SOW Attachments.pdf
PDF 1 MB Posted
- Attached to
- N045--Glycol Make Up Unit Installation Federal contract opportunity
- Solicitation number
- 36C24124Q0701
About this file
This document appears to be a set of floor plan attachments related to a federal contract opportunity for the Glycol Make Up Unit Installation at the Northampton VA Medical Center, solicitation number 36C24124Q0701.
The attachments include a basement floor plan, mechanical part plans, and a hot water piping schematic. Key details indicate the project involves replacing existing ceiling diffusers, connecting steam and condensate return piping to the basement, and installing a new steam-to-hot water converter and circulating pump. The contract is fully sprinklered and being issued by the U.S. Department of Veterans Affairs, Veterans Integrated Service Network 1. The solicitation was posted on May 4, 2020, but no additional award details are provided.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Combined Synopsis Solicitation Glycol Unit Installation rev2.pdf | ||
| 36C24124Q0701.docx | DOCX document |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FLOOR PLAN LEGEND
STRUCTURAL GRID LINE
A KEYNOTE, SEE FLOOR PLAN
KEYNOTE LEGEND
NEW CONSTRUCTION
EXISTING CONSTRUCTION
FLOOR PLAN KEYNOTES
DOOR TAG, SEE
DOOR SCHEDULE101
ACCESSORY TAG, SEE
ACCESSORY TYPES &
INTERIOR ELEVATIONS
WINDOW TAG, SEE
WINDOW SCHEDULE
1. ARCHITECTURAL DATUM = 100'-0". THE
ARCHITECTURAL DATUM IS INDEPENDENT OF
ELEVATIONS SHOWN ON THE CIVIL DRAWINGS.
SEE CIVIL DRAWINGS FOR CORRESPONDING
DATUM IN HEIGHT ABOVE SEA LEVEL.
2. ALL DIMENSIONS AT NEW WALLS ARE TO
OUTSIDE FACE OF STUD, FACE OF CONCRETE,
FACE OF MASONRY, OR CENTER OF OPENING,
U.N.O. AT EXISTING WALLS DIMENSIONS ARE
TO FINISH FACE OF WALL.
3. DO NOT SCALE DRAWINGS. CONTACT
ARCHITECT FOR ANY DISCREPANCY PRIOR TO
COMMENCING WITH ANY WORK.
4. REFER TO DIMENSION PLANS FOR GENERAL
PARTITION NOTES & PARTITION TYPES.
5. VERIFY FIELD CONDITIONS PRIOR TO
COMMENCEMENT OF EACH PORTION OF THE
WORK. NOTIFY ARCHITECT OF DISCREPANCIES.
6. ALL LUMBER IN DIRECT CONTACT WITH
CONCRETE SHALL BE PRESSURE TREATED
INCLUDING ALL SILL PLATES FOR WOOD STUD
WALLS.
7. REVIEW PRIOR TO INSTALLATION, ANY
CONFLICT OF ENGINEERING TRADE DEVICES
(I.E. FIRE ALARM STROBES) WITH
ARCHITECTURAL DETAILS AND BRING THOSE
DISCREPANCIES TO THE ARCHITECT FOR
REVIEW.
8. PROVIDE BLOCKING FOR MILLWORK,
MECHANICAL FIXTURES, PLUMBING FIXTURES
AND OTHER ITEMS IDENTIFIED IN THE
CONSTRUCTION DOCUMENTS.
9. COORDINATE MISC. STEEL REQUIREMENTS FOR
MOUNTING / HANGING OWNER SUPPLIED
EQUIPMENT.
GENERAL PLAN NOTES
X
1t
EXISTING DOOR
NEW DOOR
A301
A301
A301
A301
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room
Room 23A
Room
Room
Room
A321
A321
A322
A302
A302
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
ISSUED FOR
CONSTRUCTION
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
BI
M
VA
M C
N H
K itc he n/
V
AM
C K
IT
C
H
EN
_j s@ w ar re ns tre et
.c oo p.
rv t 6/
/2
2:
:3
PM
A111
BASEMENT PLAN
WARRENSTREET ARCHITECTS, INC.
