Text version

Btu Input 1,000,000

Recovery GPH 70°F to 140°F CD 1652 (96% ET) f------ 64 - - ----<

Recovery GPH 40°F to 140°F 1175 (97.5% Er )

Storage Capacity - gallons

HOT OUTLET 2" NPT UF1\NC LUC ACCESS

Gas Pressure Maximum Static

Gas Pressure Minimum Flow

Amperage (120VAC, 60Hz.)

14" W.C.

3.S" W.C.

CONOENSA T[ CRAIN

I" BARS FITTI NG

Max. Inlet Air Duct Length @ 6" dia. 100 ft. with four 90° ells

Max. Vent Length @ 6" dia. <i.) 100 ft. with four 90' ells

Shipping Weight lbs. 1890 .

<D Per DOE, 10 CFR 431 (ANSI Z21 .10.3@ 70°F to 140"F) <Z> Listed for category IV venting through PVC, CPVC, polypropylene, or single-wall stainless steel vent

Refer to manual for design requ irements l onger vents available with larger diameter

V<NT CONNECTION 6j 0.0.

(REFER TO I.IAf'lUAL

F'OR VENT 512:NG)

Et.EC TRICAL S£R'J!CE CONNECTIOf\l

Cl

1 ~ GAS CONNECnON

TANK DRAlN VAL.Vt'. 1• NPT

FORKLIFT ACCESS

-------- 782 ------<

SIDE VIEW

C0~8US110N AIR

CONNECTION 6& 0.0.

(REf"ER TO MANUAL

FOR VENT SIZING)

"1:NT CONNECTION 6j 0 .0 .

(REFER TO ~ ANUAL

FOR \/ENT SIZING)

TOP VIEW

fRONT VIEW

BUILDING

RElVRN lj° NPT

PRESSURE

REL Er

VALVE

9UIL0ING

RETURN

lj" NPT

Recommended Service Clearance: 18" from all sides, 12" from the top. Consult factory for heat exchanger pull space requirements.