This statement of work outlines repairs needed for a cold room located at the US Horticultural Research Laboratory in Fort Pierce, Florida. The scope of work includes replacing the condensing unit and evaporator coil with new scroll-type and automatic control systems, adding a hot gas bypass and desuperheating circuits, replacing refrigerant lines and filters, rewiring electrical systems, reinsulating suction lines, and ensuring proper temperature operation. Site visits are scheduled for August 3, 2023, with requests to attend due by August 2. Related solicitation 12405B23Q0468 from the Department of Agriculture Agricultural Research Service seeks a contractor to complete these cold room repairs at the specified location by the specified dates.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Service Provisions 1106447.docx | DOCX document | |
| Wage Rates.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STATEMENT OF WORK
REPAIR COLD ROOM 1087
The US Department of Agriculture (USDA), Agricultural Research Service (ARS), US Horticultural Research Laboratory (USHRL) needs a single Contractor who can provide supplies, services, supervision, transportation, labor, work plan, schedule, and assure effective performance to repair cold room 1087 located at 2001 South Rock Road, Ft Pierce, FL 34945.
1. SCOPE OF WORK
The general statement of work shall serve as general information only and shall not limit the Contractor’s responsibility or obligations to conform to all local, state, and federal labor laws necessary to furnish and repair cold room 1087 as follows:
a. Modify to new scroll type condensing unit.
b. New evaporator unit.
c. Automatic control
d. Add hot gas bypass.
e. Desuperheating circuits.
f. New liquid line and suction filters
g. Flush old refrigerant and change refrigerant to R404A.
h. Reslope drain line.
i. Remove unused wiring and rewire with power whip new circuits. Use weathered type of flex conduit.
i. Re-plumb copper lines.
j. Reinsulate suction line.
j. Adjust and test cold room to proper temperature swing operation.
k. Crane operation to remove and deliver old compressor units.
l. Contractor responsible for the disposal of any excess equipment and materials.
2. Site visit information. A site visit has been scheduled for 08/03/2023 at 9:00 AM EST. Please provide the name of the personnel requesting to attend and the company with which they are associated to lynn.hults@usda.gov and vic.agahan@usda.gov by 08/02/2023 at 3:00 PM EST.
2. PHOTOS:
Cold Room 1087
Condemn Condensing Unit
Evaporator Coil image1.jpeg image2.jpeg image3.jpeg