27 WARREN STREET
CONCORD, NH 03301-4049
(603) 225-0640
JONATHAN SMITH
BUILDING 5 UTILITIES
VAMC NORTHAMPTON
VA241-16-C-0124
5/4/2020
1/8" = 1'-0"A111
1 BASEMENT FLOOR PLAN
Revisions: Date:
https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215901 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215901 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215935 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215935 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215935 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215935 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215920 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215920 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215904 VHANHMMenarN Callout
JCI CONTROL BOX LOCATION
VHANHMMenarN Callout Approximate Location of Glycol Make-Up Unit
VHANHMMenarN Oval
VHANHMMenarN Callout Supply and Discharge connections approximate location
VHANHMMenarN Oval
VHANHMMenarN Oval
H W
S
HWS HWS HWS HWS HWS HWS HWS HWS HWS HWS HWS HWS
H W
S
H W
R
HWR HWR HWR HWR HWR HWR HWR HWR HWR HWR HWR HWR
H W
R
H W
R
H W
R
H W
S
H W
S
P C R
P C R
P C R
H W
S H
W S
H W
S
H W
R H
W R
H W
R
S T M
S T M
S T M
C R
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
MEP
/1
/2
:1 :4
P
M
WARRENSTREET ARCHITECTS, INC.
27 WARREN STREET
CONCORD, NH 03301-4049
(603) 225-0640
JONATHAN SMITH
BUILDING 5 UTILITIES
VAMC NORTHAMPTON
VA241-16-C-0124
Revisions: Date:
Loureiro Engineering Associates, Inc.
100 Northwest Drive
Plainville, Connecticut 06062
Phone: 860-747-6181 / Fax: 860-747-8822
An Employee Owned Company email : info@loureiro.com
Comm No. 91WN601
Loureiro Engineering · Construction · EH&S · Energy
Waste · Facility Services· Laboratory
ISSUED FOR
CONSTRUCTION
5/4/2020
FULLY SPRINKLERED
REPLACE (8 VIF) EXISTING 10"Ø CEILING
DIFFUSER, 750CFM EA.
1/8"=1'-0"
PART PLAN - NEW WORK
REPLACE (18 VIF) EXISTING 10"Ø CEILING
DIFFUSER, 750CFM EA.
1/8"=1'-0"
PART BASEMENT MECHANICAL PLAN
CONNECT STEAM & PCR TO
BASEMENT PIPING.
4"Ø HWS&R UP THROUGH FLOOR TO CLOSET
ABOVE. REFER TO PART PLAN 1 THIS SHEET
FOR CONTINUATION.
NEW STEAM TO HW CONVERTER
CV-1. SEE SCHEMATIC DETAIL.
CRU-1
NTS
HOT WATER PIPING SCHEMATIC
H-103GAL MAK
PART PLANS - NEW WORK, BASEMENT
MECH PLAN AND PIPING SCHEMATIC
NOTES:
1. DUCTWORK, STEAM & CONDENSATE PIPE ROUTING SHOWN
IS SCHEMATIC IN NATURE. CONTRACTOR TO FIELD VERIFY
EXISTING CONDITIONS PRIOR TO THE START OF WORK.
2. CONTRACTOR TO COORDINATE WITH OTHER TRADES PRIOR
TO THE START OF WORK.
HWS&R UP THROUGH ROOF TO UNIT,
REFER TO SCHEMATIC ON THIS SHEET
AND ROOF PART PLAN ON H-102 FOR
CONTINUATION (TYP)
ROUTE INSULATED HWS&R PIPING IN
CEILING SPACE (TYP)
4" HWS&R PIPING ROUTED UP FROM
BASEMENT INTO CHASE AND UP INTO
CEILING SPACE.
HWP-1
"STM
1"PCR
3" HWS&R
" HWS&R
" HWS&R
MAU-1
RTU-1
MAU-2
RTU-2
" HWS&R
" HWS&R1
" HWS&R
4" HWS&R
CV-1
CRU-1
STEAM TO HW CONVERTER
"CR
"CR
EXISTING 1" CONDENSATE
RETURN HEADER.
1"PCR
EXISTING STEAM MAIN.
CONNECT NEW 2
" STEAM
TO EXISTING STEAM MAIN.
0-60PSIG
3" HWS&R
HWP-1
CIRCULATING PUMP
190GPM @ 30 FT HD.
