United States Department of Agriculture Beltsville Agricultural Research Center Utility Management Unit Building 426A, Room 101 BARC-East 10300 Baltimore Avenue Beltsville, Maryland 20705-2305

STATEMENT OF WORK:

Emergency contracting services are needed to replace and repair all mechanical and electrical systems associated with Sewer Pump Station 1286.

Beltsville Agriculture Research Center Beltsville, Maryland

Background:

The Beltsville Agriculture Research Center (BARC) is the primary location of plant science research for the United States Department of Agriculture (USDA). The research, experiments and studies conducted within its building are critical to the ongoing mission of the USDA. The BARC campus sits on 7000 acers in Beltsville Maryland, because of the number of building, labs, and types of research associated with BARC, the center maintains two wastewater treatment plants and one water treatment plant. There are several sewage pump stations in various locations to ensure proper treatment process are followed. Sewage pump station 1286 is one such station, which is located on the BARC East campus. There are five (5) office and lab buildings that rely on the operations of pump station 1286 to process raw sewage.
In recent weeks, the area has had severe weather which is believed to have cause the sewage pump station 1286 to malfunction and fail completely. This station is one of many that is required by federal and state laws and regulation to function at all times even in the event of emergencies such as loss of power. All functions of pump station 1286 are offline. It appears the pump stations systems have been electrically shorted causing both pumps to fail. The electrical control panel needs replacing, the emergency backup system (Generator and ATS) have failed and need replacing, the alarm system has failed, and the float system has also failed.

Scope of Work:

The contractor shall furnish all parts and materials required to bring all systems associated with Sewage Pump Station 1286 back into operation. The contractor shall replace the existing nonworking generator and automatic transfer switch to ensue emergency power is available for emergency situations. The contractor shall install a Well Tech. Mission Control alarm system to keep consistency with the facilities other sewage pump station. The contractor shall replace the existing electrical panel with one capable of housing all controls for the pumps, floats, alarms system, and emergency power supply needs. The contractor shall install a new float system compatible the Well Tech Mission Control system. The contractor shall replace all valves associated with pump station 1286, in addition to any necessary brackets, and guide rails. The contractor shall replace all piping that is below industry standard after inspections. After all work, has been completed the contractor shall furnish a comprehensive electrical diagram showing sequence of operation of all system within the new electrical panel. The contractor shall provide a one year warranty on all parts and labor.

Generator and Automatic Transfer Switch (ATS) Information:

Onan Cummins Diesel Generator-25 KW 208\120 Volts, 2-Phase has a 100-amp breaker.
ATS- 25KW, 208\120 Volts, 3-Phase has a 100-amp breaker.

Mission Communication alarm information is attached below.

General:

In accordance with this contract the contractor shall provide all labor, material, equipment and transportation to include all accessories and incidentals necessary to complete the job to government requirements. The facility under this contract may contain asbestos materials. The contractor is warned not to disturb any asbestos material during the performance of this work. Should the contractor encounter any material that in their judgement may contain asbestos, they must stop work immediately and notify the contracting officer (CO) within 24 hours.

Prior to commencing work, the contractor is required to obtain Construction Authorization, vehicle permits and identification badges. Vehicle permits and identification badges must be returned to the Government prior to final payment.

NOTE: THE CONTRACTOR SHALL NOTIFY THE GOVERNMENT TECHNICAL REPRESENTATIVE ON 301-440-9641 or 301-504-8025 AT LEAST 24 HOURS BEFORE ANY WORK IS SCHEDULED TO START.

All contractors work shall be monitored and inspected by personnel and done in accordance with the Statement of Work and attached drawings, specifications, graphics, BARC special conditions and performed in accordance with federal, state and local regulations as well as all applicable building codes, Construction Standards and Codes. Americans with Disabilities Act, state and local traffic codes, Maryland department of the Environment, the Maryland Highway Specifications and MDE concerning the Clean Water Act. In the event of conflict the most stringent regulation will prevail.

Mission Communication Alarm Information:

Features In Brief:

· Economically Priced

· Easy trouble free installation

· Rugged, debris-free non-fouling Teflon™ coated 316 stainless steel housing.

· Large protruding (no cavity to clean) 2 5/8” Teflon Coated–BunaN sensing diaphragm.

· Maintenance free “Rigid Sealed Breather system” reliably equalizes atmospheric pressure.

· Versatile mounting arrangements

· Intrinsically safe, Class I, Div. 1 A, B, C & D rated with approved barrier.

