S01 - Attachment 01 - Drawings (Revised) (18 pages).pdf
PDF 16 MB Posted
- Attached to
- J061--Upgrade Motor Control Centers at BLDG One Federal contract opportunity
- Solicitation number
- Not on record
About this file
This document provides details for a federal contract opportunity to upgrade motor control centers at Building 1 for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 8. The purpose of the opportunity is to replace previously submitted Attachment 1 - Drawings (17 pages) with Attachment 1 - Drawings (Revised) (18 pages) and add a site visit sign-in sheet to contracting opportunities. Proposals are due by September 12, 2022 at 3:30 PM Eastern Time. The date for requests for information has closed, but the offer closing date for receipt of proposals remains unchanged. The project number is 573-19-615.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Site Visit Sign In 573-19-615 Upgrade Motor Control Centers at Building 1.pdf | ||
| SF30 Amendment 36C24822R0166 0001.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
For the best experience, open this PDF portfolio in
Acrobat X or Adobe Reader X, or later.
Get Adobe Reader Now!
http://www.adobe.com/go/reader
DN
ELEVATOR
PENTHOUSE
SPEMR 37-1
ELEVATOR
SPEMR 37-1
J
K
L
9 8 9 8
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
QBO: FL #29758
AKEA Design Project No. AD180-19 RAH KLL / KS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved: Project Director
VA FORM 08 - 6231
A
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 9 10
UPGRADE MOTOR CONTROL
CENTERS AT BUILDING 1
GAINESVILLE, FLORIDA
573-19-615
MARCH 23, 2022Revisions: Date:
Design, Inc.
Office of Construction and Facilities Management
ARCHITECT / ENGINEER OF RECORDCONSULTANT
BID DOCUMENTS
(FOR CONSTRUCTION)
BID DOCUMENTSELECTRICAL PLANS - 480-BED
EP102
N
FLOOR PLAN - 480-BED PENTHOUSE - NEW WORK
EXISTING & DEMOLITION PLAN - 480-BED PENTHOUSE
SHEET NOTES
SHEET KEYNOTES
KEY PLAN - BLDG 1 PENTHOUSE / ROOF
STATE OF
P R
O
FES S IO NA L ENGIN
EE
BER T A . HA FFEM
NNo. 66321 L I C E N S E
F L O R I D A
AutoCAD SHX Text
MCC-CPH3
MCC-PH3
PNL PPDQA
P-BOX
AHU-3 VFD
SHELVING RACK
EF-1
EF-2
EF-3
SIEMENS CONTROLS
PNL PPDQA
P-BOX
EF-1
AHU-3 VFD
SHELVING RACK
PNL L-CPH3
PNL H-PH3
EF-2
EF-3
SIEMENS CONTROLS
NEW MCC-CPH3
XFMR T-79, WALL MTD.
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
ENGINEER-OF-RECORD
ROBERT A. HAFFEMAN
66321
FL. P.E. NO.
SCALE:
1/4" = 1' - 0"
