of ASTM D-1557 maximum laboratory density for cohesive and cohesionless soils respectively. Cohesionless materials are defined as containing less than 40 percent by weight fine-grained material; all other materials shall be considered to be cohesive. Contractor shall fillout and submit form required Attachment No. 10 Army Radiation Authorization (ARA) Fort A.P. Hill in the event the nuclear densometer testing is the method of choice for soil compaction testing.

4-1.2.4 T h e following minimum testing requirements for subgrade, fill, backfill, and aggregate base materials shall be incorporated into the specifications:

SOW-10

a) A minimum of one moisture density test (ASTM D1557) shall be performed for each on-site or borrow soil material proposed for fill, backfill, and base course.

b) One Atterberg Limits test (ASTM D 4318) and one gradation analysis (ASTM D

422) shall be performed for every ten field density tests.

c) A minimum of one sand cone field density test (ASTM D 1556) is required for every 10 nuclear gauge field density (ASTM D 6938) tests. Results by ASTM D 1556 shall govern, and results by ASTM D 6938 shall be adjusted (calibrated) accordingly.

d) Field Density tests (ASTM D 1556 or ASTM D 6938) shall be performed on compacted subgrade and on each layer of fill/backfill/base at minimum frequencies of:

i) One test per 100 feet of utility trench.

ii) One test per 2000 square feet of paved area and building area, and per

4000 square feet for all other areas.

4-1.2.5 Fill placed under roadways shall be compacted structural fill. Controlled structural fill material for roadways should be non-expansive and free of organic matter, debris, and particles larger than 2-inches in size. Proposed fill materials should be subjected to laboratory tests consisting of, but not necessarily limited to, moisture density determinations, Atterberg limits, and sieve analysis. Areas to receive fill which are sloped surfaces, steeper than one foot vertical and four feet horizontal (1V to 4H) shall be plowed, stepped and benched so that the fill material will bond with the existing materials. Steps or benches shall be 1 foot vertical to 2 feet horizontal (1V to 2H). Structural Fill should classify per USCS as CH, CL, SC, SW, SP, SP-SM, or SM with a maximum of 65 percent fines passing the No. 200 sieve and have maximum liquid limit of 65 and a plasticity index of greater than 15.

4-1.2.6 Permanent slopes shall be no steeper than one foot vertical to one and one half feet horizontal (1V to 1.5H). Consideration shall be given to flatten slopes where mowing is required. Pipes shall be bedded in natural material or on properly compacted suitable fill as required above, except that it is limited to cohesive material. A granular bedding material under pipes shall not be used, except as noted. Due to the difficulties in obtaining proper compaction around anti-seep collars, anti-seep collars shall not be used. Therefore, the last 1/3 portion of the downstream pipe shall be wrapped with a one foot thick VDOT 57 crushed stone with a non-woven geotextile fabric around the perimeter of the stone.

4-1.2.7 These requirements shall be verified by the Contractor's professional geotechnical engineer in the report wherever engineering, existing or proposed soils, or climatic factors indicate the necessity. These requirements shall also be verified to be consistent with the specified design. Any modification to the stated compaction or pavement requirements shall be supported by engineering analysis and shall require the approval of the Contracting Officer.

SOW-11

4-2 EROSION AND SEDIMENT CONTROL. Erosion and Sediment Control Facilities shall be required in accordance with Virginia Erosion and Sediment Control Handbook latest edition.

Additional controls shall be implemented as required by local conditions on site. Erosion and Sediment Control Plans shall be submitted to the Government for review and approval. The Contractor shall prepare erosion and sediment control plans that are aligned with his work plan in removing and replacing failed culverts. Contractor shall prepare separate individual erosion and sediment control plan for each work location.

4-3 PLAN SUBMITTERS CHECKLIST. The contractor shall prepare and submit the Virginia Department of Environmental Quality “PLAN SUBMITTER’S CHECKLIST” for the required maintenance replacement of failed non-functional culverts cited in the project. Land disturbance for this maintenance replacement of failed culvert and the relining of the Delos Road culvert is minimal and limited to the areas where the existing roadway embankments are to be excavated to remove the existing storm culvert pipe. There is no land disturbance anticipated at the Delos Road culvert relining since access to the culvert will be thru the intake structure.

4-4 CLEARING AND GRUBBING. Clear and grub all trees and vegetation necessary for construction; but save as many trees as possible. All timber removed from the project site shall become the property of the Contractor, unless otherwise indicated or specified. Trees to remain shall be protected from damage.