· Pre-calibrated Pressure ranges from 1.5 PSI to 30 PSI. (0-3.5 ft to 0-69.3 ft)

· Transducer electronic components are electronically and physically isolated from sensed media.

DATA SHEET

A1000i Loop Powered/4-20mA Submersible Level Tra nsmitter

The A1000i Submersible Level Transducer is the industry’s most highly engineered and advanced submersible level transmitter for the measurement of liquids containing high amounts of solids such as raw sewage/wastewater. The unit works equally well in potable water applications. The robustness and high reliability of the A1000i is based on its maintenance free design and simplicity of operation allowing it to operate in harsh environments. The unit is unaffected by turbulence, foaming, false echoing, solids build up, and atmospheric changes that often cause other level transmitter technologies to fail. A selection of pressure ranges is available to fit most wet well level/pressure measurement applications from high accuracy weir level/flow rate measurement to the deepest of wet wells and storage tanks. Several mounting options are available including vessel, pipe, fixed and suspension kits.

Applications:Theory of Operation:
· WastewaterThe A1000i utilizes pressure, the most
Sewage lift station wet wellsreliable means to measure liquid level. The
Headworkssensor assembly is mounted at a low point

Combined Sewer Overflow (CSO) (fixed or suspended) within the liquid Sequencing Batch Reactors (SBR) media and uses a sensing diaphragm to Lagoons/ponds, Lakes & Rivers measure the hydrostatic head-pressure. The Equalization Basins pressure produced is proportional to the Weir Flow Measurement height of the liquid above the sensing Contact Tanks diaphragm.

Sumps The protruding (no cavity) flexible Teflon coated Buna-N diaphragm uses a liquid fill

· Water to transfer the external diaphragm pressure Raw Water Intake Level to a stable and accurate gauge pressure type Filter Water Levels piezoresistive sensor. The transducer uses Clearwells the loop power excitation source (9 Backflush Decant Tanks 30VDC) and converts the pressure to a Above or Below Ground Storage proportional (4-20mA) electrical signal.

TanksThetransducerisbarometrically
Standpipescompensated via a rigid breather tube

connected to a panel mounted sealed breather system.

DATA SHEET

Specifications

Housing
316 cast stainless steel , Teflon™ coated
Cable
Heavy-duty polyethylene with vent tube, 18 AWG conductors and shield.
Atmosphere Ventilation
No maintenance sealed breather system equalizes atmospheric pressure
Mounting
Suspension Cable mount or 1“ pipe mount
Exposed Materials
#316 SS, PVC, Teflon™, synthetic rubber and urethane.
Sensing head
Two layer diaphragm with Teflon™ and Buna-N material.
Power Required
9 – 30 VDC (750 ohm Load @ 24VDC)
Signal Output
4 - 20mA Two wire shielded conductor cable
Agency Approval
FM and CSA Intrinsically Safe Class I, Div. 1, Groups A,B,C,D with approved barrier.
Accuracy
0.25 % Full Scale with long term stability of 0.2 % Full Scale per year.
Pressure Ranges
1.5 PSI to 30 PSI (Consult factory for ranges over 30 PSI)
Max Over Pressure Range
1.5 PSI 8X Full Scale

5.0 PSI 4X Full Scale

15 PSI & 30 PSI 2X Full Scale

Temperature Range
-40 to +185ºF (Liquid must remain fluid)

Part Numbers Lower Assembly Dimensions

Description
Part Number

A1000i Sensors

1.5 PSI 4-20mA output (0-3.5 ft of water)
6012950011
5 PSI 4-20mA output (0-11.5 ft of water)
6012950012
15 PSI 4-20mA output (0-34.7 ft of water)
6012950013
30 PSI 4-20mA output (0-69.3 ft of water) Consult factory for ranges over 30 PSI.
6012950014

Housing/Cable Assembly

A1000 Housing/Cable Sub-Assembly 20ft
6012640002
A1000 Housing/Cable Sub-Assembly 30ft
6012640003
A1000 Housing/Cable Sub-Assembly 40ft
6012640004
A1000 Housing/Cable Sub-Assembly 60ft
6012640006
A1000 Housing/Cable Sub-Assembly 80ft
6012640008
A1000 Housing/Cable Sub-Assembly 100ft
6012640010
A1000 Housing/Cable Sub-Assembly custom lengths (XX equals number of feet)
60126400XX

