This document appears to be a set of salient characteristics for a Hazardous Materials (HAZMAT) storage building. The specifications include dimensions of 20-21' wide, 8' deep, and 8-9' high, with a 2-hour fire rating, 650-gallon spill containment, grated floors rated for 300 lb/sq ft, explosion-proof lighting and HVAC, secondary containment shelves, and a dry chemical fire suppression system.
The related federal contract opportunity is a solicitation from the Defense Logistics Agency (DLA) Maritime Puget Sound Naval Shipyard/TRF Bangor for HAZMAT storage units. The NAICS code is 332439 with a 600-employee size standard. Quotes must be submitted via email or fax and include completed solicitation, manufacturer, country of origin, and lead time for delivery. NIST SP 800-171 cybersecurity requirements apply, except for Commercial Off-The-Shelf (COTS) items.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SPMYM2-24-Q-1806.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Hazmat Storage Building Spec: 4134-0180 LEAD OF 11 JMLs
Hazmat storage building size: 20’ to 21’ wide, 8’ deep, 8’ to 9’ high
2 hour fire rating with a double walled construction of 12/14 gauge welded steel, Spill containment minimum of 650 gallons
Grated floors rated at 300LB PSF
Minimum 2 full opening doors with three point locks 56” wide x 82” high
R11 insulation
2 explosion proof Led lighting inside controlled by switch, mounted on upper back wall near the ceiling.
1 non explosion proof photocell light on front of unit
Explosion proof heater 12k BTU of greater with thermostat
Explosion proof air conditioner 19,500 BTU or better
10 each secondary containment shelves
UL & FM approved ABC dry chemical fire suppression system with manual pull station and alarm (steel enclosure for dry chemicals and controls)
Minimum 4 Explosion relief panels
2 way forklift pockets
Seismic tie downs
Exterior grade paint inside and out.