This is Addendum No. 1 to the original contract documents for the Gardner School Chiller Replacement project, issued by the Lansing School District in collaboration with Matrix Consulting Engineers on May 19, 2026. The addendum modifies and clarifies electrical specifications for the chiller replacement work at Gardner International Magnet School located at 333 Dahlia Drive, Lansing, Michigan. The project involves mechanical room modifications including demolition of existing equipment and installation of new chillers, with significant electrical work encompassing panel updates, circuit reconfiguration, and equipment reconnection. The job number is 260150.00, and the addendum applies to all bidders who received the original plans and specifications. Bidders are required to acknowledge receipt of this addendum on the proposal form.
The electrical modifications detailed in Addendum No. 1 span four sheets (E-300, E-500, E-600, and E-601), each re-issued to reflect specific changes including added existing panel information, revised panel schedules, relocated equipment (specifically the P-4 combination starter), and updated circuit tags for new equipment (EF-1, EF-2, P-HC-1). The addendum specifies base bid requirements and alternative bid options for conduit and wire management, such as reusing existing conduit versus providing new conduit and wire throughout. Additional requirements include disconnecting and removing existing capacitor equipment for chiller removal with reconnection to the new chiller, field verification of existing circuits by the contractor, and continuous operation of exhaust fans controlled by a refrigerant monitor and building automation system. All incidental items necessary to complete these modifications are to be included by bidders in their proposals, even if not explicitly listed.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| SO-1858 Gardner School Chiller Replacement.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
544 Cherbourg Drive, LANSING, MI 48917
PHONE: (517) 487-2511
FAX: (517) 487-2544
ADDENDUM NO. 1
LSD Gardner Elementary Chiller Replacement
Date:05/19/2026 Job Number: 260150.00
OWNER: ENGINEER:
Lansing School District Matrix Consulting Engineers 333 Dahlia Dr 544 Cherbourg Drive Lansing, MI 48911 Lansing, MI 48917
This Addendum is issued for the purpose of modifying and/or clarifying the original Contract Documents and shall take precedence over them.
All work included herein shall be in accordance with the original drawings and specifications except as specifically noted herein. All incidental items required to provide the following modifications shall be included even though not specifically described.
This addendum is being sent to all bidders receiving plans and specifications. Receipt of this Addendum shall be noted on the Proposal Form in the appropriate location.
Electrical
1. Sheet E-300 (Sheet Re-issued):
a. Added existing panel.
2. Sheet E-500 (Sheet Re-issued):
a. Added existing panel.
b. Removed keynote.
c. Added circuit tags to equipment (EF-1, EF-2, P-HC-1).
d. Revised location of P-4 combination starter.
3. Sheet E-600 (Sheet Re-issued):
a. Added existing panel schedule.
4. Sheet E-601 (Sheet Re-issued):
a. Added revised panel schedule.
END OF ADDENDUM
X-CH-2
X-P X-P
X-P X-P
GENERATOR
X-B X-B
X-DWH
X-COMPRESSOR
X-P-5
X-DDC CONTROL PANELS
X-P-1 VFD X-P-2 VFD
X-P-4
X-CH-1
X-P-3
X-P-6
X-P-1
X-P-2
1 1
1 2
1 1
2 2 1 1 1
J CONTROL
PANEL
35KVAR
J
9KVAR4KVAR
"EMPD-01"
PNL "PP-02"
PNL "PP-4"
TS
FACP
PNL "EXCP-01"
T7
PNL "XFAP-01"
65KVAR
J
J CONTROL
PANEL
1 2
TU
PNL "EBCP-01"
EXISTING EQUIPMENT TO REMAIN.
BASE BID:
DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT
TO REMAIN FOR CONNECTION TO NEW EQUIPMENT. REMOVE ASSOCIATED
WIRE BACK TO SOURCE.
ADD ALTERNATE:
DISCONNECT AND REMOVE EXISTING EQUIPMENT. ASSOCIATED CONDUIT
TO BE CAPPED ABOVE FINISHED FLOOR. REMOVE ASSOCIATED WIRE BACK
TO SOURCE.
BASE BID:
EXISTING EQUIPMENT TO REMAIN. ASSOCIATED CONDUIT TO REMAIN FOR
CONNECTION TO NEW EQUIPMENT. REMOVE ASSOCIATED WIRE BACK TO
SOURCE.
ADD ALTERNATE:
EXISTING EQUIPMENT TO REMAIN. ASSOCIATED CONDUIT TO BE
TERMINATED TO PULL BOX. REMOVE ASSOCIATED WIRE BACK TO SOURCE.