Mounting Hardware and Accessories

B100 9G CLS Stainless Steel Pipe Mounting Clamps
6011340001
Cable Suspension Mounting Pipe (without SS cable)
6014180001
Stainless steel cable; each additional 10’ ft (XX)
60144000XX
Breather Assembly Kit (required for all A1000i sensors)
6012880001
Terminal Connection (Junction) Box w/Built In Breather Assembly
6012910002
Complete Control Capabilities
USFilter Control Systems offers a single, high-quality source for everything from simple level sensors to telemetry systems to complex system control engineering and software. Based in St Paul, MN, USFilter Control Systems is part of United States Filter Corporation, the leading global provider of industrial, municipal and residential water and wastewater treatment systems, products and services. As a major manufacturer/integrator with an extensive selection of specialized product lines in the areas of SCADA and telemetry, power equipment integration, automation and meaurement, USFilter Control Systems is uniquely positioned to provide cost-effective, comprehensive solutions for water, wastewater and process control and telemetry applications.

CONTROL SYSTEMS

1239 WILLOW LAKE BLVD

VADNAIS HEIGHTS, MN 55110

651-766-2700 PHONE

651-766-2701 FAX

CS-A1000I-DS-0503

MyDro 150, 850 The Next Generationof Wireless Real-Time Alarm, Monitoring, and

Remote Control All of the functionality of the M110 and M800, with an onboard interactive display and enhanced electronics.

MyDro 150 and 850 RTUs Easy to Install Each remote terminal unit (RTU) includes the necessary hardware for installation, such as a cellular radio, enclosure, backup battery, transformer, antenna with cable, and mounting hardware. Purpose-built RTUs simplify and speed installation. There is no programming required, and RTUs are self-enrolling.

Reliable Wireless Communications RTUs operate on current generation cellular radios for dependable data transmissions. Mission maintains direct relationships with the largest cellular carriers in the U.S. and Canada to ensure the best service possible. There are no radios to license or cellular contracts to set up.

Real-Time Alarms Delivered To All Devices Real-time alarms are delivered via phone call, text message, email, fax, pager, and even to your existing HMI software through an OPC data link. Each alarm is logged with a timestamp for tracking and reporting. The alarm call-out schedule setup is easy, flexible, and intuitive, to be as simple or sophisticated as you want it to be.

Managed Service –The Complete Package The Mission system includes all cellular data service, data storage, alarm call-outs, reports, and on-call, 24-7-365 technical support. The highly reliable turnkey system offers more features at a lower cost than an in-house setup. No engineering or programming is required, and there are no networks to maintain.

View your data and reports using the included Mission 123SCADA software, accessible on your secure web portal from any web-enabled device. 123SCADA is the newest Mission user interface designed with the look and feel of industry-standard HMI SCADA that is packed full of new features, as well as the legacy user mode. Tabular and graphical reports can be used for compliance reporting and comparative studies. As always, system enhancements are included at no cost and are immediately available.

M150 RTUs Real-Time Alarms with Hourly Summaries M150s summarize pump run times and pump starts hourly. All alarm data is reported in real-time. Analog data and RTU status are reported hourly. Simultaneous pump runtimes can be reported when two pumps run.

M850 RTUs Real-Time Alarms and Streaming Data M850s report pump starts and stops in real-time. Analog values are reported every two minutes or on 5% change. Volumetric flow calculations can utilize this information along with sump volume (as determined by an analog level sensor or fixed entries) to calculate hourly volumetric flows.

Remote Control Expand your system with optional remote control for offsite wells, tanks, gates, chlorine dosers, variable frequency drives, and more. Optional automatic remote control interfaces include the Tank and Well Control Package, Digital Intertie, and Analog Intertie.

LCD Touch Screen

· Displays current status

· Supports local configuration Radio

· Cellular radios support LTE, 4G, 3G, and 2G forboth GSM (AT&T and partners) and CDMA (Verizon and partners)

· Dual SIM-capable radio

· No radio licenses or site path studies required Expandable

• Up to 16 digital inputs, six analog inputs, two pulse inputs, and two analog outputs, all simultaneously

· Onboard digital inputs configurable for wire fault supervision or strap on load sensor for easier pump run indication

· RS485 for digital, analog, and pulse expansion via ADAM Modules Enhanced

· 12 or 24VDC auxiliary output for battery-backedanalog instrument loop power

· Over-the-air upgradable firmware Application M150 M850 Wastewater sewage lift station, master SPS monitoring and industrial water quality control, WWTP critical

