S01 - Attachment 01 - Drawings (Revised) (18 pages).pdf

PDF 16 MB Posted

Attached to
J061--Upgrade Motor Control Centers at BLDG One Federal contract opportunity
Solicitation number
Not on record
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8

About this file

This document provides details for a federal contract opportunity to upgrade motor control centers at Building 1 for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8. The purpose of the opportunity is to replace previously submitted Attachment 1 - Drawings (17 pages) with Attachment 1 - Drawings (Revised) (18 pages) and add a site visit sign-in sheet to contracting opportunities. Proposals are due by September 12, 2022 at 3:30 PM Eastern Time. The date for requests for information has closed, but the offer closing date for receipt of proposals remains unchanged. The project number is 573-19-615.

View the file

Other files for this federal contract opportunity

Other files attached to J061--Upgrade Motor Control Centers at BLDG One, newest first.
File Type Posted
Site Visit Sign In 573-19-615 Upgrade Motor Control Centers at Building 1.pdf PDF
SF30 Amendment 36C24822R0166 0001.pdf PDF

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

DN

ELEVATOR

PENTHOUSE

SPEMR 37-1

ELEVATOR

SPEMR 37-1

J

K

L

9 8 9 8

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

QBO: FL #29758

AKEA Design Project No. AD180-19 RAH KLL / KS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved: Project Director

VA FORM 08 - 6231

A

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 9 10

UPGRADE MOTOR CONTROL

CENTERS AT BUILDING 1

GAINESVILLE, FLORIDA

573-19-615

MARCH 23, 2022Revisions: Date:

Design, Inc.

Office of Construction and Facilities Management

ARCHITECT / ENGINEER OF RECORDCONSULTANT

BID DOCUMENTS

(FOR CONSTRUCTION)

BID DOCUMENTSELECTRICAL PLANS - 480-BED

EP102

N

FLOOR PLAN - 480-BED PENTHOUSE - NEW WORK

EXISTING & DEMOLITION PLAN - 480-BED PENTHOUSE

SHEET NOTES

SHEET KEYNOTES

KEY PLAN - BLDG 1 PENTHOUSE / ROOF

STATE OF

P R

O

FES S IO NA L ENGIN

EE

BER T A . HA FFEM

NNo. 66321 L I C E N S E

F L O R I D A

AutoCAD SHX Text

MCC-CPH3

MCC-PH3

PNL PPDQA

P-BOX

AHU-3 VFD

SHELVING RACK

EF-1

EF-2

EF-3

SIEMENS CONTROLS

PNL PPDQA

P-BOX

EF-1

AHU-3 VFD

SHELVING RACK

PNL L-CPH3

PNL H-PH3

EF-2

EF-3

SIEMENS CONTROLS

NEW MCC-CPH3

XFMR T-79, WALL MTD.

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

ENGINEER-OF-RECORD

ROBERT A. HAFFEMAN

66321

FL. P.E. NO.

SCALE:

1/4" = 1' - 0"

A. NOT USED.NOT USED.

1. EXIST HOUSEKEEPING PAD TO REMAIN. EXIST HOUSEKEEPING PAD TO REMAIN.

NTS

PROJECT AREA

Sheets and Views

EP102

2022-03-23T10:44:39-0400

Robert Haffeman

34567891011121314

G

H

M

Phone: (352) 474-6124 Fax: (352) 553-4437

BID DOCUMENTSELECTRICAL PLANS - 480-BED

ROOF TOP

EP103

KEY PLAN - BLDG 1 ROOF

480-BED ROOF/ PENTHOUSE

E-4

E-11

E-27

E-15

E-17

E-XX

E-20

E-16

E-18

E-19

E-3

E-1

E-2

AHU-3

ST-3

AF-3

AHU-3

E-13

E-14

E-12

E-25

E-21

E-22

E-24

E-23

E-26

E-5

OPEN WELL

OPEN WELL

PENTHOUSE ROOF

TOP OF 5TH FLOOR ROOF

TOP OF 5TH FLOOR ROOF

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

A. ROOFTOP PLAN DRAWING IS INCLUDED ROOFTOP PLAN DRAWING IS INCLUDED FOR REFERENCE TO EXISTING FAN LOCATIONS.

1. NOT USED. NOT USED.

3/32" = 1' - 0"

Sheets and Views

EP103

2022-03-23T10:45:20-0400

Robert Haffeman

20 19 1821

E-WING

20 19 1821

ELECTRICAL PLANS - E-WING

FLOOR PLAN - E-WING PENTHOUSE - NEW WORK

EXISTING & DEMOLITION PLAN - E-WING PENTHOUSE

Phone: (352) 474-6124 Fax: (352) 553-4437

EP104

FESS IO NA L ENGIN

FRONT

BACK

PNL PNPA

XFMR T-9

MCC-E1

MCC-N1

BACK

VFD

SIEMENS APPOGEE

HONNEYWELL PNL

HYDRAULIC CONTROLS

FEEDER P-BOX

CONTROLS

XFMR TE-2

PNL PCPA

HVAC UNIT

H-N1

PNL PNPA

XFMR T-9

HONNEYWELL PNL

HVAC UNIT

FEEDER P-BOX

EM-HA

EM-L

EM-HB

XFMR EM

HYDRAULIC CONTROLS

DOWN

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

A. NOT USED.NOT USED.

1. REMOVE EXIST. HOUSEKEEPING PAD. REMOVE EXIST. HOUSEKEEPING PAD. REFINISH CONC. FLOOR SLAB TO MATCH SURROUNDING CONDITIONS. 2. REMOVE PNL PCPA AND XFMR TE-2.REMOVE PNL PCPA AND XFMR TE-2.

DEDUCTIVE ALTERNATIVE #2 WORK SHOWN IN THIS DOMAIN SHALL BE DEDUCTIVE ALTERNATIVE #2

08-26-2022

ADDENDUM #1

08-31-2022

ADDENDUM #1 REV 2

Sheets and Views

EP104

2022-08-31T13:13:17-0400

Robert A Haffeman

UP

K.3

MECHANICAL

ROOM

FB29-1

STAIR

#8

FLOOR PLAN - FB29-1 - NEW WORK

EXISTING & DEMOLITION PLAN - FB29-1

ELECTRICAL PLANS - FB29-1

Phone: (352) 474-6124 Fax: (352) 553-4437

EP-105

KEY PLAN - BLDG 1 BASEMENT

1-RF1

MCC-GB

STORM DRAIN

FIRE/SPRINKLER

CONDENSATE PIPE

HIGH PRESSURE STEAM

COLD WATER SUPPLY

COLD WATER RETURN

1-RF4

SF5

SIEMENS

1-SF4

1-RF3

SIEMENS CAB

1-RF2

1-SF3

DISC. SW.

1-P9

CNTRL PNL

MCC-GA

1-SF1

PNL H-GA

SIEMENS CAB

1-RF2

1-SF3

DISC. SW.