EXIST STM MAIN
EXIST CR MAIN
0-60PSIG
30 TO
200° F
30 TO
200° F
HEAT EXCHANGER SCHEDULE
PASSES
NUMBER
CV-1 30%PG
MEDIA
GPM
190 10
PSI
HOT SIDE (STM)
<1psi
COLD SIDE (30% PG)
EWT
160°F
LWT
180°F 1940
#/HR
P
LWT
P
(MBH HR)
CAPACITY
NO.
REMARKS
TYPE
TUBE
NOTE:
SEE NOTE #1
MANU/MODEL
1) MANU/MODEL LISTED ARE ONLY USED AS THE BASIS FOR DESIGN. REFER TO SPECIFICATIONS FOR LIST OF ACCEPTABLE MANU/MODELS.
TACO E16208-S
PUMP SCHEDULE
NUMBER
FLOW
(GFM)
RPM TYPE
REMARKS
TDH
(FT)
ELEC
HWP-1 190 1,750 INLINE
208V/3PH
MOTOR
(HP)
MEDIA
30% PG 52
HEAD (FT)
SHUT-OFF
MANU/MODEL
TACO SKV3007-1760-3
NOTE 1 & 2
NOTE:
1) MANU/MODEL LISTED ARE ONLY USED AS THE BASIS FOR DESIGN. REFER TO SPECIFICATIONS FOR LIST OF ACCEPTABLE MANU/MODELS.
2) PROVIDE PUMP WITH VFD, NON-OVERLOADING MOTOR, BACKNET INTERFACE AND DISCONNECT SWITCH.
TRANSITION AND CONNECT EXISTING R/A
DUCTWORK TO NEW DROPS FROM
PENTHOUSE ABOVE.
TRANSITION AND CONNECT EXISTING
S/A DUCTWORK TO NEW DROPS FROM
PENTHOUSE ABOVE.
TRANSITION AND CONNECT EXISTING S/A
DUCTWORK TO NEW O/A DROPS FROM
PENTHOUSE ABOVE.
EXIST EXHAUST DUCT UP TO
PENTHOUSE
AI HW-DP HOT WATER DIFFERENTIAL PRESSURE 0-10VDC
AO HX1V1-O HEAT EXCHANGER 1 VALVE 1 OUTPUT 0-10VDC
AO HX1V21-O HEAT EXCHANGER 1 VALVE 2 OUTPUT 0-10VDC
BO PHWP1-C PRIMARY HW PUMP 1 COMMAND 24VAC MAINTAINED
AO PHWP1-O PRIMARY HW PUMP 1 OUTPUT 0-10VDC
BI PHWP1-S PRIMARY HW PUMP 1 STATUS DRY CONTACT MAINTAINED
BO PHWP2-C PRIMARY HW PUMP 2 COMMAND 24VAC MAINTAINED
AO PHWP2-O PRIMARY HW PUMP 2 OUTPUT 0-10VDC
BI PHWP2-S PRIMARY HW PUMP 2 STATUS DRY CONTACT MAINTAINED
AI PHWR-T PRIMARY HW RETURN TEMPERATURE NICKEL 1K RTD
AI PHWS-T PRIMARY HW SUPPLY TEMPERATURE NICKEL 1K RTD
POINTS SCHEDULE
NAME
SIGNAL
SYMBOL DESCRIPTION
HOT WATER SUPPLY SEQUENCE OF OPERATION:
SYSTEM ENABLE:
THE HEATING SYSTEM WILL AUTOMATICALLY START WHEN THE OUTSIDE AIR TEMPERATURE (OA-T) FALLS BELOW THE SYSTEM ENABLE SETPOINT (HTGOATLOCKOUT-SP) WHILE THE SYSTEM ENABLE (SYSTEM-EN) IS "ON". WHEN THE OUTSIDE AIR TEMPERATURE (OA-T) RISES ABOVE THIS SETPOINT (HTGOATLOCKOUT-SP) OR THE SYSTEM ENABLE (SYSTEM-EN) IS "OFF", THE HEATING SYSTEM WILL BE
DISABLED.
HEAT EXCHANGER CONTROL:
THIS SYSTEM CONSISTS OF ONE STEAM HEAT EXCHANGER. TWO SEQUENCED STEAM INLET VALVES (HXXV1-O, HXXV2-O) WILL MODULATE IN SEQUENCE TO MAINTAIN THE DESIRED HOT WATER SUPPLY TEMPERATURE (PHWS-T) TO SETPOINT (HW-SP) AS RESET BY
THE OUTDOOR AIR TEMPERATURE (OA-T).