NOTE: Tree removal between 15 April and 15 September is not allowed because of Federal Protected (endangered species) Act.

4-5 EARTHWORK. The Contractor is responsible for obtaining subsurface soil information for design compliance and construction purposes.

4-6 BORROW MATERIAL. Obtain borrow material required for construction from sources not supplied by the Government.

4-7 STORM DRAINAGE SYSTEMS AND GRADING.

4-7.1 Storm Culverts and Drainage Structures. Upon the careful removal of failed or failing storm drain culverts beneath roadways and preparation of the bedding for the new culverts, the storm culverts shall be placed and installed in accordance with the requirements of the Commonwealth of Virginia (VDOT) Drainage Manual and Road and Bridge Standards and Specifications (latest edition). The contractor shall maintain the existing slopes and grades in the new replacement drainage structure and culverts. The contractor shall establish the invert elevations prior to commencing any demolition activity. The contractor shall prepare an accurate existing condition profile taken along the approximate centerline of the existing culverts. Profile should indicate roadway embankment, guard rail, endwalls, wingwalls, and approach and discharge channels. This information shall be provided to the COR prior to commencing demolition/construction

4-7.2 Drainage of Roads and Pavements. Provide a positive crown on roadway new pavement patch. Contractor shall match exiting North Range Road and Custer Trail Road cross slope grades for new patched roadway pavement at road repair areas.

4-7.3 Materials. All materials (culvert piping, pipe joints, end walls, flumes, paved ditches, spill outs, energy dissipaters, erosion control stone, geotechnical fabric, guard rail and post, shall be in accordance with VDOT Roads and Bridge Standards and Specifications (most

SOW-12

recent edition). Contractor to use only the allowable pipe materials based upon local conditions and Fort A.P. Hill criteria. Pipe for culverts and storm drains may consist of reinforced concrete, Class IV or V installed upon a bedding Class B or a ribbed steel reinforced polyethylene pipe (with smooth interior) bedded and installed in strict accordance with pipe manufacturers recommendations. Joints of culvert pipe shall be high quality having the ability to withstand test hydrostatic pressures up to 15 psi with no leakage. Ribbed steel reinforce polyethylene pipe shall have capability to maintain roundness (circular shape) within established manufacturer’s tolerance limits when subjected to a superimposed loading exerted by a soil backfill heights up to 50 feet (dependent on actual embankment and roadway design section fill height). Contractor to obtain approval from COR and Post Engineer on type of pipe to be used prior to order and purchase of pipe.

Corrugated steel metal pipe culverts shall not be used for this project.

4-7.4 Field Quality Control for Storm Drainage System. Testing procedures and requirements shall comply with the Virginia Department of Transportation (VDOT) drainage manual.

4-8 PAVEMENT CRITERIA. Pavement for road patching required for removal of roadway embankments for culvert replacement shall be in accordance with Virginia Department of Transportation (VDOT) design requirements and/or U.S. Army Corps of Engineers design requirements. The pavement design shall be able to support an estimated average daily traffic of 5,000 vehicles per day with 20% trucks (HL-93 wheel loading) for a design life of 20 years. See Drawing C-500 for intended pavement design. Confirm subgrade meets design requirements.

4-9 PERMIT REQUIREMENTS. Operating permits and licenses shall be the responsibility of the Contractor. Timely acquisition of all the necessary permits shall be the responsibility of the Contractor. The Contractor, upon notice to proceed, shall immediately begin working on obtaining the permits so as not to delay completion of the project. The following permits have been identified as potentially being required for this project: Erosion and Sediment Control, Excavation Permit, Demolition Permit, and Disposal Permits.

This project is considered as a routine maintenance drainage structure replacement and rehabilitation project. The footprint of the replacement culverts should not exceed the footprint of the existing defective culverts (prior to the collapse of the outlet structures and outlet ends of culvert pipe into the eroded drainage channels.

The Contractor shall submit a complete Army Corp of Engineers Joint Permit Application (JPA) to the Virginia Marine Resources Commission (VMRC) for all three (3) project sites. VMRC will distribute the JPA to ACOE-Regulatory and VA-DEQ for review and approval.

For Culvert Replacement No. 1032 and Culvert No. 1211 work Pre-Construction Notification to ACOE-Regulatory Branch is required under Nationwide Permit No.3. These culverts shall be countersunk in accordance with Nationwide Permit No.3.