A. NOT USED.NOT USED.
1. EXIST HOUSEKEEPING PAD TO REMAIN. EXIST HOUSEKEEPING PAD TO REMAIN.
NTS
PROJECT AREA
Sheets and Views
EP102
2022-03-23T10:44:39-0400
Robert Haffeman
34567891011121314
G
H
M
Phone: (352) 474-6124 Fax: (352) 553-4437
BID DOCUMENTSELECTRICAL PLANS - 480-BED
ROOF TOP
EP103
KEY PLAN - BLDG 1 ROOF
480-BED ROOF/ PENTHOUSE
E-4
E-11
E-27
E-15
E-17
E-XX
E-20
E-16
E-18
E-19
E-3
E-1
E-2
AHU-3
ST-3
AF-3
AHU-3
E-13
E-14
E-12
E-25
E-21
E-22
E-24
E-23
E-26
E-5
OPEN WELL
OPEN WELL
PENTHOUSE ROOF
TOP OF 5TH FLOOR ROOF
TOP OF 5TH FLOOR ROOF
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
A. ROOFTOP PLAN DRAWING IS INCLUDED ROOFTOP PLAN DRAWING IS INCLUDED FOR REFERENCE TO EXISTING FAN LOCATIONS.
1. NOT USED. NOT USED.
3/32" = 1' - 0"
Sheets and Views
EP103
2022-03-23T10:45:20-0400
Robert Haffeman
20 19 1821
E-WING
20 19 1821
ELECTRICAL PLANS - E-WING
FLOOR PLAN - E-WING PENTHOUSE - NEW WORK
EXISTING & DEMOLITION PLAN - E-WING PENTHOUSE
Phone: (352) 474-6124 Fax: (352) 553-4437
EP104
FESS IO NA L ENGIN
FRONT
BACK
PNL PNPA
XFMR T-9
MCC-E1
MCC-N1
BACK
VFD
SIEMENS APPOGEE
HONNEYWELL PNL
HYDRAULIC CONTROLS
FEEDER P-BOX
CONTROLS
XFMR TE-2
PNL PCPA
HVAC UNIT
H-N1
PNL PNPA
XFMR T-9
HONNEYWELL PNL
HVAC UNIT
FEEDER P-BOX
EM-HA
EM-L
EM-HB
XFMR EM
HYDRAULIC CONTROLS
DOWN
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
A. NOT USED.NOT USED.
1. REMOVE EXIST. HOUSEKEEPING PAD. REMOVE EXIST. HOUSEKEEPING PAD. REFINISH CONC. FLOOR SLAB TO MATCH SURROUNDING CONDITIONS. 2. REMOVE PNL PCPA AND XFMR TE-2.REMOVE PNL PCPA AND XFMR TE-2.
DEDUCTIVE ALTERNATIVE #2 WORK SHOWN IN THIS DOMAIN SHALL BE DEDUCTIVE ALTERNATIVE #2
08-26-2022
ADDENDUM #1
08-31-2022
ADDENDUM #1 REV 2
Sheets and Views
EP104
2022-08-31T13:13:17-0400
Robert A Haffeman
UP
K.3
MECHANICAL
ROOM
FB29-1
STAIR
#8
FLOOR PLAN - FB29-1 - NEW WORK
EXISTING & DEMOLITION PLAN - FB29-1
ELECTRICAL PLANS - FB29-1
Phone: (352) 474-6124 Fax: (352) 553-4437
EP-105
KEY PLAN - BLDG 1 BASEMENT
1-RF1
MCC-GB
STORM DRAIN
FIRE/SPRINKLER
CONDENSATE PIPE
HIGH PRESSURE STEAM
COLD WATER SUPPLY
COLD WATER RETURN
1-RF4
SF5
SIEMENS
1-SF4
1-RF3
SIEMENS CAB
1-RF2
1-SF3
DISC. SW.
1-P9
CNTRL PNL
MCC-GA
1-SF1
PNL H-GA
SIEMENS CAB
1-RF2
1-SF3
DISC. SW.
1-RF4
SF5
1-SF4
1-RF3
CONDENSATE PIPE
HIGH PRESSURE STEAM
COLD WATER SUPPLY
COLD WATER RETURN
STORM DRAIN
FIRE/SPRINKLER
1-RF1
CNTRL PNL
1-SF1
1-P9
1/8" = 1' - 0"
1/8" = 1' - 0"
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
A. NOT USED.NOT USED.
1. NOT USED NOT USED
PNL H-GB
DEDUCTIVE ALTERNATIVE #1 WORK SHOWN IN THIS DOMAIN SHALL BE DEDUCTIVE ALTERNATIVE #1
Sheets and Views
EP105
2022-03-23T11:19:54-0400
Robert Haffeman
ELECTRICAL PLANS - E-WING
BASEMENT
ELECTRICAL POWER PLAN BASEMENT
Phone: (352) 474-6124 Fax: (352) 553-4437
EP106
7.1 of 17
G
25 24 23 22 20 19 18 1721
EB60-1
OFFICE
EB62A-1
FIRE ALARM
CLOSET
EB62-1
ELECTRICAL
EB61-1
ASST. CHIEF
HIMS
EB58-1
EB56A-1
VAVS &
STORAGE
EB55-1
RELEASE OF
INFORMATION
EB54-1
CHIEF HIMS
EB57B-1
EB53-1
EB54A-1
EB52-1
FLAM
STOR
EB64-1
FLAM
STOR
EB63-1
E380-3
SHOP
EB67-1 UPPER
TRANSFORMER
EB66-1
UPPER
GENERATOR
EB65-1
#7-1
CORRIDOR
E213-76
E380-4
EB67B-1
DRAFTING
EB91-1
CLASSROOM
EB59B-1
EMS
EB84-1
SUPPLY
GENERAL
ENGI.