1-RF4

SF5

1-SF4

1-RF3

CONDENSATE PIPE

HIGH PRESSURE STEAM

COLD WATER SUPPLY

COLD WATER RETURN

STORM DRAIN

FIRE/SPRINKLER

1-RF1

CNTRL PNL

1-SF1

1-P9

1/8" = 1' - 0"

1/8" = 1' - 0"

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

A. NOT USED.NOT USED.

1. NOT USED NOT USED

PNL H-GB

DEDUCTIVE ALTERNATIVE #1 WORK SHOWN IN THIS DOMAIN SHALL BE DEDUCTIVE ALTERNATIVE #1

Sheets and Views

EP105

2022-03-23T11:19:54-0400

Robert Haffeman

ELECTRICAL PLANS - E-WING

BASEMENT

ELECTRICAL POWER PLAN BASEMENT

Phone: (352) 474-6124 Fax: (352) 553-4437

EP106

7.1 of 17

G

25 24 23 22 20 19 18 1721

EB60-1

OFFICE

EB62A-1

FIRE ALARM

CLOSET

EB62-1

ELECTRICAL

EB61-1

ASST. CHIEF

HIMS

EB58-1

EB56A-1

VAVS &

STORAGE

EB55-1

RELEASE OF

INFORMATION

EB54-1

CHIEF HIMS

EB57B-1

EB53-1

EB54A-1

EB52-1

FLAM

STOR

EB64-1

FLAM

STOR

EB63-1

E380-3

SHOP

EB67-1 UPPER

TRANSFORMER

EB66-1

UPPER

GENERATOR

EB65-1

#7-1

CORRIDOR

E213-76

E380-4

EB67B-1

DRAFTING

EB91-1

CLASSROOM

EB59B-1

EMS

EB84-1

SUPPLY

GENERAL

ENGI.

EB86-1

TOILET

EB94-1

TOILET

EB95-1

REVOLVING

FILES

FORMS AND

XEROX

EB93-1

ENGIN.

TECH #4

EB59C-1

TECH #3

EB96-1

TECH #2

EB92-1

TECH #1

EB90-1

SUPER.

GENERAL

ENGINEER

E213-102

ACCT. TECH.

EB88-1

RECP

EB105-1

SECY

EB103-1

DIVISION

CHIEF

EB101-1

WORK

ORDER

CLERK

EB99-1

SAFETY

EB97-1

MED.

MANAG.

SPECIAL.

EB98-1

SAFETY

SPECIALIST

EB100-1

STGE.

EB102-1

SYSTEM

CHIEF

SERV.

EB104-1

CONFERENCE

EB106-1

EB87-1

EB55B-1

EB855A-1

EB55C-1

EB56-1

EB62B-1

EB55D-1

TRANSCRIBE

E380-9

T/C

EB57A-1

EB57-1

LEGAL

EB85-1

EB67A-1

BUILDING 40

SWGR RM

AUGUST 26, 2022

N.T.S.

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

A. NOT USED.NOT USED.

1. NOT USEDNOT USED

ATS-Q

PNL FPQ4

Sheets and Views

EP104

2022-08-31T13:14:00-0400

Robert A Haffeman

MSGR-D

PARTIAL ONE-LINE DIAGRAM - BUILDING 1 - E-WING

MSGR-C

EMDP-5

Phone: (352) 474-6124 Fax: (352) 553-4437

BID DOCUMENTSELECTRICAL ONE-LINE

DIAGRAMS

EP601

800AF 150AT LSIG

800AF 400AT LSIG

1600AF LSIG SPARE

12470V

TIE

MAIN

OVERHEAD TIE BUSWAY, 3-PHASE, 4-WIRE, 2500A

800AF 800AT LSIG

800AF 600AT LSIG

EXIST. MCC-E2 (EQUIP) (EQUIP)

EXIST. MCC-N 600A MLO 480V 3PH 3W FPE CLASS 5310 MCC

EXIST. MCC-N1 1 H-1000A MLO V-600A 480Y/277, 3PH 4W GE 8000 LINE MCC

E-PENT

FROM MV-SWGR-A IN ROOM DO88-1

FROM MV-SWGR-B IN ROOM D088-1

%%UATS-E2

%%UATS-Q2

%%UATS-C2

%%UNF-3

%%UATS-C

%%UATS-Q

%%UATS-E

%%UPNL-FP4

%%UNF-2 BUS

1600AF 1200AT LSIG

800AF LSIG SPARE

480Y/ 277V

1000/1333 kVA AA/FA

800AF 800AT LSIG

2500AF 2000AT LSIG

1000/1333 kVA AA/FA

PX E195-1 CAT SCAN

TX-MSGR-C

TX-MSGR-D

ATS-C

(E-WING) (E-WING) 1600A MLO (PAD MOUNTED) 480Y/277V, 3PH 4W 65KAIC

100A

600A

ELEV. P-7

ELEV. P-8

400A

225A

200A

4EQHA

PNL-FPQ4 (EQUIPMENT) (EQUIPMENT) 800A MLO (SURFACE MOUNTED) 480Y/277, 3PH 4W 42KAIC

ELEV. P-9&10

ATS-Q2 (E-WING) EQUIPMENT 400A, 4-POLE DELAYED TRANSITION BYPASS ISOLATION 42KAIC

800A

150A

ATS-Q (E-WING) EQUIPMENT 800A, 4-POLE DELAYED TRANSITION BYPASS ISOLATION 42KAIC

EQICU XFMR

CTICU/AC

LSIA

15A/1P

LSI

FROM EMSGR-ACA IN ROOM C093-1

FROM MSGR-C

FROM MSGR-D

SPD

EXIST. MCC-Q (EQUIP) (EQUIP)

EXIST. MCC-E1 (EQUIP) (EQUIP) 150A

FCU-1/2 (RM. EB65-1)

ATS-E

ATS-E2

ATS-C2

ATS-

BLDG 40

BLDG 40

H-N1 800A 480Y/277V 3PH 4W

H-N 400A 480V 3PH 3W

EM-HA 400A 480V 3PH

H-Q 600A 480V 3PH

H-E2 400A 480V 3PH

L-E2 80A MCB 208Y/120V 3PH 4W

XF-E2 30KVA 480VΔ-208Y/120V

INTERCEPT EXIST. FEEDER AND PROVIDE JUNCTION BOX ENCLOSURE WITH INSULATED MECHANICAL DISTRIBUTION TAP BLOCKS (ILSCO MODEL PBTD OR SIMILAR). NEW FEEDER CONDUCTORS TO MATCH EXIST. (TYP.)

INTERCEPT EXISTING CIRCUIT NEAR OLD MCC

TYPICAL EXISTING LOAD WITH EXISTING LOCAL VFD, MOTOR STARTER, OR CONTROL PANEL.

TYPICAL EXISTING LOAD CONTROLLED BY STARTER IN OLD MCC.

PROVIDE NEW COMBINATION NON-FUSED FVNR DISCONNECT-TYPE MOTOR STARTER (LOCATION TBD). (BASIS OF DESIGN: SQ D CLASS 8538).

TYPICAL CIRCUIT INTERCEPT/REPLACEMENT INTENT APPLICABLE TO ALL MCC REPLACEMENTS IN PROJECT. SEE EXISTING MCC SCHEDULES FOR LISTING OF LOADS.