(WQ) alarming, liftprocess monitoring, open station generatorchannel flow monitoring,
alarmingsewer station power

monitoring, reuse water monitoring and control Water pump station alarming, pump station monitor, tank reservoir level alarming, and multiple well control, remote valve alarming, CI remote valve monitoring residual WQ alarming, and control, CI residual WQ, flow or pressure alarming, flow or pressure monitoring PRV station alarming Other gate status alarming, septic offload and billing, rainfall monitoring custody transfer and billing, canal level monitoring and gate control, I&I flow and level data logging

Technical SpecificationsOutdoor NEMA 4X enclosure:

Front shield ''w x 13.75''h x 6.25''d 13.25 with sun shield Weight: 8 lbs NEMA 1 enclosure:

11.375 ''w x 11.25''h x 3.5''d Use indoors, wall mounting Weight: 3 lbs Flatpak NEMA1 enclosure:

10.5 ''w x 7.75''h x 1.5''d Use inside MCC cabinet Weight: 2 lbs

Model M150
Model M850

Data

Alarm Data
Real-time
Real-time
Pump State
Summarized hourly
Real-time
Analog Reporting
Current value reported hourly
Every two minutes, or on 5% change
Device Health
Built-in inputs reported hourly

Input / Output

Digital Inputs
Eight on-board digital inputs (dry) with selectable wire fault supervision, or direct attach load sensor (for easiest pump run indication)

Expandable to 16 with ADAM Modules

Three configurable for pump run summary reporting (number of starts and run time each hour). Simultaneous runtimes reported when two pumps are monitored.

Up to eight configurable for pump run. Pump states reported in real-time.

Simultaneous pump runtime reporting supported for up to seven pumps.

Analog Inputs
Two on-board, 4–20mA "isolated" or 0–5VDC. Four alarm set points each. Expandable to six with ADAM Module.
Relay Outputs
Three remotely controllable, form C, dry contact relay outputs, 5amps at 30VDC, 120VAC, SPDT, N.O./N.C.
RS485
Support for specified ADAM expansion modules
Pulse Inputs
Two channels with

ADAM expansion module

Fifteen minute reporting
Two minute reporting
Electronic Key Reader
Key reader for site activity tracking and service mode

Built-in Inputs

AC voltage, battery voltage, board temp and signal strength. Optional second (removal) key reader.

Electrical

AC Power
Supervised 120VAC to 12VAC, 1.2amp, UL-recognized class II/class III transformer
Backup Power
12V, 5AH battery standard, with enhanced charging system
Up to 50 hoursUp to 18 hours
Auxiliary
Auxiliary output selectable 12VDC or 24VDC for battery-backed analog instrument loop powering. 250mA max.
Removable Terminals
Included: Amphenol PN 20020008-G061B01LF (6 pin for power), 20020004-D081B01LF (D08, D04, D03 for I/O)

Other

Physical
(See top right)
Environment
Operating temperature -20–75°C, non-condensing
Cellular Radio
Radios make live, continuous, encrypted TCP socket connections. Payload is end-to-end acknowledged. Penta band (850, 900, 1700, 1900, 2100 mHz). AT&T and partners: LTE, HSPA+, 3G. Verizon and partners: LTE, EVDO, 1XRTT, dual SIM (carrier) capable.
Antenna
Omnidirectional antenna with 11' cable, SMA termination, universal mounting bracket
Options
Optional SCADA integration OPC link (PN SW586) to client/server HMI, Tank and Well Control Package (see accessories brochure for details)
Service
Requires Service Packages for the unit and optional expansion boards (see accessories brochure for details)
Warranty
One year manufacturing and material warranty

(877) 993-1911 • sales@123mc.com • www.123mc.com ©2017 Mission Communications. The Mission Communications logo is property of Mission Communications. All Rights Reserved. Protected under patents 7,216, 145. Specifications subject to change without notice.

Literature Code: M150/M850-0817

LC150

VIEW-AT-A-GLANCE

PUMPCONTROL-TELEMETRYUNIT

Features In Brief

· Telemetry Ready

· Security

· 2 or 3 Pump Control

· UL® Listed

· Alarm/Event Log

· Volumetric Flow Calculator

· VFD Control

· Optional Dialer

· Optional Ethernet Port

USFilter Control Systems is proud to introduce the LC150 Pump Controller, the newest addition to the family of “View-At-A-Glance” controllers. For nearly two decades, the D150 Series of “View-At-AGlance” Pump Controllers has set the standard in the industry for ease of use and reliability. Now the LC150 provides the simplicity customers have come to expect with the advanced features they need – all in one system!