EB86-1
TOILET
EB94-1
TOILET
EB95-1
REVOLVING
FILES
FORMS AND
XEROX
EB93-1
ENGIN.
TECH #4
EB59C-1
TECH #3
EB96-1
TECH #2
EB92-1
TECH #1
EB90-1
SUPER.
GENERAL
ENGINEER
E213-102
ACCT. TECH.
EB88-1
RECP
EB105-1
SECY
EB103-1
DIVISION
CHIEF
EB101-1
WORK
ORDER
CLERK
EB99-1
SAFETY
EB97-1
MED.
MANAG.
SPECIAL.
EB98-1
SAFETY
SPECIALIST
EB100-1
STGE.
EB102-1
SYSTEM
CHIEF
SERV.
EB104-1
CONFERENCE
EB106-1
EB87-1
EB55B-1
EB855A-1
EB55C-1
EB56-1
EB62B-1
EB55D-1
TRANSCRIBE
E380-9
T/C
EB57A-1
EB57-1
LEGAL
EB85-1
EB67A-1
BUILDING 40
SWGR RM
AUGUST 26, 2022
N.T.S.
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
A. NOT USED.NOT USED.
1. NOT USEDNOT USED
ATS-Q
PNL FPQ4
Sheets and Views
EP104
2022-08-31T13:14:00-0400
Robert A Haffeman
MSGR-D
PARTIAL ONE-LINE DIAGRAM - BUILDING 1 - E-WING
MSGR-C
EMDP-5
Phone: (352) 474-6124 Fax: (352) 553-4437
BID DOCUMENTSELECTRICAL ONE-LINE
DIAGRAMS
EP601
800AF 150AT LSIG
800AF 400AT LSIG
1600AF LSIG SPARE
12470V
TIE
MAIN
OVERHEAD TIE BUSWAY, 3-PHASE, 4-WIRE, 2500A
800AF 800AT LSIG
800AF 600AT LSIG
EXIST. MCC-E2 (EQUIP) (EQUIP)
EXIST. MCC-N 600A MLO 480V 3PH 3W FPE CLASS 5310 MCC
EXIST. MCC-N1 1 H-1000A MLO V-600A 480Y/277, 3PH 4W GE 8000 LINE MCC
E-PENT
FROM MV-SWGR-A IN ROOM DO88-1
FROM MV-SWGR-B IN ROOM D088-1
%%UATS-E2
%%UATS-Q2
%%UATS-C2
%%UNF-3
%%UATS-C
%%UATS-Q
%%UATS-E
%%UPNL-FP4
%%UNF-2 BUS
1600AF 1200AT LSIG
800AF LSIG SPARE
480Y/ 277V
1000/1333 kVA AA/FA
800AF 800AT LSIG
2500AF 2000AT LSIG
1000/1333 kVA AA/FA
PX E195-1 CAT SCAN
TX-MSGR-C
TX-MSGR-D
ATS-C
(E-WING) (E-WING) 1600A MLO (PAD MOUNTED) 480Y/277V, 3PH 4W 65KAIC
100A
600A
ELEV. P-7
ELEV. P-8
400A
225A
200A
4EQHA
PNL-FPQ4 (EQUIPMENT) (EQUIPMENT) 800A MLO (SURFACE MOUNTED) 480Y/277, 3PH 4W 42KAIC
ELEV. P-9&10
ATS-Q2 (E-WING) EQUIPMENT 400A, 4-POLE DELAYED TRANSITION BYPASS ISOLATION 42KAIC
800A
150A
ATS-Q (E-WING) EQUIPMENT 800A, 4-POLE DELAYED TRANSITION BYPASS ISOLATION 42KAIC
EQICU XFMR
CTICU/AC
LSIA
15A/1P
LSI
FROM EMSGR-ACA IN ROOM C093-1
FROM MSGR-C
FROM MSGR-D
SPD
EXIST. MCC-Q (EQUIP) (EQUIP)
EXIST. MCC-E1 (EQUIP) (EQUIP) 150A
FCU-1/2 (RM. EB65-1)
ATS-E
ATS-E2
ATS-C2
ATS-
BLDG 40
BLDG 40
H-N1 800A 480Y/277V 3PH 4W
H-N 400A 480V 3PH 3W
EM-HA 400A 480V 3PH
H-Q 600A 480V 3PH
H-E2 400A 480V 3PH
L-E2 80A MCB 208Y/120V 3PH 4W
XF-E2 30KVA 480VΔ-208Y/120V
INTERCEPT EXIST. FEEDER AND PROVIDE JUNCTION BOX ENCLOSURE WITH INSULATED MECHANICAL DISTRIBUTION TAP BLOCKS (ILSCO MODEL PBTD OR SIMILAR). NEW FEEDER CONDUCTORS TO MATCH EXIST. (TYP.)