DESIGN INTENT FOR ENCLOSURE TYPES BASED ON LOCATION (APPLICABLE TO NEW PANELS, NEW TRANSFORMERS, AND NEW MOTOR STARTERS): EB60-1 - NEMA 4X 480-PENTHOUSE - NEMA 1 E-WING PENTHOUSE - NEMA 4X BLDG 12 ELEC RM - NEMA 1 ACA MECH ROOM - NEMA 4X EXTERIOR LOCATIONS - NEMA 4X OTHER INTERIOR NON-CONDITIONED LOCATIONS - NEMA 4X OTHER INTERIOR CONDITIONED LOCATIONS - NEMA 1

EXIST. PNL PQ-4 --A MLO 480V 3PH 3W

EXIST. PNL PCPA 208Y/120V 3PH 4W

XF-TE-2 15KVA 480VΔ-208Y/120V

EXIST. PNL PNPA 208Y/120V 3PH 4W

XF-T9 15KVA 480VΔ-208Y/120V

PNL EM-L 100A MCB 208Y/120V 3PH 4W

XFMR-EM 30KVA 480VΔ-208Y/120V

EM-HB 400A 480V 3PH

DEMAND 145A : 8/30/2022

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

NOTE: REFER TO DWG EP001 FOR FEEDER SCHEDULE WHERE WIRE SIZES ARE NOT SHOWN

Sheets and Views

EP601

2022-08-31T13:14:40-0400

Robert A Haffeman

PARTIAL ONE-LINE DIAGRAM - BUILDING 1 - ACA

PARTIAL ONE-LINE DIAGRAM - BUILDING 1 - 480 BED

PARTIAL ONE-LINE DIAGRAM - BUILDING 1 - 480 BED

US-5UNIT SUBSTATION

US-5

MSGR-A

Phone: (352) 474-6124 Fax: (352) 553-4437

BID DOCUMENTSELECTRICAL ONE-LINE

DIAGRAMS

EP602

FUTURE

SPARE 800A LSIG

400AT 400AF LSIG

SPARE 1600A LSIG

MTP (TYP.)

800AT 00AT 800AF

800AT 800AF

350AT 400AF

1200AT 1600AF

800AT 800AF LSIG

1200AT 1600AF

TIE 4000AT 4000AF LSG

EPM

4000AT 4000AF LSIG

4000A

EXISTING SWITCHGEAR 480Y/277V, 3 ,4W. 100KAIC

TO PANEL PBCNA AND PANEL PBCNB

TO AC-2

TO CHILLER-2

TO CHILLER-1

TO ATS-STBY1

TO ATS-EQ1

TO ATS-EC3

FROM 2500KVA TX-MSGR-A

TO MSGR-B

TO ATS-EQ2

TO ATS-STBY1

EXISTING EMSBD1 2500 MAIN LUG ONLY 480Y/277V, 3 , 4W.65KAIC

TO ATS-LS

TO ATS-EC2

TO ATS-EC1

TO ATS-EC3

TO ATS-EQ1

EXISTING ATS-EQ2 EQUIPMENT SYSTEM BYPASS ISOLATION 800A, 4P ATS 100KA SCR

EXISTING PANEL PBDQA 800A 480Y/277V

FROM MSGR-A

D089-1

D088-1

D088-1

D089-1

FROM GENERATOR

EXISTING PANEL PPDQA 800A 480Y/277V

SPEMR37-1

EXIST. MCC-CPH3 (EQUIP) (EQUIP)

MCC-CPH3 400A 480V 3PH

L-CPH3 100A MB 208Y/120V 3PH 4W

XFMR T-79 30KVA 480VΔ-208Y/120V

EXIST. MCC-PH-3 (EQUIP) (EQUIP)

H-PH3 400A 480V 3PH

INTERCEPT EXIST. FEEDER AND PROVIDE JUNCTION BOX ENCLOSURE WITH INSULATED MECHANICAL DISTRIBUTION TAP BLOCKS (ILSCO MODEL PBTD OR SIMILAR). NEW FEEDER CONDUCTORS SHALL MATCH EXIST. (TYP.)

EXIST. PNL RA.EQ2.PA

450A

TIE 1600A

300A

%%UATS-LS2

%%UATS-EQ2

%%UNSMSB-1

1500A

1500 kVA

4#350,1#3G, IN 3"C.

FB30-1

FROM 12.47KV PRIMARY SWGR

%%UTO US-5

SPARE 600A

%%UATS-C2

%%UPNL ALGB

450A

%%UPNL AL1B

EXIST. MCC-GB (NORM)

EXIST. MCC-GA (NORM)

4#350,1#3G, IN 3"C.

H-GA 300A MLO 480Y/277V 3PH 4W

PROVIDE TEMP. FEEDER FROM NEW PANELBOARD TO EXIST. MCC FOR DURATION OF LOAD TRANSFER (TYP.) DISCONNECT AND REMOVE AT PROJECT COMPLETION.

DOUBLE LUGS (TYP. FOR TEMP CONNECTION)

H-GB 300A MLO 480Y/277V 3PH 4W

NOTE: EXIST. XFMR T-79 ALONG WITH LIGHTNING PANEL CUL-M3 ARE CURRENTLY LOCATED IN MCC-CPH3. THEY SHALL BE REPLACED WITH NEW XFMR T-79 AND PANEL L-CPH3, OUTSIDE OF THE NEW MCC. RE-CIRCUIT ALL PREVIOUS CIRCUITS FROM CUL-M3 (12 POLE PANELBOARD) TO L-CHP3.

NORTH ROOF FACE

BOB THIS PANEL IS RATED FOR 1600

NOTE: REPLACE 400/3 CB IN PNL PPDQA WITH NOW 400/3 CB

ESEQDP4

ESEQDP3

EXISTING ATS-EQ3C

EXISTING ATS-EQ3B

EMDP-1

EMDP-2

PROVIDE NEW LABEL WHICH ELEVATOR IS BEEN FED BY THIS PANEL

PROVIDE NEW LABEL WHICH ELEVATOR IS BEEN FED BY THIS PANEL

PROVIDE NEW LABEL TO INDICATE NEW H-GA AND H-GB PANELS

NOTE: REFER TO DWG EP001 FOR FEEDER SCHEDULE WHERE WIRE SIZES ARE NOT SHOWN

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

Sheets and Views

EP602

2022-03-23T11:23:11-0400

Robert Haffeman

Phone: (352) 474-6124 Fax: (352) 553-4437

EXISTING EQUIP

RECONNECTION SCHEDULES

MECH ROOM EB60-1

EP701

EXIST MCC Q

EXIST MCC E2

EXIST MCC N

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

1. MOVE ALL WIRING TO NEW PANEL, MOVE ALL WIRING TO NEW PANEL, EXTEND CONDUIT AND WIRE AS REQUIRED

1. NOT USEDNOT USED

3A

3B

3D

3E

3F

3C

1A

1B

1C

1D

1E

2A

2B

2D

2E

2C

2F

4A

4B

4C

5A

5B

5D

5E

5F

5C

6A

6B

6D

6C

2G

4D

6E

5F

6A

6B

6D

6C

3G

7A

Sheets and Views

EP701

2022-03-23T11:24:52-0400

Robert Haffeman

Phone: (352) 474-6124 Fax: (352) 553-4437

480 BED PENTHOUSE

EP702

EXIST MCC CPH3

EXIST MCC PH3

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

1. NOT USEDNOT USED

1F

2H

3H

1G

1. MOVE ALL WIRING TO NEW PANEL, MOVE ALL WIRING TO NEW PANEL, EXTEND CONDUIT AND WIRE AS REQUIRED

Sheets and Views

EP702

2022-03-23T11:26:17-0400

Robert Haffeman

Phone: (352) 474-6124 Fax: (352) 553-4437

EP703

E-WING PENTHOUSE

EXIST MCC N1

EXIST MCC E1

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

1. NOT USEDNOT USED

1H

(FRONT)

(BACK)

(FRONT)

(BACK)

