SATPC0039131 Tab 04 4 SOW.pdf

PDF 180 KB Posted

Attached to
High Frequency Partial Discharge Portable detection system Federal contract opportunity
Solicitation number
80NSSC25909768Q
Issued by
National Aeronautics and Space Administration Shared Services Center

About this file

This document contains specifications for a high-frequency partial discharge detection system and software designed for advanced electrical equipment monitoring and maintenance. The system features a module with 4 simultaneous input channels (expandable to 8 or 12 via multiplexer), offering a 250 MS/s sampling rate, 0.01-100 MHz bandwidth, and selectable amplification up to 50 dB. Key capabilities include continuous monitoring with early warning signal detection, threshold-based alarms, and overall device health assessment.

The system supports high and low-resolution data transfer, with transfer rates up to 50,000 pulses per second and 400 Mbps, utilizing Ethernet copper or fiber communication (100/1000 BASE-T). The accompanying sensor, identified by model HSENS-H0-XX-10-00, comes in HFCT-5 or HFCT-9 variants and includes a 10-foot cable. The software provides comprehensive functionality for discharge detection, data collection, analysis, pulse shape classification, and predictive maintenance, enabling detailed condition monitoring of electrical equipment.

View the file

Other files for this federal contract opportunity

Other files attached to High Frequency Partial Discharge Portable detection system, newest first.
File Type Posted
SATPC0039131 Tab 07 Capability Statement Commercial.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Specifications Summary High frequency partial discharge detection system and software for discharge detection, data collection, analysis and data processing, with pulse shape classification for PD source identification, high-frequency detection, condition monitoring/predictive maintenance. This includes software for data capture, storage and analysis. Additionally, the systems provides early warnings and alarms when inputted thresholds are breached providing an overall health assessment of a DUT.

Specifications

MODULE

Input Channels:

• 4 simultaneous channels, 8 & 12 channel options available with multiplexer

• Sampling Rate: 250 MS/s

• Bandwidth: 0.01-100 MHz

• Amplification: Selectable up to 50 dB

• Filtering: Configurable band pass filters

• Continuous monitoring detection with:

o Capable detecting early warning signal o Signal/Alarms when threshold inputs thresholds are breached, o DUT overall health assessment

Data Transfer:

• High Resolution (Pulses data on simultaneous channels, 10,000 Pps for 4 simultaneous channels

• Low Resolution (Pulse amplitude on simultaneous channels)

• Transfer Rate: 50,000 Pps for 4 simultaneous channels, 400 Mbps (depending on operating system and connection)

Communication

• Type Ethernet Copper or Fiber (100/1000 BASE-T)

• Connector RJ45 or LC Multi-mode

SENSOR

• HSENS-H0-XX-10-00

• Model Number HFCT-5 or HFCT-9

• 10 foot cable length

Summary
Specifications

File details come from the government source that posted it. Updated .