The LC150 is designed specifically for pump station applications and offers a simple, reliable and cost effective solution. The new "View-At-AGlance" interface provides the operator with all the information needed to operate and maintain the pumping system and is UL® listed and NEMA® 4 rated.

FEATURES

Telemetry Ready - with the addition of a radio, phone line connection or connection to a high speed Ethernet interface (with the Ethernet option), the LC150 allows you to monitor station status, change pump start and stop setpoints, change high and low level alarm setpoints, acknowledge alarms, and view pump run, fail, and performance information remotely. If alarm notification is the only requirement, the optional integrated alarm dialer provides real voice notification of alarm conditions over a dial up telephone line.

Versatile - the LC150 can be used to control and monitor up to three constant and/or variable speed pumps in either pump up or pump down mode. This versatility makes the LC150 useable even in difficult pump applications like pressure/flow controlled booster stations.

Time and Date Stamped Alarm/Event Log - the LC150 logs the time and date that alarms and events occur. This historical log provides the operator with the ability to analyze pump performance and system failures.

Volumetric Flow Calculator - the LC150 calculates flow rates based on level excursions and logs daily flow, flow rates per pump and average flow rate per pumping cycle. This information can be viewed locally at the operator interface and remotely via the telemetry connection.

Password Protection - three levels of password security allows only authorized users to modify the controller parameters.

Site Security - with the addition of a simple door switch or motion detector, the LC150 can function as a site security system used to detect unauthorized entry onto the premises.

Simply

View-At-A-Glance Operator Interface View all critical information including:on/offsetpoints,level alarm setpoints,level alarms and the process variable without pressing any keys.

Custom Scale Ranges Allows you to scale the controller display precisely to the process.

NEMA 4 Rated Operator Interface Pump Up or Pump Down Mode Controls 2 or 3 pumps in either mode.

Alarm Control Easily silence audible alarms and reset latching alarm conditions.

LCD with Backlighting line x character display and simple (4-key) key pad allows easy access to more advanced information.

Verify Proper Pump Operation Two simple up/down keys allows an operator to simulate the process.

Alternation The LC150 supports multiple modes of operation configurable through the LCD and keypad.

Drop in Replacement Operator Interface has the same footprint as D15x series products.No drilling or modifying the door.

the Easiest Most User Friendly Pump Control-Telemetry Unit on the Market Today the Most Advancedthe Most Advanced Pump Control-Telemetry Unit on the Market Today

Pump Protection The LC150 controller will detect failed pumps, and take the failed pump out of service until corrected and reset.

Volumetric Flow Calculation The controller can calculate station flows without the need for a flow meter.

Pump Run Data

· Total run time

· Total number ofstarts

· Daily run time

· Average number of starts/day

· Total pump flow

· Average flow rate of the pump A utility can monitor the pumps performance over time and perform maintenance on a pro-active basis rather than a reactive one.

Time and Date

Stamped Alarm/Event LogTwo Piece Design
Stores the last 100Door mounted operator
Alarm/Events.interface and DIN rail

mounted I/O base.

Security Protection

· 3 level passwordsecurity

· Detect unauthorizedstation access (intruders) with a door switch input and an operator interface security password.

· Activates local alarmand telemeters unauthorized entry to a central monitoring point.

Calculated Flow Statistics

· Total station flow

· Average daily flow

· Maximum daily flow A utility can monitor station performance and spot potential problems.

Built-in RS-232 Serial Port The LC150 Supports a Wide Variety of Supports Modbus® and USFilter Communication Media

• Ethernet (optional)Open Protocols

• Radio (UHF,VHF,Spread Spectrum) Volts AC or 10-30

VDC

Operation Isolated Inputs Pull Apart Terminal Blocks Ease of Installation & Diagnostics On board communication and diagnostics LED support troubleshooting

APPLICATIONS
Built-in Battery Charger
Maintenance

Sewage Lift Pump Station – Well Pump Station – Controls pumps based on locallyControls pumps based on locally monitored wetwell level. Supports bothmonitored pressure/level sensor or level transmitter and float switch controlremotely telemetered tank level.

inputs for primary and back up control strategies.