HOT WATER PUMP CONTROL:
WHEN ENABLED, A PUMP (PHWPX-C) FOR EACH OPERATING HEAT EXCHANGER WILL BE STARTED. WHEN AN ADDITIONAL PUMP IS REQUIRED, THE PUMP WITH THE LOWEST RUNTIME TOTAL SHALL BE ENABLED TO RUN. IF THE PUMP STATUS (PHWPX-S) DOES NOT MATCH THE COMMAND (PHWPX-C), AN ALARM WILL BE GENERATED AND THE PUMP WILL BE STOPPED. UPON LOSS OF STATUS (PHWPX-S), THE PUMP (PHWPX-C) WILL RESTART AFTER THE SYSTEM RESET (SYS-RESET) IS MANUALLY ACTIVATED.
PRIMARY LOOP PRESSURE CONTROL:
WHEN A PUMP (PHWPX-S) STATUS IS VERIFIED, THE PUMP (PHWPX-O) WILL MODULATED TO MAINTAIN THE SYSTEM DIFFERENTIAL
PRESSURE (HW-DP) OF THE SYSTEM.
ADDITIONAL POINTS MONITORED BY THE FMS:
· PRIMARY HW RETURN TEMPERATURE (PHWR-T)
HX1V2-O
2/3
NC
STEAM
NC
HX1V1-O
1/3
COND
CV-1
HWS
HWR
HL
HW-DP
PHWP1-C
PHWP1-S
PHWP2-C
PHWP2-S
PHWS-T
PHWP2
PHWP1
PHWP2-O
PHWP2 VFD
PHWP1-O
PHWP1 VFD
PHWR-T
A
A A
A
AIR VENTS AT HIGH POINTS.
INSTALL DRAIN VALVE AT
LOW POINT IN SYSTEM.
NOTE:
1. PROVIDE AIR VENTS AT HIGH POINTS AND DRAIN VALVES AT LOW POINTS.
AS
A
BSF
BYPASS FILTERED SHOT
FEEDER W/3/4" TAPS
" CW MAKEUP
BACKFLOW PREVENTER
PRESSURE REGULATING VALVE
BALANCE
VALVE
STEAM TRAP (TYP)
STRAINER W/BLOWDOWN
(TYP)
CONTROL VALVE
AUTOMATIC AIR VENT
AIR STRAINER
EXPANSION TANK
EXIST DUCT TO REMAIN,
REFER TO SHEET H-100.
PACKAGED CONDENSATE
PUMP SYSTEM
BALANCE
VALVE (TYP.)
NORTH
NORTH
HWP-2 190 1,750 INLINE
208V/3PH
30 330% PG 52 TACO SKV3007-1760-3
NOTE 1 & 2
HWP-2
CIRCULATING PUMP
190GPM @ 30 FT HD.
AutoCAD SHX Text G:\AUTOCAD\PROJECTS\91WN601 VA BLDG 5 RENO\DWGS\91WN601 MECH.DWG Tab: H3 Saved: 5/11/2020 4:41 PM Plotted: 5/26/2020 10:29 AM https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215927 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215898 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215898
| 2. PROJECT SCOPE OF WORK |
| Work shall consist of, installation and testing of Glycol Make-Up Unit in room 14 of the basement of Building 5. |
| This includes the following task: |
| a) Furnishing and install Glycol feeder equipment and materials including all plumbing, electrical, and data requirements. |
| b) All plumbing from tank to existing supply and discharge to have unions and valves for future maintenance. Insulate plumbing pipe as needed. |
| c) Size tank to 55 gallons minimum. Glycol mixture to match existing mixture (see attached mixture submittal for reference). |
| d) Connect Glycol Feeder Tank to VA METASYS to alert for system low level alarm. (Existing JCI control box located in room 14 on west wall). Refer to COR for location. |
| e) Locate Tank and pump in eastwest corner of room 14. (Do not block access doors, existing valves, or door to steam tunnel. Refer to COR for placement of Gylcol Feeder. |
File details come from the government source that posted it. Updated .