SOW Attachments.pdf

PDF 1 MB Posted

Attached to
N045--Glycol Make Up Unit Installation Federal contract opportunity
Solicitation number
36C24124Q0701
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

This document appears to be a set of floor plan attachments related to a federal contract opportunity for the Glycol Make Up Unit Installation at the Northampton VA Medical Center, solicitation number 36C24124Q0701.

The attachments include a basement floor plan, mechanical part plans, and a hot water piping schematic. Key details indicate the project involves replacing existing ceiling diffusers, connecting steam and condensate return piping to the basement, and installing a new steam-to-hot water converter and circulating pump. The contract is fully sprinklered and being issued by the U.S. Department of Veterans Affairs, Veterans Integrated Service Network 1. The solicitation was posted on May 4, 2020, but no additional award details are provided.

View the file

Other files for this federal contract opportunity

Other files attached to N045--Glycol Make Up Unit Installation, newest first.
File Type Posted
Combined Synopsis Solicitation Glycol Unit Installation rev2.pdf PDF
36C24124Q0701.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FLOOR PLAN LEGEND

STRUCTURAL GRID LINE

A KEYNOTE, SEE FLOOR PLAN

KEYNOTE LEGEND

NEW CONSTRUCTION

EXISTING CONSTRUCTION

FLOOR PLAN KEYNOTES

DOOR TAG, SEE

DOOR SCHEDULE101

ACCESSORY TAG, SEE

ACCESSORY TYPES &

INTERIOR ELEVATIONS

WINDOW TAG, SEE

WINDOW SCHEDULE

1. ARCHITECTURAL DATUM = 100'-0". THE

ARCHITECTURAL DATUM IS INDEPENDENT OF

ELEVATIONS SHOWN ON THE CIVIL DRAWINGS.

SEE CIVIL DRAWINGS FOR CORRESPONDING

DATUM IN HEIGHT ABOVE SEA LEVEL.

2. ALL DIMENSIONS AT NEW WALLS ARE TO

OUTSIDE FACE OF STUD, FACE OF CONCRETE,

FACE OF MASONRY, OR CENTER OF OPENING,

U.N.O. AT EXISTING WALLS DIMENSIONS ARE

TO FINISH FACE OF WALL.

3. DO NOT SCALE DRAWINGS. CONTACT

ARCHITECT FOR ANY DISCREPANCY PRIOR TO

COMMENCING WITH ANY WORK.

4. REFER TO DIMENSION PLANS FOR GENERAL

PARTITION NOTES & PARTITION TYPES.

5. VERIFY FIELD CONDITIONS PRIOR TO

COMMENCEMENT OF EACH PORTION OF THE

WORK. NOTIFY ARCHITECT OF DISCREPANCIES.

6. ALL LUMBER IN DIRECT CONTACT WITH

CONCRETE SHALL BE PRESSURE TREATED

INCLUDING ALL SILL PLATES FOR WOOD STUD

WALLS.

7. REVIEW PRIOR TO INSTALLATION, ANY

CONFLICT OF ENGINEERING TRADE DEVICES

(I.E. FIRE ALARM STROBES) WITH

ARCHITECTURAL DETAILS AND BRING THOSE

DISCREPANCIES TO THE ARCHITECT FOR

REVIEW.

8. PROVIDE BLOCKING FOR MILLWORK,

MECHANICAL FIXTURES, PLUMBING FIXTURES

AND OTHER ITEMS IDENTIFIED IN THE

CONSTRUCTION DOCUMENTS.

9. COORDINATE MISC. STEEL REQUIREMENTS FOR

MOUNTING / HANGING OWNER SUPPLIED

EQUIPMENT.

GENERAL PLAN NOTES

X

1t

EXISTING DOOR

NEW DOOR

A301

A301

A301

A301

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room

Room 23A

Room

Room

Room

A321

A321

A322

A302

A302

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

ISSUED FOR

CONSTRUCTION

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

BI

M

VA

M C

N H

K itc he n/

V

AM

C K

IT

C

H

EN

_j s@ w ar re ns tre et

.c oo p.

rv t 6/

/2

2:

:3

PM

A111

BASEMENT PLAN

WARRENSTREET ARCHITECTS, INC.