See JPA (Attachment No. 8) to this package and ensure the government provided drawings, specifications and reports meet the minimum requirements of the JPA. See Attachment No.9 for Nationwide Permit No.3.

4-10 LAND DISTURBER CERTI.FICATE.

The contractor shall provide a current Commonwealth of Virginia Responsible Land Disturber certificate for equipment operators. A sample copy of this certificate is provided in Attachment No. 12 of this solicitation.

SOW-13

CHAPTER 5

Project Specific Requirements

5-1 PLANNING & CONSTRUCTION GOALS.

5-1.1 Site Planning Objectives. Primary planning & construction objective is to rapidly complete and obtain required approvals to engage in construction activities at Ft. A.P. Hill.

Preparation and completion of the contractors proposed work activity plans for the three areas are required and needed for the replacement of failed or failing drainage piping and structures beneath North Range Road, Custer Trail and the upgrade of the concrete pipe culvert beneath the road crossing Pneumansend Creek near Lower Delos Pond. Reconstruction of eroded toes of roadway fill embankment at the downstream outfall end of culverts will be required to support new culvert pipelines and endwall-wingwall outlet structures to the downstream discharge channels. Existing drop inlet structure shall be replaced with new permanent structure with fixed concrete drainage apron and grate. Existing downstream outlet discharge channels shall be lined with rip-rap stone to prevent channel bank and invert erosion.

Contractor to coordinate partial or full closures of North Range Road and Custer Trail with Fort A.P. HILL post engineers office and facility security office. Culverts 1032 and 1211 cannot be replaced simultaneously. Culvert 1486 may be rehabilitated simultaneously with Culvert 1032 or with Culvert 1211 replacement.

5-1.2 See drawings in Attachment 5 for additional (supplemental) detailed listing of project and statement of work requirements necessary to execute this project.

5-2 APPLICABLE CODES AND STANDARDS. Except as specified otherwise in the Statement of Work, planning and construction execution of this Repair- Replace Culverts project the project shall comply with the latest editions (as of the date of this document) of the criteria listed in Appendix A. Unless noted otherwise the materials specifications used by the contractor shall comply with Virginia Department of Transportation (VDOT) criteria listed in Appendix A.

5-3 SPECIAL WORK AREA ACCESS REQUIREMENT. All work required at the Culvert No. 1486 location must coordinated (by the contractor) and approved by Officer in Charge at Range Control. Culvert No. 1486 is located within the controlled range access area of Fort A.P. Hill that that is extensively used for military training activities and exercises.

5-4 TABULATION OF AND HANDLING OF RECYCLABLE MATERIALS. Contractor shall keep an accurate record of recyclable demolition debris, metal culvert and concrete removed from the project sites and delivered to a commercial-licensed demolition debris recycler. The contractor shall provide the official scale tickets from the recycler to the COR.

The weight tickets shall detail the type of product recycled and the quantity (in pound) of the product recycled. The tickets shall be time and date stamped.

SOW-14

Appendix A: Applicable Criteria

A APPLICABLE CRITERIA

A.1 APPLICABLE INDUSTRY CRITERIA

Applicable engineering and construction criteria references are listed in below. Criteria shall be taken from the most current references as of the date of issue of the contract.

This list is not intended to include all criteria that may apply or to restrict design and construction to only those references listed.

AMERICAN ASSOCIATION OF STATE HIGHWAY AND

TRANSPORTATION OFFICIALS (AASHTO)

ROADSIDE DESIGN GUIDE (GUARDRAILS, ROADSIDE SAFETY DEVICES)

STANDARD SPECIFICATIONS FOR TRANSPORTATION MATERIALS AND

METHODS OF SAMPLING AND TESTING (ROAD CONSTRUCTION MATERIALS)

STANDARD SPECIFICATIONS FOR STRUCTURAL SUPPORTS FOR HIGHWAY

SIGNS

AMERICAN SOCIETY OF CIVIL ENGINEER (ASCE)

DESIGN AND CONSTRUCTION OF SANITARY AND STORM SEWERS, MANUALS

AND ENGINEERING PRACTICE – NO. 37 (SANITARY SEWER AND STORM

SEWER DESIGN CRITERIA)

A.2 STATE/LOCAL DESIGN STANDARDS, CRITERIA & REGULATION

1. VDOT ROAD AND BRIDGE SPECIFICATIONS (2007 EDITION)

2. VDOT VIRGINIA ROAD AND BRIDGE STANDARDS VOLUMES I & II (LATEST

EDITION)

3. VDOT DRAINAGE MANUAL, PREPARED BY THE HYDRAULICS SECTION

VDOT (LATEST EDITION)

4. VDOT PAVEMENT DESIGN GUIDE FOR SUBDIVISION AND SECONDARY

ROADS IN VIRGINIA (2009 EDITION)

SOW-15

5. VIRGINIA DEPARTMENT OF CONSERVATION AND RECREATION DIVISION OF SOIL

AND WATER CONSERVATION

VIRGINIA EROSION AND SEDIMENT CONTROL HANDBOOK (LATEST EDITION).