DISCONNECT AND REMOVE EXISTING CAPACITOR FOR REMOVAL OF
CHILLER. RE-CONNECT CAPACITOR TO NEW CHILLER.
DEMOLITION NOTES
M A
T R
I X
N MECHANICAL ROOM PLAN - DEMOLITION
SCALE: 1/4" = 1'-0"
0 1 5 10
AutoCAD SHX Text
PROJECT NUMBER
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
SHEET DESCRIPTION
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CONSULTING ENGINEERS, INC
AutoCAD SHX Text
PHONE: (517) 487-2511
AutoCAD SHX Text Lansing, MI 48917
AutoCAD SHX Text 544 Cherbourg Drive
AutoCAD SHX Text administrator@matrixceinc.com
AutoCAD SHX Text 260150.00
AutoCAD SHX Text 05/18/2026
AutoCAD SHX Text
GARDNER INTERNATIONAL MAGNET SCHOOL
AutoCAD SHX Text
CHILLER REPLACEMENT
AutoCAD SHX Text
333 DAHLIA DR, LANSING, MI
AutoCAD SHX Text
ADDENDUM #1
AutoCAD SHX Text 05/19/2026
AutoCAD SHX Text
100% BID SET
AutoCAD SHX Text 05/18/2026
AutoCAD SHX Text Matrix Project No. 260150.00
AutoCAD SHX Text E-300
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
ROOM PLAN
AutoCAD SHX Text
DEMOLITION
AutoCAD SHX Text
BTT
AutoCAD SHX Text
JFS
X-CH-2
X-P X-P
X-P X-P
X-B X-B
X-DWH
X-COMPRESSOR
X-P-5
X-DDC CONTROL PANELS
P-2 VFD
P-1
480V-3Ø, 50HP
GENERATOR
T
J
4KVAR
EXIST.
"EMPD-01"
EXIST.
PNL "PP-02"
EXIST.
PNL "PP-4"
TS
FACP
EXIST.
PNL "EXCP-01"
T7
EXIST.
PNL "XFAP-01"
65KVAR
J
J CONTROL
PANEL
P-2
480V-3Ø, 50HPP-6
480V-3Ø, 10HP
P-3
480V-3Ø, 10HP
CH-1
480V-3Ø, 272.9A
J CONTROL
PANEL
35KVAR
EX
EX
EX
EX
EX
EX
EX
EX
EX EX
EX
VFD
VFD
P-1 VFD
(3) #10
(1) #10 GND
3/4" CND
PP-02-1PP-02-3 (3) #4
(1) #8 GND
1-1/4" CND(3) #4
(1) #8 GND
1-1/4" CND
(3) #10
(1) #10 GND
3/4" CND PP-02-5
PP-02-7
PP-02-9
EMPD-01-10
(4) #350KCMIL
(1) #4 GND
3-1/2" CND
P-6 COMBINATION STARTER
P-4 COMBINATION STARTER
P-3 COMBINATION STARTER
EF-1
120V-1Ø, 6.6 FLA
P-HC-1
120V-1Ø, 1/6HP
EF-2
120V-1Ø, 16.0 FLA
EX
EX EX
EX
U
EBCP-01-3
EBCP-01-18
EBCP-01-17
PNL "EBCP-01"
1 (3) #10
(1) #10 GND
3/4" CND
P-4
480V-3Ø, 5HP
ELECTRICAL KEY NOTES
BASE BID:
REUSE EXISTING CONDUIT FOR CONNECTION TO NEW EQUIPMENT. PROVIDE
AND INSTALL NEW WIRE.
ADD ALTERNATE:
PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR CONNECTION TO NEW
EQUIPMENT.
BASE BID:
REUSE EXISTING CONDUIT TO PULL BOX FOR CONNECTION TO NEW
EQUIPMENT. PROVIDE AND INSTALL NEW CONDUIT FROM PULL BOX TO
CHILLER. PROVIDE AND INSTALL NEW WIRE IN ENTIRETY.
ADD ALTERNATE:
PROVIDE AND INSTALL NEW CONDUIT AND WIRE FOR CONNECTION TO NEW
EQUIPMENT.
RE-CONNECT CAPACITOR TO NEW CHILLER.
EXISTING CIRCUIT IS UNKNOWN, NEW CIRCUIT NUMBER IS SHOWN FOR
LOAD PURPOSES. CONTRACTOR SHALL FIELD VERIFY EXISTING CIRCUIT,
FOR POTENTIAL RE-CONNECTION.