27 WARREN STREET

CONCORD, NH 03301-4049

(603) 225-0640

JONATHAN SMITH

BUILDING 5 UTILITIES

VAMC NORTHAMPTON

VA241-16-C-0124

5/4/2020

1/8" = 1'-0"A111

1 BASEMENT FLOOR PLAN

Revisions: Date:

https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215901 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215901 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215935 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215935 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215935 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215935 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215920 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215920 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215904 VHANHMMenarN Callout

JCI CONTROL BOX LOCATION

VHANHMMenarN Callout Approximate Location of Glycol Make-Up Unit

VHANHMMenarN Oval

VHANHMMenarN Callout Supply and Discharge connections approximate location

VHANHMMenarN Oval

VHANHMMenarN Oval

H W

S

HWS HWS HWS HWS HWS HWS HWS HWS HWS HWS HWS HWS

H W

S

H W

R

HWR HWR HWR HWR HWR HWR HWR HWR HWR HWR HWR HWR

H W

R

H W

R

H W

R

H W

S

H W

S

P C R

P C R

P C R

H W

S H

W S

H W

S

H W

R H

W R

H W

R

S T M

S T M

S T M

C R

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

MEP

/1

/2

:1 :4

P

M

WARRENSTREET ARCHITECTS, INC.

27 WARREN STREET

CONCORD, NH 03301-4049

(603) 225-0640

JONATHAN SMITH

BUILDING 5 UTILITIES

VAMC NORTHAMPTON

VA241-16-C-0124

Revisions: Date:

Loureiro Engineering Associates, Inc.

100 Northwest Drive

Plainville, Connecticut 06062

Phone: 860-747-6181 / Fax: 860-747-8822

An Employee Owned Company email : info@loureiro.com

Comm No. 91WN601

Loureiro Engineering · Construction · EH&S · Energy

Waste · Facility Services· Laboratory

ISSUED FOR

CONSTRUCTION

5/4/2020

FULLY SPRINKLERED

REPLACE (8 VIF) EXISTING 10"Ø CEILING

DIFFUSER, 750CFM EA.

1/8"=1'-0"

PART PLAN - NEW WORK

REPLACE (18 VIF) EXISTING 10"Ø CEILING

DIFFUSER, 750CFM EA.

1/8"=1'-0"

PART BASEMENT MECHANICAL PLAN

CONNECT STEAM & PCR TO

BASEMENT PIPING.

4"Ø HWS&R UP THROUGH FLOOR TO CLOSET

ABOVE. REFER TO PART PLAN 1 THIS SHEET

FOR CONTINUATION.

NEW STEAM TO HW CONVERTER

CV-1. SEE SCHEMATIC DETAIL.

CRU-1

NTS

HOT WATER PIPING SCHEMATIC

H-103GAL MAK

PART PLANS - NEW WORK, BASEMENT

MECH PLAN AND PIPING SCHEMATIC

NOTES:

1. DUCTWORK, STEAM & CONDENSATE PIPE ROUTING SHOWN

IS SCHEMATIC IN NATURE. CONTRACTOR TO FIELD VERIFY

EXISTING CONDITIONS PRIOR TO THE START OF WORK.

2. CONTRACTOR TO COORDINATE WITH OTHER TRADES PRIOR

TO THE START OF WORK.

HWS&R UP THROUGH ROOF TO UNIT,

REFER TO SCHEMATIC ON THIS SHEET

AND ROOF PART PLAN ON H-102 FOR

CONTINUATION (TYP)

ROUTE INSULATED HWS&R PIPING IN

CEILING SPACE (TYP)

4" HWS&R PIPING ROUTED UP FROM

BASEMENT INTO CHASE AND UP INTO

CEILING SPACE.

HWP-1

"STM

1"PCR

3" HWS&R

" HWS&R

" HWS&R

MAU-1

RTU-1

MAU-2

RTU-2

" HWS&R

" HWS&R1

" HWS&R

4" HWS&R

CV-1

CRU-1

STEAM TO HW CONVERTER

"CR

"CR

EXISTING 1" CONDENSATE

RETURN HEADER.

1"PCR

EXISTING STEAM MAIN.

CONNECT NEW 2

" STEAM

TO EXISTING STEAM MAIN.

0-60PSIG

3" HWS&R

HWP-1

CIRCULATING PUMP

190GPM @ 30 FT HD.