6. COMMONWEALTH OF VIRGNIA, DEPARTMENT OF ENVIRONMENTAL QUALITY

• VIRGINIA DEQ REGULATIONS (MOST RECENT)

• VIRGINIA STORM WATER MANAGEMENT PROGRAM

• VIRGINIA EROSION AND SEDIMENT CONTROL LAW

• VIRGINIA EROSION AND SEDIMENT CONTROL REGULATIONS

A.3 APPLICABLE MILITARY CRITERIA

The project features shall (in lieu of state criteria) conform to the following criteria.

Certain design impacts and features due to these criteria are noted for Contractor information purposes.

PCASE PAVEMENT-TRANSPORTATION COMPUTER ASSISTED STRUCTURAL

ENGINEERING (program available on WEB at: www.pcase.com )

UNIFIED FACILITIES CRITERIA (UFC)

UFC 3-250-01 PAVEMENT DESIGN FOR ROADS, STREETS, WALKS AND

OPEN STORAGE AREAS

UNIFIED FACILITIES CRITERIA (UFC): available on the WEB at:

http://www.wbdg.org/ccb/browse_cat.php?o=29&c=4 http://www.pcase.com/ http://www.wbdg.org/ccb/browse_cat.php?o=29&c=4

FORT A.P. HILL MILITARY INSTALLATION

REGULATIONS & REQUIREMENTS

(PARTIAL)

ATTACHMENT 1

(PARTIAL)

FAPH Regulation 190-13

PHYSICAL SECURITY

INSTALLATION ACCESS REGULATION

Effective 3 March 2014

Unescorted Access Requirements 2-2. Acceptable Identity Source Documents (Non Federal/DOD Affiliated personnel) Non Federal Government or non DOD affiliated personnel requesting access (ESCORTED or UNESCORTED) must provide an approved identification credential or document listed in Table 2-2.

Table 2-2. Acceptable Identity Proofing Documents.

Non Federal Government or non DOD affiliated personnel

Driver’s license or identification card issued by a State or outlying possession of the United States, provided it contains a photograph and biographic information such as name, date of birth, gender, height, eye color, and address.

Identification card issued by Federal, State, or local government agencies, provided it contains a photograph and biographic information such as name, date of birth, gender, height, eye color, and address.

U.S. passport or U.S. passport card.

Transportation Worker Identification Credential (TWIC) Permanent resident card or Alien Registration Receipt Card (INS Form I-551).

Foreign passport with a temporary (I-551) stamp or temporary (I-551) printed notation on a machine readable immigrant visa.

In the case of a nonimmigrant alien authorized to work for a specific employer incident to status, a foreign passport with INS Form I-94 or INS Form I-94A bearing the same name as the passport and containing an endorsement of the alien’s nonimmigrant status, as long as the endorsement has not yet expired and the proposed employment is not in conflict with any restrictions or limitations identified on the form.

Employment authorization document that contains a photograph (INS Form I-766).

U.S. Military or draft record. DD FM 214 with matching ID U.S. Coast Guard Merchant Mariner Card Native American tribal document.

3-1. Proofing and Vetting Non-Federal Government and non-DoD affiliated persons who require unescorted access require identity proofing and vetting to determine fitness and eligibility for access.

Access decisions are the result of a Risk Management process intended to identify and mitigate threats to the installation. The below fitness criteria in Table 3-1 are guidelines and are applied generally rather than specifically to applicants criminal histories when determining risk. This unescorted access fitness criteria in Table 3.1 if revealed during an NCIC III check are generally grounds for denial of unescorted access.

Table 3-1 Unescorted Access Fitness Criteria

Administratively barred or excluded from any other DOD installation.