1. MOVE ALL WIRING TO NEW PANEL, MOVE ALL WIRING TO NEW PANEL, EXTEND CONDUIT AND WIRE AS REQUIRED

Sheets and Views

EP703

2022-03-23T11:28:36-0400

Robert Haffeman

Phone: (352) 474-6124 Fax: (352) 553-4437

EP704

MECH ROOM FB29-1

EP704

EXIST MCC GA

EXIST MCC GB

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

1. NOT USEDNOT USED

2H

3H

4E

1. MOVE ALL WIRING TO NEW PANEL, MOVE ALL WIRING TO NEW PANEL, EXTEND CONDUIT AND WIRE AS REQUIRED

Sheets and Views

EP704

2022-03-23T11:30:05-0400

Robert Haffeman

Phone: (352) 474-6124 Fax: (352) 553-4437

BID DOCUMENTSPANELBOARD SCHEDULES

MECH ROOM EB60-1

EP721

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

NOTE: TRANSFER ALL EXISTING 120V CIRCUITS TO THIS PANEL. EXTEND WIRING AS REQUIRED

Sheets and Views

EP721

2022-03-23T11:31:48-0400

Robert Haffeman

Phone: (352) 474-6124 Fax: (352) 553-4437

EP722

PANELBOARD SCHEDULES

480 BED PENTHOUSE

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

Sheets and Views

EP722

2022-03-23T11:32:25-0400

Robert Haffeman

X

X X

X X

XXX

MAIN HOSPITAL

7"

6"

10"10"

18"

11"

BLDG 1 - SECTIONS OVERVIEW

VICINITY MAP

TITLE PAGE, LOCATION MAP,

AND INDEX OF DRAWINGS

VA PROJECT NO. 573-19-615

UPGRADE MOTOR CONTROL CENTERS

AT BUILDING 1

MALCOM RANDALL VETERANS AFFAIRS MEDICAL CENTER

1601 SW ARCHER ROAD

GAINESVILLE, FL 32608

A-E CONTRACT NO. 36C24819D0021 36C24819N1164

DEPARTMENT OF VETERANS AFFAIRS

NORTH FLORIDA/SOUTH GEORGIA

VETERANS HEALTH SYSTEM

1601 SW ARCHER ROAD

GAINESVILLE, FL 32608

3603 NW 98TH STREET, SUITE B

GAINESVILLE, FLORIDA 32606

PH: (352) 474-6124

FAX. (352) 553-4437

DESIGNED FOR:

Design, Inc.Veterans Affairs Department of

FOR CONSTRUCTION

MARCH 23, 2022

DESIGNED BY:

PROJECT

LOCATION

PROJECT LOCATION MAP

G001

Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

DEDUCTIVE ALTERNATES

ORDER OF PRIORITY

PROJECT

LOCATION

BLDG #26

BLDG #27

T-1

T-2

T-5

T-4

T-6

S.W. 16th AVENUE

T-7

T-8

T-3

RAMP

DECK

DECK

S.W. 16th STREET

NEW

AMBULATORY

CARE

T-9

T-10

T-1B

WATER TANK

T-1A

MH-3

S-3

S-13

NEW BED TOWER

S

WV

BOILER

%%UACA (F,G)

%%UE-WING (E)

%%UMAIN BUILDING (A,B,C,D)

%%UBED TOWER (H,J)

(A)

(B)

(C)

(D)

%%UMEP BLDG

(G)

(F)

(H)

(J)

%%U480-BED

ROTATION -22°56'18"

VAMC

26A

GAINESVILLE, FL NOT TO SCALE

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

THIS PROJECT INCLUDES MULTIPLE DEDUCTIVE ALTERNATES. CONTRACTOR SHALL REFER TO SPEC SECTION 01 00 00 FOR DETAILED DESCRIPTIONS. IN SUMMARY: BASE BID: ALL WORK SHOWN. DEDUCT ALTERNATE #1: (EP105) DEDUCT MCC-GB & MCC-GA. DEDUCT ALTERNATE #2: (EP104) DEDUCT MCC-GB, MCC-GA, MCC-N1, AND MCC-E1.

HIGHEST PRIORITY ITEM IS LISTED FIRST. EACH ADDITIONAL ITEM IS PROGRESSIVELY LOWER IN PRIORITY. THIS LIST DOES NOT SPECIFY CONSTRUCTION SEQUENCE. 1. BUILDING 1 - EB60-1 - MCC-E2 BUILDING 1 - EB60-1 - MCC-E2 EB60-1 - MCC-E2 MCC-E2 2. BUILDING 1 - EB60-1 - MCC-Q BUILDING 1 - EB60-1 - MCC-Q EB60-1 - MCC-Q MCC-Q 3. BUILDING 1 - EB60-1 - MCC-N BUILDING 1 - EB60-1 - MCC-N EB60-1 - MCC-N MCC-N ............................................................................................... 4. BUILDING 1 - ELEVATOR PENTHOUSE - MCC-CPH-3 BUILDING 1 - ELEVATOR PENTHOUSE - MCC-CPH-3 5. BUILDING 1 - ELEVATOR PENTHOUSE - MCC-PH-3 BUILDING 1 - ELEVATOR PENTHOUSE - MCC-PH-3 ............................................................................................... 6. BUILDING 1 - E-WING PENTHOUSE - MCC-E1 BUILDING 1 - E-WING PENTHOUSE - MCC-E1 7. BUILDING 1 - E-WING PENTHOUSE - MCC-N1 BUILDING 1 - E-WING PENTHOUSE - MCC-N1 ............................................................................................... 8. BUILDING 1 - FB29-1 - MCC-GA BUILDING 1 - FB29-1 - MCC-GA 9. BUILDING 1 - FB29-1 - MCC-GBBUILDING 1 - FB29-1 - MCC-GB

Sheets and Views

G001

2022-08-31T13:15:14-0400

Robert A Haffeman

Phone: (352) 474-6124 Fax: (352) 553-4437

E-WING PENTHOUSE

EP723

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

Sheets and Views

EP723

2022-08-26T15:26:22-0400

Robert A Haffeman

Phone: (352) 474-6124 Fax: (352) 553-4437

BID DOCUMENTSELECTRICAL NOTES, SYMBOLS

AND ABBREVIATIONS

EP001

POWER

SYMBOLS ABBREVIATIONSELECTRICAL NOTES

DEMOLITION NOTES

BRANCH CLASSIFICATION

INVESTIGATIVE SERVICES

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

A AMPERE AMPERE AFC AVAILABLE FAULT CURRENT AVAILABLE FAULT CURRENT AFF ABOVE FINISHED FLOOR ABOVE FINISHED FLOOR ATS AUTOMATIC TRANSFER SWITCH AUTOMATIC TRANSFER SWITCH AWG AMERICAN WIRE GAUGE AMERICAN WIRE GAUGE BKR BREAKER BREAKER C CONDUIT CONDUIT CKT CIRCUIT CIRCUIT CONC CONCRETE CONCRETE CTRL CONTROL CONTROL CU COPPER COPPER DISC DISCONNECT DISCONNECT EGC EQUIPMENT GROUNDING CONDUCTOR EQUIPMENT GROUNDING CONDUCTOR ENCL ENCLOSURE ENCLOSURE EM EMERGENCY EMERGENCY EMT ELECTRIC METALLIC TUBING ELECTRIC METALLIC TUBING EXIST EXISTING EXISTING FLA FULL LOAD AMPERAGE FULL LOAD AMPERAGE GRD GROUND GROUND KAIC KILO-AMPERES INTERRUPTING CURRENT KILO-AMPERES INTERRUPTING CURRENT KCMIL THOUSAND CIRCULAR MILS THOUSAND CIRCULAR MILS KVA KILO-VOLT-AMPERE KILO-VOLT-AMPERE KW KILO-WATT KILO-WATT MCA MINIMUM CIRCUIT AMPACITY MINIMUM CIRCUIT AMPACITY MCB MAIN CIRCUIT BREAKER MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MOTOR CONTROL CENTER MCP MOTOR CIRCUIT PROTECTOR MOTOR CIRCUIT PROTECTOR MDP MAIN DISTRIBUTION PANEL MAIN DISTRIBUTION PANEL MLO MAIN LUGS ONLY MAIN LUGS ONLY MS MOTOR STARTER MOTOR STARTER MTD MOUNTED MOUNTED NEC NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL MANUFACTURER NATIONAL ELECTRICAL MANUFACTURER ASSOCIATION P POLE POLE PH, PHASE PNL PANEL PANEL PRI PRIMARY PRIMARY STRT STARTER STARTER SZ SIZE SIZE TYP TYPICAL TYPICAL UNO UNLESS NOTED OTHERWISE UNLESS NOTED OTHERWISE V VOLT VOLT VA VOLTS-AMPERE VOLTS-AMPERE WP WEATHERPROOF WEATHERPROOF XFMR TRANSFORMERTRANSFORMER