Raw Water Pump Station – WWTP Influent or Effluent PumpControls pumps based on locally Station – Controls pumps based onmonitored or telemetered flow locally monitored wetwell level.rate/pressure/level sensor signal.

Supports both level transmitter and float switch control inputs for primary and back up control strategies.

Transfer Pump Station – Booster Pump Station – Controls pumps based on locally Controls pumps based on locallymonitored wetwell level. Supports monitored discharge pressure sensor orboth level transmitter and float switch remotely telemetered tank level.control inputs for primary and back up control strategies.

Irrigation Pump Station – Controls pumps based on locally monitored discharge pressure or flow rate.

SPECIFICATIONS

Base Unit

Power Supply
120 VAC or 10-30 VDC w/Battery backup
Packaging
DIN rail mount, 5.4” x 7.5” x 2.25”
Communications Port
OI port, RS232 Telemetry Port, 10/100 Ethernet port (optional), 802-11 b/g wireless Ethernet (optional), Ethernet and serial ports support Modbus and

USFilter Open, 32 channel auto-dialer (optional)

Discrete Inputs
16 channels, max 30 VDC, isolated
Pump/Alarm Outputs
5 channels, 10A @ 120 VAC relays
High/Low Level Alarm Outputs
2 channels, Open collector, 100 mA @ 5-30 VDC
Analog Input
1 channel, 4-20 mA or 0-10 VDC
Resolution
16 bits
Calibration
Software
Isolation
1 KV
Excitation Voltage
24 VDC or 6.2 VDC, isolated
Analog Output
1 channel, 0-5 VDC
Certifications
UL, FCC, CE

Operator Interface

Packaging
Door mounted, 8.5” x 7.5” x 1.5”
Power
Supplied through communications cable from Base Unit
Level, Stage, Alarm Setpoint Display
LED columns, 40 segment, ultra bright
LCD
2 x 16 character, backlight, 4 key keypad
Communications Port
RS232 w/power
Environmental Rating
NEMA 4
Part Number
Description
Availability
ILK-LC150001-01
LC150 Pump Controller, Base Unit, 16 DI, 5 relay outputs, 2 open collector outputs, 1AI, 1 AO, RS232 telemetry port
Q3 2005
ILK-LC150002-01
LC150 Pump Controller, Base Unit, 16 DI, 5 relay outputs, 2 open collector outputs, 1AI, 1 AO, 10/100 Ethernet port
Q1 2006
ILK-LC150003-01
LC150 Pump Controller, Base Unit, 16 DI, 5 relay outputs, 2 open collector outputs, 1AI, 1 AO, 802.11b/g wireless Ethernet port
Q1 2006
ILK-LC150004-01
LC150 Pump Controller, Base Unit, 16 DI, 5 relay outputs, 2 open collector outputs, 1AI, 1 AO, 32 channel Auto-dialer, voice annunciated alarms, touch tone acknowledge
Q1 2006
ILK-LC150020-01
LC150 Operator Interface
Q3 2005

UL is a registered trademark of Underwriter’s Laboratories, Inc.

Modbus is a registered trademark of Schneider Automation, Inc.

NEMA is a registered trademark of National Electrical Manufacturers Association.

USFilter is a registered trademark of USFilter Corporation.

USFilter reserves the right to change the specifications referred to in this literature at any time, without prior notice.

CS-LC1-BR-0705

To find out more about how to put USFilter to work for you, contact us at USFilter Control Systems 1239 Willow Lake Boulevard Vadnais Heights, MN 55110 800-224-9474 toll free 651-766-2700 phone 651-766-2701 fax For more information, call 800.944.4811 or visit our web site at www.usfilter.com ©2005 USFilter Corporation

April 27, 2020 image4.jpg image5.png image6.png image7.png image8.png image9.jpg image10.jpg image11.jpg image12.jpg image13.jpg image14.jpeg image15.jpeg image16.png image17.png image18.png image19.png image20.jpeg image21.jpeg image22.jpeg image23.jpeg image24.jpeg image25.png image26.png image27.png image28.png image29.png image30.png image31.png image32.png image33.png image34.jpg image35.png image36.png image37.png image38.png image39.png image40.png image41.png image42.png image43.png image44.jpeg image45.png image46.png image47.png image48.png image49.png image50.png image51.png image52.png image53.png image54.png image55.png image56.jpg image57.png image58.png image59.jpeg image60.png image61.png image62.png image63.jpg image1.jpg image64.png image65.jpeg image66.png image67.jpg image2.png image3.jpg