SALIENT CHARACTERISTICS

· Needs to be able to build up and maintain 4400 PSI for two tanks/outlets.

· Compatible with use of Diesel fuel, JP-4, JP-5, JP-8 or Jet A

· Have an N2 Purity level of 95% or Greater

· Have 2 Low pressure outlets to operate 2 separate fill stations

· Will be utilized in industrial area and may be exposed to diesel/Jet-A fuel, engine oils, hydraulic fluid, coolant/anti-freeze, various greases, and aerosol sprays.

· “Dead Man’s Switch” required in order to stop pressure generation if switch is disengaged. Switch located outside of unit (engaged while occupied/disengaged while unoccupied) is recommended.

· Must have a form of corrosion protection/resistance (e.g. paint) to prevent rusting/deterioration of parts.

· Overall size of unit shouldn’t be bigger than 13ft 4” X 6ft 4” inches to be placed on slab

· Sealed maintenance free batteries for diesel motor

· Must contain battery charge level gauge, hour meter