EXIST STM MAIN

EXIST CR MAIN

0-60PSIG

30 TO

200° F

30 TO

200° F

HEAT EXCHANGER SCHEDULE

PASSES

NUMBER

CV-1 30%PG

MEDIA

GPM

190 10

PSI

HOT SIDE (STM)

<1psi

COLD SIDE (30% PG)

EWT

160°F

LWT

180°F 1940

#/HR

P

LWT

P

(MBH HR)

CAPACITY

NO.

REMARKS

TYPE

TUBE

NOTE:

SEE NOTE #1

MANU/MODEL

1) MANU/MODEL LISTED ARE ONLY USED AS THE BASIS FOR DESIGN. REFER TO SPECIFICATIONS FOR LIST OF ACCEPTABLE MANU/MODELS.

TACO E16208-S

PUMP SCHEDULE

NUMBER

FLOW

(GFM)

RPM TYPE

REMARKS

TDH

(FT)

ELEC

HWP-1 190 1,750 INLINE

208V/3PH

MOTOR

(HP)

MEDIA

30% PG 52

HEAD (FT)

SHUT-OFF

MANU/MODEL

TACO SKV3007-1760-3

NOTE 1 & 2

NOTE:

1) MANU/MODEL LISTED ARE ONLY USED AS THE BASIS FOR DESIGN. REFER TO SPECIFICATIONS FOR LIST OF ACCEPTABLE MANU/MODELS.

2) PROVIDE PUMP WITH VFD, NON-OVERLOADING MOTOR, BACKNET INTERFACE AND DISCONNECT SWITCH.

TRANSITION AND CONNECT EXISTING R/A

DUCTWORK TO NEW DROPS FROM

PENTHOUSE ABOVE.

TRANSITION AND CONNECT EXISTING

S/A DUCTWORK TO NEW DROPS FROM

PENTHOUSE ABOVE.

TRANSITION AND CONNECT EXISTING S/A

DUCTWORK TO NEW O/A DROPS FROM

PENTHOUSE ABOVE.

EXIST EXHAUST DUCT UP TO

PENTHOUSE

AI HW-DP HOT WATER DIFFERENTIAL PRESSURE 0-10VDC

AO HX1V1-O HEAT EXCHANGER 1 VALVE 1 OUTPUT 0-10VDC

AO HX1V21-O HEAT EXCHANGER 1 VALVE 2 OUTPUT 0-10VDC

BO PHWP1-C PRIMARY HW PUMP 1 COMMAND 24VAC MAINTAINED

AO PHWP1-O PRIMARY HW PUMP 1 OUTPUT 0-10VDC

BI PHWP1-S PRIMARY HW PUMP 1 STATUS DRY CONTACT MAINTAINED

BO PHWP2-C PRIMARY HW PUMP 2 COMMAND 24VAC MAINTAINED

AO PHWP2-O PRIMARY HW PUMP 2 OUTPUT 0-10VDC

BI PHWP2-S PRIMARY HW PUMP 2 STATUS DRY CONTACT MAINTAINED

AI PHWR-T PRIMARY HW RETURN TEMPERATURE NICKEL 1K RTD

AI PHWS-T PRIMARY HW SUPPLY TEMPERATURE NICKEL 1K RTD

POINTS SCHEDULE

NAME

SIGNAL

SYMBOL DESCRIPTION

HOT WATER SUPPLY SEQUENCE OF OPERATION:

SYSTEM ENABLE:

THE HEATING SYSTEM WILL AUTOMATICALLY START WHEN THE OUTSIDE AIR TEMPERATURE (OA-T) FALLS BELOW THE SYSTEM ENABLE SETPOINT (HTGOATLOCKOUT-SP) WHILE THE SYSTEM ENABLE (SYSTEM-EN) IS "ON". WHEN THE OUTSIDE AIR TEMPERATURE (OA-T) RISES ABOVE THIS SETPOINT (HTGOATLOCKOUT-SP) OR THE SYSTEM ENABLE (SYSTEM-EN) IS "OFF", THE HEATING SYSTEM WILL BE

DISABLED.

