STATEMENT OF WORK
PLACE OF PERFORMANCE:
USS Whidbey Island
JEGLC
Norfolk, VA
DESCRIPTION OF WORK:
Equipment: #6 AC unit
· Pumpers to remove up to 500 gallons of contaminated salt water from unit
· Remove condenser, chiller heads, and blank water lines.
· Pressure test system to identify source of leak.
· Submit a Report identifying the source of the leak.
· Plug up to three leaking condenser tubes, do not exceed 10% overall.
· Remove compressor to deck and open/inspect.
· Submit a Report of compressor findings.
· Move motor, scroll assembly to blank system, and prepare for flush.
· Accomplish approved hot water/cleanser flush of system including receiver. (PCP required).
· Install new compressor bearings, sleeves, and gasket set.
· Re-install compressor, scroll assembly and align motor and compressor.
· Pressure test to ensure system integrity (VG) Check Point.
· Accomplish dehydration/evacuation to ensure absence of moisture (VG) Check Point
· Charge compressor with oil and Ship Force Supplied Refrigerant (900 lbs. R-236fa).
· Op-test IAW Tech Manual. (VG) Check Point.
References:
S9514-D8-MMA-010
PMS MIP: 5140/013-70