S

PANELBOARD, SURFACE MOUNTED TRANSFORMER DISCONNECT SWITCH COMBINATION MOTOR STARTER MOTOR TOGGLE SWITCH, MOTOR RATED JUNCTION BOX MOUNTED ABOVE CEILING WALL MOUNTED JUNCTION BOX POINT OF ELECTRICAL CONNECTION CONDUIT CONCEALED IN WALL OR CLG. CONDUIT UNDER FLOOR HOMERUN TO PNL WITH (2) #12, #12G IN 3/4"C, UNO. CIRCUIT CONTINUATION DENOTES SCOPE OF DEMOLITION ON RISER

APPLICABLE TO ALL ELECTRICAL SHEETS: 1. ALL WORK SHALL COMPLY WITH NEC, NFPA, AND ALL APPLICABLE FEDERAL CODES. ALL WORK SHALL COMPLY WITH NEC, NFPA, AND ALL APPLICABLE FEDERAL CODES. 2. FIELD VISIT BY INTERESTED CONTRACTORS IS "STRONGLY RECOMMENDED" TO BECOME FAMILIAR WITH THE FIELD VISIT BY INTERESTED CONTRACTORS IS "STRONGLY RECOMMENDED" TO BECOME FAMILIAR WITH THE COMPLEXITIES OF THIS PROJECT AND THE NECESSARY CONSTRUCTION CONSTRAINTS. 3. ALL BRANCH CIRCUITS SHALL BE RUN WITH DEDICATED NEUTRALS: NO SHARED NEUTRALS. ALL BRANCH CIRCUITS SHALL BE RUN WITH DEDICATED NEUTRALS: NO SHARED NEUTRALS. 4. IT IS ANTICIPATED THAT ANY CRITICAL WORK (SHUTDOWNS, ETC.), AFFECTING OTHER AREAS, WILL BE DONE DURING IT IS ANTICIPATED THAT ANY CRITICAL WORK (SHUTDOWNS, ETC.), AFFECTING OTHER AREAS, WILL BE DONE DURING OFF HOURS (NIGHTS, WEEK-ENDS, HOLIDAYS, ETC.) AND INTERESTED CONTRACTORS SHOULD PLAN ACCORDINGLY. A TWO (2) WEEK ADVANCE NOTIFICATION IS REQUIRED. INTENSIVE PLANNING IS REQUIRED TO ALLOW SCHEDULED WORK TO BE ACCOMPLISHED DURING SCHEDULED SHUTDOWN PERIODS. 5. ALL EXISTING CIRCUITS THAT ARE TO BE RE-FED, ARE TO BE INTERCEPTED AT THE CLOSEST POSSIBLE POINT OF ALL EXISTING CIRCUITS THAT ARE TO BE RE-FED, ARE TO BE INTERCEPTED AT THE CLOSEST POSSIBLE POINT OF THE EXISTING CIRCUIT SOURCE (ELECTRICAL CLOSET, PANELBOARD, DISCONNECT, ETC.) TO MINIMIZE DISRUPTION WHILE REPLACING FEEDER CIRCUITS. 6. IT IS ANTICIPATED THIS PROJECT MAY INVOLVE WORK ON OR VERY NEAR LIVE CIRCUITS. ANY SUCH WORK WILL IT IS ANTICIPATED THIS PROJECT MAY INVOLVE WORK ON OR VERY NEAR LIVE CIRCUITS. ANY SUCH WORK WILL REQUIRE A WRITTEN, TASK SPECIFIC, DETAILED PLAN OF ACTION THAT IS AGREEABLE TO BOTH THE CONTRACTOR AND COR, SIGNED BY BOTH, AND SUBMITTED TWO (2) WEEKS PRIOR TO STARTING THE TASK. ALL ELECTRICAL WORKERS SHALL MEET THE MINIMUM TRAINING/EXPERIENCE REQUIREMENTS AS DESCRIBED IN THE SPECIFICATIONS. CONTRACTOR SHALL BE TRAINED ON ARC FLASH SAFETY PROCEDURES AND SHALL POSSESS THE PROTECTIVE EQUIPMENT. CONTRACTOR SHALL COMPLY WITH THE VAMC INTERNAL PROCEDURES FOR WORKING ON ENERGIZED CIRCUITS. ENERGIZED WORK SHALL FOLLOW REQUIREMENTS OF NFPA 70E AND VA FMS SOP NO. 7. 7. ALL PATIENT CARE AREAS MUST COMPLETE EQUIPOTENTIAL TESTING/CERTIFICATION, PRIOR TO RETURNING TO ALL PATIENT CARE AREAS MUST COMPLETE EQUIPOTENTIAL TESTING/CERTIFICATION, PRIOR TO RETURNING TO OPERATIONAL STATUS. 8. ALL CONDUITS SHALL BE CLEAN AND FREE OF DEBRIS PRIOR TO INSTALLING NEW CONDUCTORS. ALL CONDUITS SHALL BE CLEAN AND FREE OF DEBRIS PRIOR TO INSTALLING NEW CONDUCTORS. 9. ALL CONDUCTORS SHALL BE INSTALLED IN CONDUIT. GENERAL DESIGN INTENT IS TO USE EMT WITH COMPRESSION ALL CONDUCTORS SHALL BE INSTALLED IN CONDUIT. GENERAL DESIGN INTENT IS TO USE EMT WITH COMPRESSION FITTINGS FOR INTERIOR SPACES, RMC WITH THREADED FITTINGS FOR ABOVE GROUND EXTERIOR. 10. ELECTRICAL DEVICES SHALL BE FED WITH (1) #12, (1) #12 N, AND (1) #12 G, UNO. ELECTRICAL DEVICES SHALL BE FED WITH (1) #12, (1) #12 N, AND (1) #12 G, UNO. 11. ALL WORK ABOVE EXISTING AND NEW ELECTRICAL EQUIPMENT SHALL BE PLANNED SUCH THAT THERE IS NO ALL WORK ABOVE EXISTING AND NEW ELECTRICAL EQUIPMENT SHALL BE PLANNED SUCH THAT THERE IS NO CLIMBING OR STANDING ON ELECTRICAL EQUIPMENT. FURNISH AND INSTALL TEMPORARY SCAFFOLDING AS REQUIRED. WORK ABOVE OR AT THE TOP OF EQUIPMENT SHALL BE PERFORMED IN A MANNER THAT PREVENTS DEBRIS AND DROPPED PARTS FROM ENTERING THE EQUIPMENT. PROVIDE TEMPORARY PROTECTION FOR EQUIPMENT AS REQUIRED, HOWEVER DO NOT BLOCK EQUIPMENT VENTILATION OPENINGS. 