HEAT EXCHANGER CONTROL:

THIS SYSTEM CONSISTS OF ONE STEAM HEAT EXCHANGER. TWO SEQUENCED STEAM INLET VALVES (HXXV1-O, HXXV2-O) WILL MODULATE IN SEQUENCE TO MAINTAIN THE DESIRED HOT WATER SUPPLY TEMPERATURE (PHWS-T) TO SETPOINT (HW-SP) AS RESET BY

THE OUTDOOR AIR TEMPERATURE (OA-T).

HOT WATER PUMP CONTROL:

WHEN ENABLED, A PUMP (PHWPX-C) FOR EACH OPERATING HEAT EXCHANGER WILL BE STARTED. WHEN AN ADDITIONAL PUMP IS REQUIRED, THE PUMP WITH THE LOWEST RUNTIME TOTAL SHALL BE ENABLED TO RUN. IF THE PUMP STATUS (PHWPX-S) DOES NOT MATCH THE COMMAND (PHWPX-C), AN ALARM WILL BE GENERATED AND THE PUMP WILL BE STOPPED. UPON LOSS OF STATUS (PHWPX-S), THE PUMP (PHWPX-C) WILL RESTART AFTER THE SYSTEM RESET (SYS-RESET) IS MANUALLY ACTIVATED.

PRIMARY LOOP PRESSURE CONTROL:

WHEN A PUMP (PHWPX-S) STATUS IS VERIFIED, THE PUMP (PHWPX-O) WILL MODULATED TO MAINTAIN THE SYSTEM DIFFERENTIAL

PRESSURE (HW-DP) OF THE SYSTEM.

ADDITIONAL POINTS MONITORED BY THE FMS:

· PRIMARY HW RETURN TEMPERATURE (PHWR-T)

HX1V2-O

2/3

NC

STEAM

NC

HX1V1-O

1/3

COND

CV-1

HWS

HWR

HL

HW-DP

PHWP1-C

PHWP1-S

PHWP2-C

PHWP2-S

PHWS-T

PHWP2

PHWP1

PHWP2-O

PHWP2 VFD

PHWP1-O

PHWP1 VFD

PHWR-T

A

A A

A

AIR VENTS AT HIGH POINTS.

INSTALL DRAIN VALVE AT

LOW POINT IN SYSTEM.

NOTE:

1. PROVIDE AIR VENTS AT HIGH POINTS AND DRAIN VALVES AT LOW POINTS.

AS

A

BSF

BYPASS FILTERED SHOT

FEEDER W/3/4" TAPS

" CW MAKEUP

BACKFLOW PREVENTER

PRESSURE REGULATING VALVE

BALANCE

VALVE

STEAM TRAP (TYP)

STRAINER W/BLOWDOWN

(TYP)

CONTROL VALVE

AUTOMATIC AIR VENT

AIR STRAINER

EXPANSION TANK

EXIST DUCT TO REMAIN,

REFER TO SHEET H-100.

PACKAGED CONDENSATE

PUMP SYSTEM

BALANCE

VALVE (TYP.)

NORTH

NORTH

HWP-2 190 1,750 INLINE

208V/3PH

30 330% PG 52 TACO SKV3007-1760-3

NOTE 1 & 2

HWP-2

CIRCULATING PUMP

190GPM @ 30 FT HD.

AutoCAD SHX Text G:\AUTOCAD\PROJECTS\91WN601 VA BLDG 5 RENO\DWGS\91WN601 MECH.DWG Tab: H3 Saved: 5/11/2020 4:41 PM Plotted: 5/26/2020 10:29 AM https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215927 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215898 https://app.procore.com/1597978/project/drawing_areas/1200400/drawing_log/159215898

2. PROJECT SCOPE OF WORK
Work shall consist of, installation and testing of Glycol Make-Up Unit in room 14 of the basement of Building 5.
This includes the following task:
a) Furnishing and install Glycol feeder equipment and materials including all plumbing, electrical, and data requirements.
b) All plumbing from tank to existing supply and discharge to have unions and valves for future maintenance. Insulate plumbing pipe as needed.
c) Size tank to 55 gallons minimum. Glycol mixture to match existing mixture (see attached mixture submittal for reference).
d) Connect Glycol Feeder Tank to VA METASYS to alert for system low level alarm. (Existing JCI control box located in room 14 on west wall). Refer to COR for location.
e) Locate Tank and pump in eastwest corner of room 14. (Do not block access doors, existing valves, or door to steam tunnel. Refer to COR for placement of Gylcol Feeder.