Any felony conviction of any type within 10 years, or a felony arrest that has not yet been adjudicated includes “Deferred Findings” and recent arrests or summonses that have not yet been adjudicated)

Any misdemeanor conviction within 5 years includes “Deferred Findings” and recent arrests or summonses that have not yet been adjudicated) Traffic violations are reviewed on a case by case basis and determined by the DES Police Chief

4-1 Unescorted Access Requirements The unescorted access procedures shown in this chapter apply to domestic visitors only. Chapter 8 covers Foreign National access and visits. This includes U.S.

citizens and resident aliens who have been issued a resident alien credential (commonly called a “green card”) or have an approved identification credential or document listed in Table 2-2.

All non Federal Government or non DOD affiliated personnel requiring unescorted access will meet three (3) requirements and have possession of an authorized access credential found in Table 2-1 and Table 2-2 in order to access the installation. The three (3) requirements are:

1. Purpose. All individuals will have a valid and legal government purpose for accessing the installation. Meeting the requirements of “government purpose” frequently includes oversight by government personnel to ensure that the validity of the purpose is maintained.

2. Vetting. All individuals will be evaluated (vetted) to ensure that their character and conduct are suitable for approval or denial of unescorted access. For individuals who require vetting prior to receiving unescorted access, vetting request procedures are outlined in Chapter 3 of this regulation.

3. Identity Proofing. All individuals will have their identity verified (identity proofed) by presenting authorized identification for inspection of authenticity.

c. All non Federal government or non DOD affiliated personnel age 18 and older requiring unescorted access will be meet all the requirements in Chapter 3.

4-2. Unescorted Access Request Procedures

a. FAPH is required to complete a review of each visitor’s criminal history prior to granting unescorted access, see Chapter 3. The minimum information required to request this review and unescorted access has been formatted into FAPH Form 21, Request for Unescorted Installation Access.

b. On government employees with an authorized credential found in Table 2-1 are allowed to send FAPH Form 21’s to the VCC. Completed requests that contain PII will be labeled as “FOR OFFICIAL USE ONLY” and will be afforded protection consistent with this level of sensitivity IAW DOD and Army regulations.

c. Sponsors of unescorted visitors will provide blank FAPH Form 21’s to their visitors or visiting organization and maintain oversight of the visit process until completion.

1. Submitting the Request.

a) The sponsor will receive the completed form from the visitors and review the form for errors and accuracy prior to submission to the VCC. The sponsor (or the requestor where direct submission of requests is authorized) will submit the request to the VCC by encrypted email to: usarmy.aphill.imcom-atlantic.mbx.installation-access@mail.mil or by fax at (804) 633-8444, or in person to the VCC.

b) The VCC will not accept incomplete or illegible FAPH Form 21’s or FAPH Form 577’s. The VCC will not accept unescorted access requests from Non Federal or Non DOD personnel who are not in possession of a credential in Table 2-1.

c) Federal and DOD authorized government employees must ensure all information is completed on the FAPH Form 21. When submitting requests, requesters must provide the authorized identification document or credential (see table 2-2) as this will be the access credential for those approved unescorted access.

d) Below is an example of the information the non affiliated DOD/Federal person(s) will have to submit and utilize each time they attempt to enter the installation. Should individuals be approved unescorted access and not have in their possession the approved and authorized Identifying Document (s), see table 2-2 they submitted on the FAPH Form 21, they will be denied installation access.

e) Example: VA Drivers License# A1234566, US Passport# ABCD1783464634, VA Identification Card# 12345678.

f) While completion time for requests is frequently shorter, requestors are advised that 10 business days is the standard for processing time.

g) The VCC shall not be responsible for incomplete processing of requests that were submitted less than ten business days prior to the event.

mailto:usarmy.aphill.imcom-atlantic.mbx.installation-access@mail.mil mailto:usarmy.aphill.imcom-atlantic.mbx.installation-access@mail.mil

h) Specific requests for faster processing may not be honored, based on the priority assigned to other operations, or may be available to visiting, transient or tenant units only on a reimbursable basis.

2. Processing the Request

a) For individuals with criminal histories revealed by the initial NCIC III review, the VCC will follow the guidance described in Chapter 3.

3. Approval of Unescorted Access.

a) In instances where no criminal record is revealed by the NCIC review, or where the severity of criminal histories can be adjudicated by time or other circumstances, the individual may be placed on the installation access roster and may be granted access with an expiration date no later than 1 year from the date of the completed NCIC review (except as authorized by this regulation or the Garrison Commander).

b) Individuals with recurring, open-ended access…