12. THE CONTRACTOR SHALL NOT OPERATE ANY EXISTING EQUIPMENT INCLUDING, BUT NOT LIMITED TO BREAKERS, THE CONTRACTOR SHALL NOT OPERATE ANY EXISTING EQUIPMENT INCLUDING, BUT NOT LIMITED TO BREAKERS, DISCONNECT SWITCHES, ETC., WITHOUT AUTHORIZATION FROM THE VAMC ENGINEERING SERVICE, UNLESS AN EMERGENCY SITUATION EXISTS. IN GENERAL, THE OPERATING STAFF OF THE VAMC ENGINEERING SERVICE WILL OPERATE ANY EXISTING EQUIPMENT WHICH THE CONTRACTOR MAY REQUIRE. 13. IF AN OBSTRUCTION SHOULD BE ENCOUNTERED THAT REQUIRES A DEVIATION FROM THE ORIGINAL PLANS, THE IF AN OBSTRUCTION SHOULD BE ENCOUNTERED THAT REQUIRES A DEVIATION FROM THE ORIGINAL PLANS, THE CONTRACTOR SHALL CONTACT THE COR AND ENGINEER FOR GUIDANCE. 14. PRINTED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON CONSTRUCTION DOCUMENTS. THE PRINTED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON CONSTRUCTION DOCUMENTS. THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE DOES NOT WARRANT THE ACCURACY OF SCALED DIMENSIONS. 15. OMISSIONS IN AND CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE CONSTRUCTION DOCUMENTS SHALL BE OMISSIONS IN AND CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE CONSTRUCTION DOCUMENTS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ENGINEER AND COR. CONFLICTS SHALL BE RESOLVED BY THE SAME BEFORE PROCEEDING WITH ANY WORK INVOLVED. 16. THE CONTRACTOR SHALL BECOME FAMILIAR WITH ALL PORTIONS OF THE CONSTRUCTION DOCUMENTS AND SHALL THE CONTRACTOR SHALL BECOME FAMILIAR WITH ALL PORTIONS OF THE CONSTRUCTION DOCUMENTS AND SHALL ENSURE THAT ALL SUBCONTRACTORS ARE FAMILIAR WITH THOSE PORTIONS PERTAINING TO THEIR AREA OF WORK. THE CONTRACTOR SHALL VERIFY ALL SITE CONDITIONS, DIMENSIONS, ELEVATIONS, COORDINATE ALL DOORS, WINDOWS, NON-BEARING INTERIOR AND EXTERIOR WALLS, ELEVATIONS, SLOPES, STAIRS, CURBS, DRAINS, RECESSES, DEPRESSIONS, RAILINGS, WATERPROOFING, FINISHES, CHAMFER, KERFS, AND SO FORTH, AND IMMEDIATELY NOTIFY THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE REGARDING ACTUAL CONDITIONS WHICH ARE NOT IN AGREEMENT WITH THE CONSTRUCTION DOCUMENTS. 17. CONTRACTOR SHALL MAKE PROVISIONS PER CODE AND SPECIFICATIONS FOR ALL EXPANSION JOINT CROSSINGS. CONTRACTOR SHALL MAKE PROVISIONS PER CODE AND SPECIFICATIONS FOR ALL EXPANSION JOINT CROSSINGS. 18. PROPOSED RACEWAY ROUTING FOR CONDUITS 2" AND LARGER IS SHOWN ON THE PLANS. RACEWAY ROUTING PROPOSED RACEWAY ROUTING FOR CONDUITS 2" AND LARGER IS SHOWN ON THE PLANS. RACEWAY ROUTING DEPICTED ON PLANS IS APPROXIMATE AND DIAGRAMMATIC. CONTRACTOR SHALL PROVIDE ALL OFFSETS AND PULLBOXES AS REQUIRED BY EXISTING CONDITIONS AND NEC TO ACCOMPLISH INSTALLATIONS. ALTERNATE ROUTING DIAGRAMS MAY BE CONTRACTOR-PROPOSED, CONTRACTOR-DESIGNED, CONTRACTOR-DRAWN, AND CONTRACTOR-SUBMITTED TO COR FOR REVIEW AND APPROVAL; ALTERNATE ROUTINGS WILL ONLY BE CONSIDERED IF ALTERNATE REQUIRES NO ADDITIONAL COST TO THE GOVERNMENT. CONTRACTOR SHALL PROVIDE ALL FIELD INVESTIGATION AND COORDINATION AS REQUIRED TO COMPLETE THE CONDUIT RUNS (FROM START TO END). 19. ALL CONDUITS SHALL BE INSPECTED BY COR, ELECTRIC SHOP, AND IRMS (IF APPLICABLE) PRIOR TO CLOSING WALLS ALL CONDUITS SHALL BE INSPECTED BY COR, ELECTRIC SHOP, AND IRMS (IF APPLICABLE) PRIOR TO CLOSING WALLS (TO CONFIRM BENDS, CONDUIT TYPES, BOXES, FITTINGS, ETC.) CONTRACTOR SHALL COORDINATE WITH VA FOR NECESSARY INSPECTIONS AND SHALL OBTAIN SIGNATURES UPON INSPECTION COMPLETIONS. 20. CONTRACTOR SHALL PROVIDE INFRARED SCANNING SERVICES TO CONFIRM TEMPERATURES AT ALL FINAL SPLICES AND CONTRACTOR SHALL PROVIDE INFRARED SCANNING SERVICES TO CONFIRM TEMPERATURES AT ALL FINAL SPLICES AND CONNECTIONS. 21. ALL NEW CIRCUIT BREAKERS RATED 225A AND LARGER SHALL BE 100% RATED WITH SOLID STATE LSIG TRIP UNITS.ALL NEW CIRCUIT BREAKERS RATED 225A AND LARGER SHALL BE 100% RATED WITH SOLID STATE LSIG TRIP UNITS.

