This document is a Statement of Work (SOW) detailing specifications for four types of TransData units dated January 24, 2024. The SOW outlines technical requirements for current transducers (Item 1), voltage transducers (Item 2), wattage 2-element transducers (Item 3), and wattage 2.5-element transducers (Item 4).

All units share common specifications including temperature range (-20°C to 70°C), frequency range (50-70 Hz), full scale input (5 Amps), 4-20mA DC output, response time (<400 MS), surge withstand capability (5000V Peak), and utility specified steel enclosure with standardized mounting footprint. Key differences include: Items 1 and 2 are single phase with 12 electrical elements, 0-95% operating humidity, 100-130V power supply, and ±0.2% accuracy; while Items 3 and 4 are three phase with 12-14 wiring terminals, 0-99% non-condensing humidity, 120V power supply, and ±0.1% accuracy. Items 1 and 2 require zero adjustment (±5%), while Items 3 and 4 require no zero adjustment.

View the file

Other files for this federal contract opportunity

Other files attached to 10x10 TransData unit replacements, newest first.
File Type Posted
SATPC0037521 Tab 06 RDSS..pdf PDF
SATPC0037521 Tab 07 Capability Statement SAM.gov.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

10x10 TransData units 1/24/2024

1.0 Current Transducer Specifications (Item 1):

1.1.1 Number of Electrical Elements: 12

1.1.2 Temperature Range: -20 degrees C to 70 degrees C

1.1.3 Operating Humidity: 0-95%

1.1.4 Power Supply: 100-130V, 60 Hz

1.1.5 Frequency Range: 50-70 Hz

1.1.6 Full Scale Input: 5 Amps

1.1.7 4-20mA DC output

1.1.8 Response Time to 99%: <400 MS

1.1.9 Surge Withstand Capability: 5000V Peak

1.1.10 Accuracy @ 25 degrees C +/- 5 degrees C: +/-0.2% of rated output

1.1.11 Single phase

1.1.12 Calibration Adjustment: +/-10%

1.1.13 Zero (offset) Adjustment: +/- 5%

1.1.14 Utility specified steel enclosure

1.1.15 Standardized mounting footprint

2.0 Voltage Transducer Specifications (Item 2):

2.1.1 Number of electrical elements: 12

2.1.2 Temperature Range: -20 degrees C to 70 degrees C

2.1.3 Operating Humidity: 0-95%

2.1.4 Power Supply: 100-130V, 60 Hz

2.1.5 Frequency Range: 50-70 Hz

2.1.6 Full Scale Input: 5 Amps

2.1.7 4-20mA DC output

2.1.8 Response Time to 99%: <400 MS

2.1.9 Surge Withstand Capability: 5000V Peak

2.1.10 Accuracy @ 25 degrees C +/- 5 degrees C: +/-0.2% of rated output

2.1.11 Single phase

2.1.12 Calibration Adjustment: +/-10%

2.1.13 Zero (offset) Adjustment: +/- 5%

2.1.14 Utility specified steel enclosure

2.1.15 Standardized mounting footprint

3.0 Wattage 2-Element Transducer Specifications (Item 3):

3.1.1 Number of wiring terminals: 12

3.1.2 Temperature Range: -20 deg C to 70 deg C

3.1.3 Operating Humidity: 0-99% non-condensing

3.1.4 Power Supply: 120V, 60 Hz

3.1.5 Frequency Range: 50-70 Hz

3.1.6 Full Scale Input: 5 Amps

3.1.7 4-20mA DC output

3.1.8 Response Time to 99%: <400 MS

3.1.9 Surge Withstand Capability: 5000V Peak

3.1.10 Accuracy @ 25 degrees C +/- 2 deg C: +/-0.1% of rated output

3.1.11 Three phase

3.1.12 Calibration Adjustment: +/-10%

3.1.13 Zero Adjustment: none required

3.1.14 Utility specified steel enclosure

3.1.15 Standardized mounting footprint

4.0 Wattage 2.5-Element Transducer Specifications (Item 4):

4.1.1 Number of wiring terminals: 14

4.1.2 Temperature Range: -20 deg C to 70 deg C

4.1.3 Operating Humidity: 0-99% non-condensing

4.1.4 Power Supply: 120V, 60 Hz

4.1.5 Frequency Range: 50-70 Hz

4.1.6 Full Scale Input: 5 Amps

4.1.7 4-20mA DC output

4.1.8 Response Time to 99%: <400 MS

4.1.9 Surge Withstand Capability: 5000V Peak

4.1.10 Accuracy @ 25 degrees C +/- 2 deg C: +/-0.1% of rated output

4.1.11 Three phase

4.1.12 Calibration Adjustment: +/-10%

4.1.13 Zero Adjustment: none required

4.1.14 Utility specified steel enclosure

4.1.15 Standardized mounting footprint