INTERCEPT EXISTING CIRCUIT NEAR OLD MCC
TYPICAL EXISTING LOAD WITH EXISTING LOCAL VFD, MOTOR STARTER, OR CONTROL PANEL.
TYPICAL EXISTING LOAD CONTROLLED BY STARTER IN OLD MCC.
PROVIDE NEW COMBINATION NON-FUSED FVNR DISCONNECT-TYPE MOTOR STARTER (LOCATION TBD). (BASIS OF DESIGN: SQ D CLASS 8538).
TYPICAL CIRCUIT INTERCEPT/REPLACEMENT INTENT APPLICABLE TO ALL MCC REPLACEMENTS IN PROJECT. SEE EXISTING MCC SCHEDULES FOR LISTING OF LOADS.
DESIGN INTENT FOR ENCLOSURE TYPES BASED ON LOCATION (APPLICABLE TO NEW PANELS, NEW TRANSFORMERS, AND NEW MOTOR STARTERS): EB60-1 - NEMA 4X 480-PENTHOUSE - NEMA 1 E-WING PENTHOUSE - NEMA 4X BLDG 12 ELEC RM - NEMA 1 ACA MECH ROOM - NEMA 4X EXTERIOR LOCATIONS - NEMA 4X OTHER INTERIOR NON-CONDITIONED LOCATIONS - NEMA 4X OTHER INTERIOR CONDITIONED LOCATIONS - NEMA 1
EXIST. PNL PQ-4 --A MLO 480V 3PH 3W
EXIST. PNL PCPA 208Y/120V 3PH 4W
XF-TE-2 15KVA 480VΔ-208Y/120V
EXIST. PNL PNPA 208Y/120V 3PH 4W
XF-T9 15KVA 480VΔ-208Y/120V
PNL EM-L 100A MCB 208Y/120V 3PH 4W
XFMR-EM 30KVA 480VΔ-208Y/120V
EM-HB 400A 480V 3PH
DEMAND 145A : 8/30/2022
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
NOTE: REFER TO DWG EP001 FOR FEEDER SCHEDULE WHERE WIRE SIZES ARE NOT SHOWN
Sheets and Views
EP601
2022-08-31T13:14:40-0400
Robert A Haffeman
PARTIAL ONE-LINE DIAGRAM - BUILDING 1 - ACA
PARTIAL ONE-LINE DIAGRAM - BUILDING 1 - 480 BED
PARTIAL ONE-LINE DIAGRAM - BUILDING 1 - 480 BED
US-5UNIT SUBSTATION
US-5
MSGR-A
Phone: (352) 474-6124 Fax: (352) 553-4437
BID DOCUMENTSELECTRICAL ONE-LINE
DIAGRAMS
EP602
FUTURE
SPARE 800A LSIG
400AT 400AF LSIG
SPARE 1600A LSIG
MTP (TYP.)