FITTINGS SHALL BE PAINTED IN ACCORDANCE WITH BRANCH CLASSIFICATION. ALTERNATIVELY, CONDUIT MAY BE PAINTED WITH 3" WIDE STRIPS AT 8' MIN. INTERVALS, WITHIN 12" OF WALL PENETRATIONS, AND WITHIN 6" OF CONDUIT TERMINATIONS. (LS) LIFE SAFETY YELLOW LIFE SAFETY YELLOW YELLOW (CRIT) CRITICAL ORANGE CRITICAL ORANGE ORANGE (EQUIP) EQUIPMENT GREEN EQUIPMENT GREEN GREEN (NORM) NORMAL BLACK NORMAL BLACK BLACK (ESS) ESSENTIAL PURPLE ESSENTIAL PURPLE PURPLE FIRE ALARM RACEWAY (AND BOXES) SHALL BE RED PER SPECS

1. THE CONTRACTOR SHALL NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL-INCLUSIVE. IT IS THE CONTRACTOR'S THE CONTRACTOR SHALL NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL-INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH AREA AND TO FULFILL THE INTENT OF THE DESIGN INDICATED BY THE CONTRACT DOCUMENTS. REFER TO SPECIFICATION SECTION 010000 - GENERAL REQUIREMENTS AND THE VA MEDICAL CENTER FOR WORK RESTRICTIONS. CONTRACTOR SHALL COORDINATE DEMOLITION DRAWINGS AND NOTES WITH ALL DISCIPLINES INVOLVED. PATCH OR REBUILD ANY AREAS TO REMAIN THAT HAVE BEEN DAMAGED OR DISTURBED BY DEMOLITION. 2. REMOVE ALL EXISTING CONSTRUCTIONS AND FINISHES NECESSARY FOR THE COMPLETION OF THE WORK AS DEPICTED ON THE DRAWINGS. REMOVE ALL EXISTING CONSTRUCTIONS AND FINISHES NECESSARY FOR THE COMPLETION OF THE WORK AS DEPICTED ON THE DRAWINGS. INCLUDING BUT NOT LIMITED TO, ITEMS SHOWN ON THE PLANS. NECESSARY DISCONNECTS AND ALTERATIONS TO EXISTING MECHANICAL AND ELECTRICAL SYSTEMS SHALL BE INCLUDED. PATCH AS REQUIRED ALL CONSTRUCTIONS TO REMAIN IN ACCORDANCE WITH THE CONTRACT DRAWINGS. WHERE CONTRACTOR IS DESIGNATED TO MAKE REMOVALS, DISPOSITION OF MATERIALS IS THE RESPONSIBILITY OF THE CONTRACTOR. VERIFY WITH VA MEDICAL CENTER, THE DISPOSITION AND REMOVAL OF ANY COMPONENTS OF SALVAGEABLE VALUE. 3. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS WITHIN THE CONTRACT LIMITS AND NOTIFY THE COR IMMEDIATELY IN THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS WITHIN THE CONTRACT LIMITS AND NOTIFY THE COR IMMEDIATELY IN WRITING OF ANY DEVIATION FROM CONTRACT DOCUMENTS NECESSITATED BY FIELD CONDITIONS OR ITEMS NOT DEPICTED ON THE DRAWINGS. 4. ALL REMOVALS AND SALVAGE, UNLESS SPECIFICALLY NOTED OR REQUESTED BY THE VA MEDICAL CENTER SHALL BECOME THE PROPERTY OF ALL REMOVALS AND SALVAGE, UNLESS SPECIFICALLY NOTED OR REQUESTED BY THE VA MEDICAL CENTER SHALL BECOME THE PROPERTY OF THE CONTRACTOR. 5. ANY FLOOR OPENINGS SHALL BE PROTECTED AND SECURED DURING DEMOLITION AND CONSTRUCTION. ANY FLOOR OPENINGS SHALL BE PROTECTED AND SECURED DURING DEMOLITION AND CONSTRUCTION. 6. ANY EXTERIOR WALL OPENINGS SHALL BE CLOSED IMMEDIATELY OR BE PROVIDED WITH TEMPORARY WEATHER AND SECURITY PROTECTION IN ANY EXTERIOR WALL OPENINGS SHALL BE CLOSED IMMEDIATELY OR BE PROVIDED WITH TEMPORARY WEATHER AND SECURITY PROTECTION IN ACCORDANCE WITH SPECIFICATIONS. 7. PATCH ALL FINISHES TO MATCH EXISTING, INCLUDING BUT NOT LIMITED TO, GYPSUM BOARD, PLASTER, ACOUSTIC SYSTEMS, WOOD TRIM, PATCH ALL FINISHES TO MATCH EXISTING, INCLUDING BUT NOT LIMITED TO, GYPSUM BOARD, PLASTER, ACOUSTIC SYSTEMS, WOOD TRIM, COVERS, BASE, PANELS, RAILS AND WAINSCOT. FOR ALL SURFACES SCHEDULED TO REMAIN, PATCH AND MATCH SURFACES DISTURBED BY DEMOLITION OR REMOVAL OF EQUIPMENT OR UTILITIES. INSTALL PATCHING TO MATCH ADJACENT WORK IN FINISH, STRUCTURAL QUALITIES, COURSING OF MASONRY, AND OTHER CHARACTERISTICS. VERIFY MATCH OF NEW FINISH MATERIALS TO EXISTING IN COLOR, TEXTURE, THICKNESS, CUT, ETC… TO SATISFACTION OF VA MEDICAL CENTER PRIOR TO INSTALLATION. PROVIDE OTHER MATERIALS TO MATCH EXISTING TO SATISFACTION OF VA MEDICAL CENTER PRIOR TO INSTALLATION. PROVIDE OTHER MATERIALS TO MATCH EXISTING WHEN REQUIRED (TO BE APPROVED BY VA MEDICAL CENTER). PATCH EXISTING WALLS GYPSUM DRYWALL OR PLASTER TO MATCH EXISTING OF SUFFICIENT THICKNESS TO MAINTAIN UNIFORM WALL THICKNESS. ALL EXPOSED PORTIONS OF WALL SHALL BE FINISHED WITH THREE (3) COATS OF SPACKLING, SANDED AND LEFT IN A PAINT READY CONDITION. WHERE APPLICABLE, LEVEL ALL EXISTING FLOORS AS REQUIRED TO RECEIVE NEW FLOOR FINISHES. INSTALL REQUIRED TRANSITION PIECES BETWEEN VARIOUS FLOOR FINISHES SUITABLE FOR CONDITIONS, MEETING ADA REQUIREMENTS AND ACCEPTABLE TO THE VA MEDICAL CENTER. MATCH EXISTING WHEREVER POSSIBLE. PATCH SURFACES TO COMPLY WITH FIRE RATINGS, SMOKE-TIGHT RATINGS, ACOUSTICAL CRITERIA AND OTHER PERFORMANCE CRITERIA INDICATED. 8. MAINTAIN ACCESS TO EXITS AND EXIT STAIRS AT ALL TIMES. FIRE ALARM AND SMOKE DETECTION SYSTEM SHALL REMAIN OPERATIONAL AT MAINTAIN ACCESS TO EXITS AND EXIT STAIRS AT ALL TIMES. FIRE ALARM AND SMOKE DETECTION SYSTEM SHALL REMAIN OPERATIONAL AT ALL TIMES. PROTECT SMOKE DETECTORS AS REQUIRED AND IN CONFORMANCE WITH CODES AND LOCAL AUTHORITIES HAVING JURISDICTION. REFER TO MEDICAL CENTER CONTRACTOR HANDBOOK FOR WORK RESTRICTIONS. 9. ALL DEMOLITION SHALL BE PERFORMED IN A SAFE AND ACCEPTABLE MANNER TO ALL AUTHORITIES HAVING JURISDICTION AND THE VA ALL DEMOLITION SHALL BE PERFORMED IN A SAFE AND ACCEPTABLE MANNER TO ALL AUTHORITIES HAVING JURISDICTION AND THE VA MEDICAL CENTER. A FIRE WATCH SHALL BE PROVIDED IF ANY HAZARDOUS SITUATIONS ARE THOUGHT TO BE PRESENT OR POSSIBLE. COMPLY WITH GOVERNING REGULATIONS PERTAINING TO ENVIRONMENTAL PROTECTION FOR POLLUTION CONTROL. THOROUGHLY CLEAN ADJACENT AREAS OF DUST, DIRT AND DEBRIS CAUSED BY DEMOLITION WORK. BEFORE NEW WORK BEGINS, RETURN ADJACENT AREAS TO CONDITION FOUND PRIOR TO START OF DEMOLITION WORK. 10. ALL WORK SHALL BE DONE IN PROTECTED SPACE. NO DUST OR DIRT SHALL TRAVEL FROM CONSTRUCTION AREA TO ADJACENT AREAS. ALL WORK SHALL BE DONE IN PROTECTED SPACE. NO DUST OR DIRT SHALL TRAVEL FROM CONSTRUCTION AREA TO ADJACENT AREAS. TEMPORARY DUST PROTECTION SHALL BE ERECTED PRIOR TO START OF WORK. CONTRACTORS SHALL REVIEW PROVISIONS TO CONTROL AIRBORNE DUST WITH INFECTION CONTROL DIRECTOR, FACILITIES-BUILDING MANAGER AND CONSTRUCTION MANAGER. COORDINATE ADDITIONAL FILTRATION OF EXTERIOR AIR INTAKES TO MECHANICAL SYSTEMS. CONTRACTOR SHALL ASSIGN A PERSON(S) TO CLEAN ALL CONSTRUCTION AND COMMON AREAS, USED BY THE CONTRACTOR AND STAFF, DURING THE THE CONSTRUCTION HOURS. 11. PROVIDE TEMPORARY PARTITIONS/DUST PROTECTION (RATED AND/OR NON-RATED) AS REQUIRED. REVIEW LOCATIONS OF TEMPORARY PROVIDE TEMPORARY PARTITIONS/DUST PROTECTION (RATED AND/OR NON-RATED) AS REQUIRED. REVIEW LOCATIONS OF TEMPORARY PARTITIONS/DUST PROTECTION WITH VA MEDICAL CENTER AND COR PRIOR TO START OF WORK. 12. IF HAZARDOUS MATERIAL IS ENCOUNTERED OR SUSPECTED TO BE PRESENT, CONTRACTOR SHALL STOP WORK AND INFORM VA MEDICAL IF HAZARDOUS MATERIAL IS ENCOUNTERED OR SUSPECTED TO BE PRESENT, CONTRACTOR SHALL STOP WORK AND INFORM VA MEDICAL CENTER IMMEDIATELY IN WRITING OF ANY HAZARDOUS MATERIAL ENCOUNTERED OR THOUGHT TO BE HAZARDOUS MATERIAL. THE VA MEDICAL CENTER, AFTER RECEIVING WRITTEN NOTICE SHALL INSTRUCT CONTRACTOR ON HOW TO PROCEED. THIS INCLUDES, BUT IS NOT LIMITED TO PAINT THAT IS SUSPECT ON PIPING, CONDUIT, DUCTWORK OR ADJACENT SURFACES. 13. WHERE REMOVAL OF AN EXISTING CONCRETE HOUSEKEEPING PAD IS CALLED FOR, THE FOLLOWING ITEMS SHALL BE INCLUDED: A) CUT ANY WHERE REMOVAL OF AN EXISTING CONCRETE HOUSEKEEPING PAD IS CALLED FOR, THE FOLLOWING ITEMS SHALL BE INCLUDED: A) CUT ANY VERTICAL REINFORCING STEEL BACK BELOW FINISHED SLAB ELEVATION; B) CUT AND PLUG ANY UNUSED CONDUIT BACK BELOW FINISHED SLAB ELEVATION; C) ENSURE ANY ACTIVE EXISTING CONDUIT TO REMAIN IS NOT DISTURBED DURING DEMO OF THE PAD; D) REPAIR DEMO AREA WITH NEW CONCRETE AND REFINISH PER DIV 3 SPECIFICATIONS.

