SATPC0039131 Tab 04 4 SOW.pdf
PDF 180 KB Posted
- Attached to
- High Frequency Partial Discharge Portable detection system Federal contract opportunity
- Solicitation number
- 80NSSC25909768Q
About this file
This document contains specifications for a high-frequency partial discharge detection system and software designed for advanced electrical equipment monitoring and maintenance. The system features a module with 4 simultaneous input channels (expandable to 8 or 12 via multiplexer), offering a 250 MS/s sampling rate, 0.01-100 MHz bandwidth, and selectable amplification up to 50 dB. Key capabilities include continuous monitoring with early warning signal detection, threshold-based alarms, and overall device health assessment.
The system supports high and low-resolution data transfer, with transfer rates up to 50,000 pulses per second and 400 Mbps, utilizing Ethernet copper or fiber communication (100/1000 BASE-T). The accompanying sensor, identified by model HSENS-H0-XX-10-00, comes in HFCT-5 or HFCT-9 variants and includes a 10-foot cable. The software provides comprehensive functionality for discharge detection, data collection, analysis, pulse shape classification, and predictive maintenance, enabling detailed condition monitoring of electrical equipment.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SATPC0039131 Tab 07 Capability Statement Commercial.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Specifications Summary High frequency partial discharge detection system and software for discharge detection, data collection, analysis and data processing, with pulse shape classification for PD source identification, high-frequency detection, condition monitoring/predictive maintenance. This includes software for data capture, storage and analysis. Additionally, the systems provides early warnings and alarms when inputted thresholds are breached providing an overall health assessment of a DUT.
Specifications
MODULE
Input Channels:
• 4 simultaneous channels, 8 & 12 channel options available with multiplexer
• Sampling Rate: 250 MS/s
• Bandwidth: 0.01-100 MHz
• Amplification: Selectable up to 50 dB
• Filtering: Configurable band pass filters
• Continuous monitoring detection with:
o Capable detecting early warning signal o Signal/Alarms when threshold inputs thresholds are breached, o DUT overall health assessment
Data Transfer:
• High Resolution (Pulses data on simultaneous channels, 10,000 Pps for 4 simultaneous channels
• Low Resolution (Pulse amplitude on simultaneous channels)
• Transfer Rate: 50,000 Pps for 4 simultaneous channels, 400 Mbps (depending on operating system and connection)
Communication
• Type Ethernet Copper or Fiber (100/1000 BASE-T)
• Connector RJ45 or LC Multi-mode
SENSOR
• HSENS-H0-XX-10-00
• Model Number HFCT-5 or HFCT-9
• 10 foot cable length
| Summary |
| Specifications |
File details come from the government source that posted it. Updated .