800AT 00AT 800AF
800AT 800AF
350AT 400AF
1200AT 1600AF
800AT 800AF LSIG
1200AT 1600AF
TIE 4000AT 4000AF LSG
EPM
4000AT 4000AF LSIG
4000A
EXISTING SWITCHGEAR 480Y/277V, 3 ,4W. 100KAIC
TO PANEL PBCNA AND PANEL PBCNB
TO AC-2
TO CHILLER-2
TO CHILLER-1
TO ATS-STBY1
TO ATS-EQ1
TO ATS-EC3
FROM 2500KVA TX-MSGR-A
TO MSGR-B
TO ATS-EQ2
TO ATS-STBY1
EXISTING EMSBD1 2500 MAIN LUG ONLY 480Y/277V, 3 , 4W.65KAIC
TO ATS-LS
TO ATS-EC2
TO ATS-EC1
TO ATS-EC3
TO ATS-EQ1
EXISTING ATS-EQ2 EQUIPMENT SYSTEM BYPASS ISOLATION 800A, 4P ATS 100KA SCR
EXISTING PANEL PBDQA 800A 480Y/277V
FROM MSGR-A
D089-1
D088-1
D088-1
D089-1
FROM GENERATOR
EXISTING PANEL PPDQA 800A 480Y/277V
SPEMR37-1
EXIST. MCC-CPH3 (EQUIP) (EQUIP)
MCC-CPH3 400A 480V 3PH
L-CPH3 100A MB 208Y/120V 3PH 4W
XFMR T-79 30KVA 480VΔ-208Y/120V
EXIST. MCC-PH-3 (EQUIP) (EQUIP)
H-PH3 400A 480V 3PH
INTERCEPT EXIST. FEEDER AND PROVIDE JUNCTION BOX ENCLOSURE WITH INSULATED MECHANICAL DISTRIBUTION TAP BLOCKS (ILSCO MODEL PBTD OR SIMILAR). NEW FEEDER CONDUCTORS SHALL MATCH EXIST. (TYP.)
EXIST. PNL RA.EQ2.PA
450A
TIE 1600A
300A
%%UATS-LS2
%%UATS-EQ2
%%UNSMSB-1
1500A
1500 kVA
4#350,1#3G, IN 3"C.
FB30-1
FROM 12.47KV PRIMARY SWGR
%%UTO US-5
SPARE 600A
%%UATS-C2
%%UPNL ALGB
450A
%%UPNL AL1B
EXIST. MCC-GB (NORM)
EXIST. MCC-GA (NORM)
4#350,1#3G, IN 3"C.
H-GA 300A MLO 480Y/277V 3PH 4W
PROVIDE TEMP. FEEDER FROM NEW PANELBOARD TO EXIST. MCC FOR DURATION OF LOAD TRANSFER (TYP.) DISCONNECT AND REMOVE AT PROJECT COMPLETION.
DOUBLE LUGS (TYP. FOR TEMP CONNECTION)
H-GB 300A MLO 480Y/277V 3PH 4W
NOTE: EXIST. XFMR T-79 ALONG WITH LIGHTNING PANEL CUL-M3 ARE CURRENTLY LOCATED IN MCC-CPH3. THEY SHALL BE REPLACED WITH NEW XFMR T-79 AND PANEL L-CPH3, OUTSIDE OF THE NEW MCC. RE-CIRCUIT ALL PREVIOUS CIRCUITS FROM CUL-M3 (12 POLE PANELBOARD) TO L-CHP3.
NORTH ROOF FACE
BOB THIS PANEL IS RATED FOR 1600
NOTE: REPLACE 400/3 CB IN PNL PPDQA WITH NOW 400/3 CB
ESEQDP4
ESEQDP3
EXISTING ATS-EQ3C
EXISTING ATS-EQ3B
EMDP-1
EMDP-2
PROVIDE NEW LABEL WHICH ELEVATOR IS BEEN FED BY THIS PANEL
PROVIDE NEW LABEL WHICH ELEVATOR IS BEEN FED BY THIS PANEL
PROVIDE NEW LABEL TO INDICATE NEW H-GA AND H-GB PANELS
NOTE: REFER TO DWG EP001 FOR FEEDER SCHEDULE WHERE WIRE SIZES ARE NOT SHOWN
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
Sheets and Views
EP602
2022-03-23T11:23:11-0400
Robert Haffeman
Phone: (352) 474-6124 Fax: (352) 553-4437
EXISTING EQUIP
RECONNECTION SCHEDULES
MECH ROOM EB60-1
EP701
EXIST MCC Q
EXIST MCC E2
EXIST MCC N
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
1. MOVE ALL WIRING TO NEW PANEL, MOVE ALL WIRING TO NEW PANEL, EXTEND CONDUIT AND WIRE AS REQUIRED
1. NOT USEDNOT USED
3A
3B
3D
3E
3F
3C
1A
1B
1C
1D
1E
2A
2B
2D
2E
2C
2F
4A
4B
4C
5A
5B
5D
5E
5F
5C
6A
6B
6D
6C
2G
4D
6E
5F
6A
6B
6D
6C
3G
7A
Sheets and Views
EP701
2022-03-23T11:24:52-0400
Robert Haffeman
Phone: (352) 474-6124 Fax: (352) 553-4437
480 BED PENTHOUSE
EP702
EXIST MCC CPH3
EXIST MCC PH3
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