THIS PROJECT MAY REQUIRE NEW PENETRATIONS THROUGH EXISTING CONCRETE FLOORS. PRIOR TO LAYOUT AND INSTALLATION OF NEW CONDUIT REQUIRING NEW PENETRATIONS OF EXISTING CONCRETE FLOOR SLABS, THE CONTRACTOR SHALL SUBMIT TO THE COR THE TESTING AND INVESTIGATION SERVICE (TIS) WHICH WILL BE USED TO LOCATE THE EXISTING SLAB REINFORCEMENT FOR APPROVAL. THE TIS SHALL HAVE A MINIMUM OF 5 YEARS OF EXPERIENCE IN THE USE OF X-RAY AND GROUND PENETRATING RADAR (GPR). THE CONTRACTOR SHALL SUBMIT THE INVESTIGATIVE TESTING SERVICES WORK PLAN AND SCHEDULE FOR APPROVAL. THE TIS SHALL USE X-RAY, GPR OR OTHER SUITABLE NON-DESTRUCTIVE TESTING METHODOLOGY TO ACCURATELY IDENTIFY THE SLAB REINFORCING, FROM WHICH ADJUSTMENTS TO THE PENETRATIONS WILL BE MADE SO AS NOT TO COMPROMISE THE STRUCTURAL INTEGRITY OF THE EXISTING CONCRETE FLOOR SLABS. THE X-RAY OR GPR SHALL BE A CONTINUOUS 3-D GRID PROCESS (SCANNING GRID OF 2” ON CENTER) FOR AN AREA OF 24” BEYOND THE PROPOSED PENETRATION IN ALL ON CENTER) FOR AN AREA OF 24” BEYOND THE PROPOSED PENETRATION IN ALL BEYOND THE PROPOSED PENETRATION IN ALL DIRECTIONS. THE IDENTIFIED X-RAY OR GPR OF THE REINFORCING SHALL BE IDENTIFIED BY PENETRATION TYPE AND COLUMN GRID LINE DESIGNATION. THE AREA SHALL BE SURVEYED, MAPPED AND SUBMITTED TO THE COR FOR RECORD PURPOSES. THE REINFORCING SHALL BE MARKED ON THE CONCRETE SLAB AND USE DIFFERING COLORS FOR THE IDENTIFICATION OF TOP AND BOTTOM REINFORCING. THE CONTRACTOR SHALL GIVE THE COR 72 HOURS NOTICE PRIOR TO ANY INVESTIGATIVE TESTING WORK.

Sheets and Views

EP001

2022-03-23T10:43:23-0400

Robert Haffeman

Phone: (352) 474-6124 Fax: (352) 553-4437

MECH ROOM FB29-1

EP724

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

Sheets and Views

EP724

2022-03-23T11:34:18-0400

Robert Haffeman

JN

25 24 23

JN

25 24 23

Phone: (352) 474-6124 Fax: (352) 553-4437

BID DOCUMENTSELECTRICAL PLANS - EB60-1

EP101

FLOOR PLAN - EB60-1 - NEW WORK

EXISTING & DEMOLITION PLAN - EB60-1

KEY PLAN - BLDG 1 BASEMENT

MCC-E2

MCC-Q

MCC-N

CTRL RELAYS

DWP CP

AC-4

AC-4E

AC-4E SF VFD

HWP-1&2 VFD

AC-4 SF VFD

ORAL EVAC CNTRL

HONEYWELL CP

HWP-2

HWP-1

HWP-3

HWP-4

AIR COMP

AIR COMP CONTROLLERS

CP-5 MS

FLR CAB

AC4E-EF-1 (VFD)

AC4E-RHE-1 (VFD)

METAL CATWALK

AC-4E SOURCE MTS

PNL AC-4E

AC-4E EF VFD

ERV-4E VFD

H-N

H-Q

L-E2

XF-E2

H-E2

AC-4E

ORAL EVAC COMP

CTRL RELAYS

AC-4

AC-4 SF VFD

DWP CP

HWP-2

HWP-1

HWP-3

HWP-4

CONTROLLERS

CP-5 MS

AC-4E SF VFD

AC-4E EF VFD

ERV-4E VFD

HWP-1&2 VFD

AC-4E SOURCE MTS

PNL AC-4E

HONEYWELL CP

This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

A. NOT USED.NOT USED.

1. COORDINATE WITH THE VA FOR THE COORDINATE WITH THE VA FOR THE RELOCATION OF FLOOR SHELVING/CABINET. 2. REMOVE EXIST HOUSEKEEPING PAD. REMOVE EXIST HOUSEKEEPING PAD. REFINISH CONC FLOOR SLAB TO MATCH SURROUNDING CONDITIONS.