This document provides the salient characteristics for a SCBA refill station/compressor solicited by the Department of the Army National Guard. Key requirements for the refill station include a Bauer Unicus 4I or equal item with a minimum of 6000 psig pressure, CO monitoring system, NFPA 1901 2016 edition compliance, a 3 position containment fill station to accommodate SCBAs, a solid-state auto cascade system, tri fill/3 positions, Posi Check connection, NEMA 4 rated electrical enclosure, and an emergency stop push button with audible alarm on safety shutdowns. The related federal contract opportunity is solicitation number W50S73-23-Q-0007 for a SCBA refill station/compressor for the Gowen Field, ID Fire Department.

View the file

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Salient Characteristics 124TH CEF SCBA Refill Station/Compressor

(14 September 2023)

1. Bauer Unicus 4I or equal item

2. Minimum Specs Required

A. 6000 psig B. CO monitoring system C. NFPA 1901 2016 edition compliant 3 position containment fill station accommodates SCBA

D. Solid-state auto cascade system.

E. Tri Fill/3 positions

F. Posi Check Connection G. NEMA 4 rated electrical enclosure H. Emergency stop push button

I. Audible alarm on safety shutdowns