This document includes a Statement of Work and related federal contract opportunity. The Statement of Work seeks two 275-kilowatt Cummins mobile generators with diesel engines rated for EPA Tier 4 emissions and able to operate at minimum temperatures of 122 degrees Fahrenheit. The generators must have auto, manual, start, stop, and fault reset controls that are UL compliant with PC-based diagnostic software. A 24-hour fuel tank and diesel exhaust fluid tank are required along with electric trailer brakes and a single point lift eye. A minimum three-year or 3,000-hour warranty is specified. The related federal contract opportunity with solicitation number FA442721Q0126 also seeks the two Cummins C275D2RE generators detailed in the Statement of Work. The generators must be self-contained units on attached trailers with 24-hour fuel capacity at 75% rating. The Cummins brand is specified with no equivalents accepted. The customer is the Air Force Civil Engineer Center located at Travis Air Force Base in California.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Combo - Generator.pdf | ||
| Brand Name Justification (Cummins)_Redacted.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Statement of Work (SOW)
275kW Cummins Mobile Generators, (2 each)
120 Days or less after Receipt of Order
Description: AFCEC/CEMIRT is tasked with responding to natural disasters with its mobile Electrical Power Plants. In order to do this multiple sized generators are needed. The Generators in this contract will be vital to ensuring backup mission capabilities for CEMIRT, NASA, USAF, USSF, etc.
The selected Contractor shall provide two (2) each of the C275D2RE, Diesel Genset, 50/60Hz, 275kW, Standby-Rental. CEMIRT requires these units to execute our disaster response capabilities, as well as a mobile generator fleet for any emergency power requirements from AF bases across CONUS. The generator needs to be a self-contained unit with attached trailer, to include fuel tank sizing for a minimum of 24 hour runtime at 75% rated. Full specification is provided below.
Shipping Address:
AFCEC/CEMIRT
730 E. Street Bldg 1205 Travis, AFB 94535
Specifications:
Mobile Generator Features/Specifications
Engine
- Diesel Engine
- US EPA Tier 4 Final Emissions rating
- Cooling system rated at a minimum 122 degree F operation
- Battery Disconnect Switch
Generator Controls
- Electronic Based Control System
- Must be UL compliant
- Must have Auto, Manual, Start, Stop, Fault Reset, and Lamp Test/Panel Test switches
- PC based service tool diagnostic software o Must include any and all level access passwords for full diagnostic testing o Must include any generator specific control cables for diagnostic testing
- Generator must have parallel ability to connect to similar generators
Alternator/Electrical Package
- Permanently mounted 4 position voltage selection switch
- Must have the following switchable 3 Phase voltages: 277/480, 139/240, 120/208 VAC
- Must have the following switchable 1 Phase voltage: 120/240 VAC
- 20 Amp GFCI receptacles
- 50 Amp 240V twist lock receptacle
- Shore power connection for coolant heater and battery charger
- Remote Start Capability
Fuel System
- 24-hour Fuel Tank
- 24 hour Diesel Exhaust Fluid (DEF) tank (if applicable)
- Auxiliary Fuel and Diesel Exhaust Fluid Connections
Trailer Specifications
- DOT approved trailer with electric trailer brakes
- 2-5/16” Ball Mount or Pintle Hook.
Miscellaneous
- Warranty- 3 years/3000hrs minimum
- Roof Mounted Single Point Lift Eye
Special Requirements: N/A
Qualifications/Certifications: N/A