Pump_Specifications-Repair_Fire_Pump.pdf
PDF 4 MB Posted
- Attached to
- Repair Diesel Powered Fire Pump Federal contract opportunity
- Solicitation number
- W15QKN-19-Q-1265
About this file
Attached are the Fire Pump Specifications
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment_0001.docx | DOCX document | |
| 1265___SITE_VISIT_INFORMATION.docx | DOCX document | |
| Construction_Format_for_contractor's_proposals.xls | XLS spreadsheet | |
| W15QKN-19-Q-1265__Fire_Pump_Danville,_PA_(released).pdf | ||
| DRAFT_SOW__Danville,_PA176-Lewisburg_ARC.docx | DOCX document | |
| Pump_Specifications-Repair_Fire_Pump,_PA176-Lewisburg_ARC.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MDAVIS
D03-116667
GENERAL ARRANGEMENT
FOR
5x4 E4J11A-FPH w/ CLARKE JU4H-UF22
C096841
TS
6/7/2010
BYDATEECRREVZONE
H J K L M
V W X
D E F G N P R S T U
XWVUTSRPNMLKJHGFEDCBA
A B C
R
REV.
APPRVD.SCALE
DATEDRAWN
DWG. NO.
A SUBSIDIARY OF THE GORMAN-RUPP COMPANY
PATTERSON PUMP COMPANY
3 29878 10-26-10 MD
Estimated Weight: 22629 lbm
103.75 2635.3
132.00 3352.8
38.19 970.1
119.07 3024.3
111.00 2819.4
145.82 3703.7
198.75 5048.2
225.25 5721.3
242.20 6151.8
302.53 7684.3
336.00 8534.4
42.12 1069.7
168.00 4267.2
242.96 6171.1
285.83 7260.1
18.72 475.5
58.81 1493.8
78.67 1998.2
46.72 1186.7
5 7
12.22 310.4
21.79 553.5
29.67 753.6
94.85 2409.1
63.86 1622.2
30.72 780.3
44.05 1119.0
52.05 1322.2
27 25
A A
A
E
G
NOTES:
1: ANCHOR BOLT HOLES AVAILABLE ONLY UPON CUSTOMER REQUEST.
2: IF THERE IS A DRAIN OR ANY OTHER OBSTRUCTION
IN THE FLOOR THAT SHOULD BE CONSIDERED, PLEASE LOCATE
IT ON THIS DRAWING.
3: THIS SKID IS DESIGNED TO BE FILLED WITH CONCRETE AT
INSTALLATION. THE BASE PLATE (UNDER THE PUMP AND DRIVER)
IS TO BE GROUTED PER INSTRUCTIONS IN THE 0 & M MANUALS
SENT WITH THE UNIT, IF DECKPLATE IS USED OMIT NOTE #3.
4: DUE TO VARIATIONS IN THE PIPE FITTINGS, CUSTOMER PIPE
CONNECTION LOCATIONS MAY VARY +/- 1/2 ". IT IS RECOMMENDED
THAT PIPING NOT BE ANCHORED RIGIDLY UNTIL FINAL FIT-UP IS
COMPLETE.
5: TAMPER SWITCHES ARE PROVIDED ON ALL BUTTERFLY VALVES,
WIRING OF THESE SWITCHES WILL BE BY OTHERS.
6: IF APPLICABLE BUILDING HEATER, EMERGENCY LIGHT, LIGHTS, JOCKEY
PUMP CONTROL PANEL, JOCKEY PUMP, AND OTHER ITEMS THAT MAY'
BE DIMENSIONED IN PARENTHESIS ( ), ARE SHOWN IN THEIR GENERAL
REPECTIVE LOCATIONS AND MAY VARY SLIGHTLY FROM THE
LOCATION SHOWN ON THE DRAWING.
7: ELECTRICAL SERVICE TO BE LANDED BY OTHERS IN DISTRIBUTION PANEL
PROVIDED WITH BUILDING.
8: CASING RELIEF VALVE DISCHARGE DRAIN IS NOT PLUMBED UNLESS
SPECIFIED BY CUSTOMER.
9: THE LINE BELOW IS 12" LONG ON THE ORIGINAL DRAWING, USE THIS
LINE TO MAKE SCALING ADJUSTMENTS WHEN INQUIRING ON LENGTHS.