1. NOT USEDNOT USED
1F
2H
3H
1G
1. MOVE ALL WIRING TO NEW PANEL, MOVE ALL WIRING TO NEW PANEL, EXTEND CONDUIT AND WIRE AS REQUIRED
Sheets and Views
EP702
2022-03-23T11:26:17-0400
Robert Haffeman
Phone: (352) 474-6124 Fax: (352) 553-4437
EP703
E-WING PENTHOUSE
EXIST MCC N1
EXIST MCC E1
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
1. NOT USEDNOT USED
1H
(FRONT)
(BACK)
(FRONT)
(BACK)
1. MOVE ALL WIRING TO NEW PANEL, MOVE ALL WIRING TO NEW PANEL, EXTEND CONDUIT AND WIRE AS REQUIRED
Sheets and Views
EP703
2022-03-23T11:28:36-0400
Robert Haffeman
Phone: (352) 474-6124 Fax: (352) 553-4437
EP704
MECH ROOM FB29-1
EP704
EXIST MCC GA
EXIST MCC GB
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
1. NOT USEDNOT USED
2H
3H
4E
1. MOVE ALL WIRING TO NEW PANEL, MOVE ALL WIRING TO NEW PANEL, EXTEND CONDUIT AND WIRE AS REQUIRED
Sheets and Views
EP704
2022-03-23T11:30:05-0400
Robert Haffeman
Phone: (352) 474-6124 Fax: (352) 553-4437
BID DOCUMENTSPANELBOARD SCHEDULES
MECH ROOM EB60-1
EP721
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
NOTE: TRANSFER ALL EXISTING 120V CIRCUITS TO THIS PANEL. EXTEND WIRING AS REQUIRED
Sheets and Views
EP721
2022-03-23T11:31:48-0400
Robert Haffeman
Phone: (352) 474-6124 Fax: (352) 553-4437
EP722
PANELBOARD SCHEDULES
480 BED PENTHOUSE
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
Sheets and Views
EP722
2022-03-23T11:32:25-0400
Robert Haffeman
X
X X
X X
XXX
MAIN HOSPITAL
7"
6"
10"10"
18"
11"
BLDG 1 - SECTIONS OVERVIEW
VICINITY MAP
TITLE PAGE, LOCATION MAP,
AND INDEX OF DRAWINGS
VA PROJECT NO. 573-19-615
UPGRADE MOTOR CONTROL CENTERS
AT BUILDING 1
MALCOM RANDALL VETERANS AFFAIRS MEDICAL CENTER
1601 SW ARCHER ROAD
GAINESVILLE, FL 32608
A-E CONTRACT NO. 36C24819D0021 36C24819N1164
DEPARTMENT OF VETERANS AFFAIRS
NORTH FLORIDA/SOUTH GEORGIA
VETERANS HEALTH SYSTEM
1601 SW ARCHER ROAD
GAINESVILLE, FL 32608
3603 NW 98TH STREET, SUITE B
GAINESVILLE, FLORIDA 32606
PH: (352) 474-6124
FAX. (352) 553-4437
DESIGNED FOR:
Design, Inc.Veterans Affairs Department of
FOR CONSTRUCTION
MARCH 23, 2022
DESIGNED BY:
PROJECT
LOCATION
PROJECT LOCATION MAP
G001
Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
DEDUCTIVE ALTERNATES
ORDER OF PRIORITY
PROJECT
LOCATION
BLDG #26
BLDG #27
T-1
T-2
T-5
T-4
T-6
S.W. 16th AVENUE
T-7
T-8
T-3
RAMP
DECK
DECK
S.W. 16th STREET
NEW
AMBULATORY
CARE
T-9
T-10
T-1B
WATER TANK
T-1A
MH-3
S-3
S-13
NEW BED TOWER
S
WV
BOILER
%%UACA (F,G)
%%UE-WING (E)
%%UMAIN BUILDING (A,B,C,D)
%%UBED TOWER (H,J)
(A)
(B)
(C)
(D)
%%UMEP BLDG
(G)
(F)
(H)
(J)
%%U480-BED
ROTATION -22°56'18"
VAMC
26A
GAINESVILLE, FL NOT TO SCALE
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
THIS PROJECT INCLUDES MULTIPLE DEDUCTIVE ALTERNATES. CONTRACTOR SHALL REFER TO SPEC SECTION 01 00 00 FOR DETAILED DESCRIPTIONS. IN SUMMARY: BASE BID: ALL WORK SHOWN. DEDUCT ALTERNATE #1: (EP105) DEDUCT MCC-GB & MCC-GA. DEDUCT ALTERNATE #2: (EP104) DEDUCT MCC-GB, MCC-GA, MCC-N1, AND MCC-E1.
