STATEMENT OF WORK
Makah National Fish Hatchery (NFH)
Generator Switch Repair
1. GENERAL:
• Repair communication between two automated transfer switches (ATS) and two 450kw generators.
• Existing ATS configuration doesn’t allow for the generators to operate from either ATS unit (there are two separate ATS devices).
• Current issue could be the four way rotary switch, timer relay, alarm panel wiring, or an unknown problem.
• The existing Eaton SPD Series surge protective device on ATS #2 needs to be replaced along with repairing the communication between generators and ATS #1 and #2.
2. DEFINITIONS:
• Generator #1: Make: Cummins/Year:2013/Model:DFEJ-1335491/SN:I130562068
• Generator #2: Make: CAT/Year:2017/Model:450/SN:CAT00C15PT3300201
• ATS #1 & #2: Make: Eaton/Cutler-Hammer/Year:2010/Model:1600amp480v/
GO#kw601182/Job#ese0006492
3. SCOPE:
• Identify communication issues between Makah NFH’s two generators and two ATS switches.
• Properly repair communication so that each generator will run from either ATS (we run one generator at a time).
• Remove and replace Eaton SPD Series surge protective device from ATS#2.
4. REQUIREMENTS:
• While work is being performed generator use will not be interrupted. Generators provide back-up power for the hatchery and are critical to fish survival in an emergency. Short periods of interruption are acceptable and can be scheduled with Makah NFH’s Maintenance Mechanic.
• The generators are tied into the Makah NFH’s emergency alarm system.
Communication with the alarm system must be maintained and remain intact at the end of the project.
5. PLACE/DELIVERY AND PERIOD OF PERFORMANCE:
• Makah National Fish Hatchery 897 Hatchery Road Neah Bay, WA 98357
Period of Performance
• Will be determined between mutual agreement between contractor and hatchery management.
• Work shall be coordinated with Kristin Bates at 360-645-2521 or by email at kristin_bates@fws.gov mailto:kristin_bates@fws.gov
STATEMENT OF WORK
Makah National Fish Hatchery (NFH)
Generator Switch Repair
6. INSPECTION AND ACCEPTANCE: Inspection and acceptance will be performed by Vern Tolliver (Maintenance Mechanic) from Makah NFH.
7. GOVERNMENT FURNISHED EQUIPMENT OR MATERIALS/
INFORMATION: Government will not furnish any equipment, tools, or materials.
Contractor will provide all necessary materials and equipment to complete generator/ATS repair.
8. AVAILABILITY: Work site available upon coordinated work schedule.
9. TECHNICAL COORDINATOR:
Point of Contact for technical assistance is Kristin Bates Phone: 360-645-2521