EXHAUST FAN TO RUN CONTINUOUSLY.
EXHAUST FAN SHALL BE CONTROLLED BY REFRIGERANT MONITOR. ROUTE
CIRCUIT THROUGH RIB RELAY CONTROLLED BY BAS SYSTEM. PROVIDE ALL
WIRE AND CONDUIT FOR A COMPLETE INSTALLATION.
M A
T R
I X
N MECHANICAL ROOM PLAN - POWER
SCALE: 1/4" = 1'-0"
0 1 5 10
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text S
AutoCAD SHX Text
PROJECT NUMBER
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
SHEET DESCRIPTION
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CONSULTING ENGINEERS, INC
AutoCAD SHX Text
PHONE: (517) 487-2511
AutoCAD SHX Text Lansing, MI 48917
AutoCAD SHX Text 544 Cherbourg Drive
AutoCAD SHX Text administrator@matrixceinc.com
AutoCAD SHX Text 260150.00
AutoCAD SHX Text 05/18/2026
AutoCAD SHX Text
GARDNER INTERNATIONAL MAGNET SCHOOL
AutoCAD SHX Text
CHILLER REPLACEMENT
AutoCAD SHX Text
333 DAHLIA DR, LANSING, MI
AutoCAD SHX Text
ADDENDUM #1
AutoCAD SHX Text 05/19/2026
AutoCAD SHX Text
100% BID SET
AutoCAD SHX Text 05/18/2026
AutoCAD SHX Text Matrix Project No. 260150.00
AutoCAD SHX Text E-500
AutoCAD SHX Text
MECHANICAL
AutoCAD SHX Text
ROOM PLAN
AutoCAD SHX Text
POWER
AutoCAD SHX Text
BTT
GROUND BUS
PARTIAL RISER DIAGRAM - EXISTING
SCALE: N.T.S.
EXISTING "EMPD-01"
277/480V, 3Ø, 4W 3000A
3000A-3P
MAINUTILITY CO.
1000KVA M
UTILITY CO.
FROM UTILITY
0A
-3 P
PANEL
EXISTING
"PP-5"
277/480V 3Ø, 4W
300A, MLO
0A
-3 P
5A
-3 P
T
0A
-3 P
PANEL
EXISTING
"PP-2"
277/480V 3Ø, 4W
200A, MLO
0A
-3 P
PANEL
EXISTING
"PP-1"
277/480V 3Ø, 4W
200A, MLO
0A
-3 P
T
0A
-3 P
PANEL
EXISTING
"PP-4"
277/480V 3Ø, 3W
400A, MLO
0A
-3 P
PANEL
EXISTING
"PP-3"
277/480V 3Ø, 4W
600A, MLO
0A
-3 P
0A
-3 P
GROUND BUS
EXISTING "PP-02"
277/480V, 3Ø, 3W 400A
0A
-3 P
0A
-3 P
A-
3P
A-
3P
SPARE
A-
3P
SPARE
A-
3P
SPARE
0A
-3 P
0A
-3 P
A-
3P
SPARE
A-
3P
SPARE
A-
3P
SPARE
A-
3P
SPARE
G
KW
GENERATOR
TRANSFER SW.
30A/3P
3PH 4W
FUSED
KVA
T
PANEL
EXISTING
"EXCP-01"
120/208V 3Ø, 4W
100A, MLO
AUTOMATIC
30A
NORMAL
SOURCE
P-2
WEST COOLING
TOWER PUMP P-1 P-5 P-6
WEST
CHILLER-2
EAST
CHILLER-16
DISCONNECT AND REMOVE EXISTING EQUIPMENT. MODIFY ASSOCIATED
CONDUIT AND WIRE FOR NEW EQUIPMENT.
REMOVE EXISTING BREAKER, AND TURN OVER TO OWNER.
DEMOLITION NOTES
1 1 1
2 2 2
EXEX
EX
M A
T R
I X
AutoCAD SHX Text
PROJECT NUMBER
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
SHEET DESCRIPTION
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CONSULTING ENGINEERS, INC
AutoCAD SHX Text
PHONE: (517) 487-2511
AutoCAD SHX Text Lansing, MI 48917
AutoCAD SHX Text 544 Cherbourg Drive
AutoCAD SHX Text administrator@matrixceinc.com
AutoCAD SHX Text 260150.00
AutoCAD SHX Text 05/18/2026
AutoCAD SHX Text
GARDNER INTERNATIONAL MAGNET SCHOOL
AutoCAD SHX Text
CHILLER REPLACEMENT
AutoCAD SHX Text
333 DAHLIA DR, LANSING, MI
AutoCAD SHX Text
ADDENDUM #1
AutoCAD SHX Text 05/19/2026
AutoCAD SHX Text
100% BID SET
AutoCAD SHX Text 05/18/2026
AutoCAD SHX Text Matrix Project No. 260150.00
AutoCAD SHX Text E-600
AutoCAD SHX Text
EXISTING RISER
AutoCAD SHX Text
DIAGRAM AND
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
SCHEDULES
AutoCAD SHX Text
BTT
GROUND BUS
PARTIAL RISER DIAGRAM - REVISED
SCALE: N.T.S.