12.00 304.8
CEILING HEIGHT: 96.00"
270.53 6871.5
B B
SECTION B-B
265.00 6731.0
18.12 460.1
80.28 2039.0
G
G
G
52.00 1320.8
68.18 1731.82
F
134.96 3427.9
92.79 2357.0
C
C
MDAVIS
D03-116667
GENERAL ARRANGEMENT
FOR
5x4 E4J11A-FPH w/ CLARKE JU4H-UF22
C096841
TS
6/7/2010
BYDATEECRREVZONE
H J K L M
V W X
D E F G N P R S T U
XWVUTSRPNMLKJHGFEDCBA
A B C
R
REV.
APPRVD.SCALE
DATEDRAWN
DWG. NO.
A SUBSIDIARY OF THE GORMAN-RUPP COMPANY
PATTERSON PUMP COMPANY
3 29878 10-26-10 MD
SECTION A-A
44.05 1119.0
68.18 1731.8
52.05 1322.2
30.72 780.3
52.05 1322.2
63.86 1622.2
94.85 2409.1
B
C
D
E
Item# Qty Description Wt
1 1 PUMP E4J11A 223 lbm
2 1 Clarke JU4H Naturally Aspirated Models 958 lbm
3 1 BASE E4J11A-FP w/ CLARKE JU4H ENGINES 554 lbm
4 2 Motorized Louver / Damper 44" x 30" 67 lbm
5 3 Overhead Light 4' x 1' 175 lbm
6 2 Heater (Standard) 134 lbm
7 3 Sprinkler Head 0 lbm
8 2 Exhaust Fan 24" 114 lbm
9 1 Enclosed Waste Cone 4" x 6" 74 lbm
10 1 VLV RLF 4" ANG #2050B4KG 300#/150# 150 lbm
11 1 Emergency Light 3 lbm
12 1 Joslyn Pump Controller B7E2LN16-42E 527 lbm
13 1 Hammond Transformer 7.5 kVA 152 lbm
14 1 Main Distribution Panel 60" x 20" x 6" 80 lbm
15 1 JOSLYN CLARKE JOCKEY PUMP CONTROLLER 21 lbm
16 1 Exterior Light 12 lbm
17 1 Double Door 6ft (Trachte Building) 222 lbm
18 1 Muffler Residential 3" JRE-03 16 lbm
19 1 GVI Flowmeter 6" Grooved 16 lbm
20 1 GRUNDFOS CR1-9 100 lbm
21 1 SKID STRUCTURE BEAM W12@26#, 132"x336"LG 5619 lbm
22 1 Backflow Preventer 8" 774 DCDA w/ Gates 643 lbm
23 5 VLV GATE 6" FLG 150# 772 lbm
24 1 VLV GATE 6" FLG 150# W 1 1/4"NPT LOC B 154 lbm
Item# Qty Description Wt
25 2 Valve Rls Air 1/4" #FV-4M Watts 2 lbm
26 1 VLV GATE 6" FLG 150# W 1 1/2"NPT LOC A 154 lbm
27 1 VLV CHK 4" FLG SWG #F-908-W 150# 175 PSI NIBCO 104 lbm
28 1 VLV CHECK SWING 6" 175psi #F-908-W 176 lbm
29 1 Fire Department Conn. 4" 22 lbm
30 2 VLV BALL DRIP 1/2" 0 lbm
31 1 EXT SPILL BASIN FOR 120 GAL FUEL TANK 227 lbm
32 1 Fuel Tank 120 Gallon Single Wall W/ 42" Legs 620 lbm
33 1 Trachte Building 132" x 336" (96" Ceiling Height) 6619 lbm
34 1 HOSE VALVE HEADER 6" 150# FLUSH MOUNT 75 lbm
35 1 Battery Rack (Dual Batteries) 57 lbm
36 1 Beacon 143 lbm
Item# Description
A SUCTION FLANGE 8" 150#
B 1 1/4" JOCKEY PUMP CONNECTION SUCTION SIDE
C 1/2" SENSING LINE CONNECTION
D 1 1/4" JOCKEY PUMP CONNECTION DISCHARGE SIDE
E DISCHARGE FLANGE 6" 150#
F HOSE VALVE CONNECTION 6" 150#
G FIRE DEPT. CONNECTION 4"
20.74 526.8
SECTION C-C
52.05 1322.2
80.28 2039.0
ARMY RESERVE TRAINING CENTER 2112
KEYSTONE DIVERSIFIED COMPANIES LLC
E4J11A-FPH 750 173
UL/FM FP-C096841
-UF22 2600 75 120
JOSLYN MODEL-B7E2LN16-42E
TONY SPENCER 6/3/2010
kclardy Oval kclardy Oval kclardy Line kclardy Line kclardy Line kclardy Line kclardy Line kclardy Line
File details come from the government source that posted it.