EXISTING "EMPD-01"
277/480V, 3Ø, 4W 3000A
3000A-3P
MAINUTILITY CO.
1000KVA M
UTILITY CO.
FROM UTILITY
0A
-3 P
PANEL
EXISTING
"PP-5"
277/480V 3Ø, 4W
300A, MLO
0A
-3 P
5A
-3 P
T
0A
-3 P
PANEL
EXISTING
"PP-2"
277/480V 3Ø, 4W
200A, MLO
0A
-3 P
PANEL
EXISTING
"PP-1"
277/480V 3Ø, 4W
200A, MLO
0A
-3 P
T
0A
-3 P
PANEL
EXISTING
"PP-4"
277/480V 3Ø, 3W
400A, MLO
0A
-3 P
PANEL
EXISTING
"PP-3"
277/480V 3Ø, 4W
600A, MLO
0A
-3 P
0A
-3 P
GROUND BUS
EXISTING "PP-02"
277/480V, 3Ø, 3W 400A
0A
-3 P
0A
-3 P
A-
3P
A-
3P
A-
3P
A-
3P
SPARE
0A
-3 P
0A
-3 P
A-
3P
SPARE
A-
3P
SPARE
A-
3P
SPARE
A-
3P
SPARE
G
KW
GENERATOR
TRANSFER SW.
30A/3P
3PH 4W
FUSED
KVA
T
PANEL
EXISTING
"EXCP-01"
120/208V 3Ø, 4W
100A, MLO
AUTOMATIC
30A
NORMAL
SOURCE
P-2
WEST COOLING
TOWER PUMP
P-1
P-5
P-6
WEST
CHILLER-2
EAST
CHILLER-16
VFD VFD
ELECTRICAL KEY NOTES
CONTRACTOR SHALL PROVIDE AND INSTALL NEW BREAKER, TO MATCH
EXISTING TYPE.
1 1 1
P-4 P-3
EXEX
EX
M A
T R
I X
AutoCAD SHX Text
PROJECT NUMBER
AutoCAD SHX Text
SHEET NUMBER
AutoCAD SHX Text
SHEET DESCRIPTION
AutoCAD SHX Text
DATE
AutoCAD SHX Text
PROJECT
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
APPROVED
AutoCAD SHX Text
DRAWN
AutoCAD SHX Text
CONSULTING ENGINEERS, INC
AutoCAD SHX Text
PHONE: (517) 487-2511
AutoCAD SHX Text Lansing, MI 48917
AutoCAD SHX Text 544 Cherbourg Drive
AutoCAD SHX Text administrator@matrixceinc.com
AutoCAD SHX Text 260150.00
AutoCAD SHX Text 05/18/2026
AutoCAD SHX Text
GARDNER INTERNATIONAL MAGNET SCHOOL
AutoCAD SHX Text
CHILLER REPLACEMENT
AutoCAD SHX Text
333 DAHLIA DR, LANSING, MI
AutoCAD SHX Text
ADDENDUM #1
AutoCAD SHX Text 05/19/2026
AutoCAD SHX Text
100% BID SET
AutoCAD SHX Text 05/18/2026
AutoCAD SHX Text Matrix Project No. 260150.00
AutoCAD SHX Text E-601
AutoCAD SHX Text
REVISED RISER
AutoCAD SHX Text
DIAGRAM AND
AutoCAD SHX Text
PANEL
AutoCAD SHX Text
SCHEDULES
AutoCAD SHX Text
BTT
| 260150.00 - LSD Gardner Elementary Chiller Replacement - Addendum #1 - Write-Up.pdf |
| 260150.00 - LSD Gardner Elementary Chiller Replacement - Addendum #1 - Electrical.pdf |
| Sheets and Views |
| E300-26015000-24x36 |
| E500-26015000-24x36 |
| E600-26015000-24x36 |
| E601-26015000-24x36 |
File details come from the government source that posted it. Updated .