HIGHEST PRIORITY ITEM IS LISTED FIRST. EACH ADDITIONAL ITEM IS PROGRESSIVELY LOWER IN PRIORITY. THIS LIST DOES NOT SPECIFY CONSTRUCTION SEQUENCE. 1. BUILDING 1 - EB60-1 - MCC-E2 BUILDING 1 - EB60-1 - MCC-E2 EB60-1 - MCC-E2 MCC-E2 2. BUILDING 1 - EB60-1 - MCC-Q BUILDING 1 - EB60-1 - MCC-Q EB60-1 - MCC-Q MCC-Q 3. BUILDING 1 - EB60-1 - MCC-N BUILDING 1 - EB60-1 - MCC-N EB60-1 - MCC-N MCC-N ............................................................................................... 4. BUILDING 1 - ELEVATOR PENTHOUSE - MCC-CPH-3 BUILDING 1 - ELEVATOR PENTHOUSE - MCC-CPH-3 5. BUILDING 1 - ELEVATOR PENTHOUSE - MCC-PH-3 BUILDING 1 - ELEVATOR PENTHOUSE - MCC-PH-3 ............................................................................................... 6. BUILDING 1 - E-WING PENTHOUSE - MCC-E1 BUILDING 1 - E-WING PENTHOUSE - MCC-E1 7. BUILDING 1 - E-WING PENTHOUSE - MCC-N1 BUILDING 1 - E-WING PENTHOUSE - MCC-N1 ............................................................................................... 8. BUILDING 1 - FB29-1 - MCC-GA BUILDING 1 - FB29-1 - MCC-GA 9. BUILDING 1 - FB29-1 - MCC-GBBUILDING 1 - FB29-1 - MCC-GB
Sheets and Views
G001
2022-08-31T13:15:14-0400
Robert A Haffeman
Phone: (352) 474-6124 Fax: (352) 553-4437
E-WING PENTHOUSE
EP723
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
Sheets and Views
EP723
2022-08-26T15:26:22-0400
Robert A Haffeman
Phone: (352) 474-6124 Fax: (352) 553-4437
BID DOCUMENTSELECTRICAL NOTES, SYMBOLS
AND ABBREVIATIONS
EP001
POWER
SYMBOLS ABBREVIATIONSELECTRICAL NOTES
DEMOLITION NOTES
BRANCH CLASSIFICATION
INVESTIGATIVE SERVICES
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
A AMPERE AMPERE AFC AVAILABLE FAULT CURRENT AVAILABLE FAULT CURRENT AFF ABOVE FINISHED FLOOR ABOVE FINISHED FLOOR ATS AUTOMATIC TRANSFER SWITCH AUTOMATIC TRANSFER SWITCH AWG AMERICAN WIRE GAUGE AMERICAN WIRE GAUGE BKR BREAKER BREAKER C CONDUIT CONDUIT CKT CIRCUIT CIRCUIT CONC CONCRETE CONCRETE CTRL CONTROL CONTROL CU COPPER COPPER DISC DISCONNECT DISCONNECT EGC EQUIPMENT GROUNDING CONDUCTOR EQUIPMENT GROUNDING CONDUCTOR ENCL ENCLOSURE ENCLOSURE EM EMERGENCY EMERGENCY EMT ELECTRIC METALLIC TUBING ELECTRIC METALLIC TUBING EXIST EXISTING EXISTING FLA FULL LOAD AMPERAGE FULL LOAD AMPERAGE GRD GROUND GROUND KAIC KILO-AMPERES INTERRUPTING CURRENT KILO-AMPERES INTERRUPTING CURRENT KCMIL THOUSAND CIRCULAR MILS THOUSAND CIRCULAR MILS KVA KILO-VOLT-AMPERE KILO-VOLT-AMPERE KW KILO-WATT KILO-WATT MCA MINIMUM CIRCUIT AMPACITY MINIMUM CIRCUIT AMPACITY MCB MAIN CIRCUIT BREAKER MAIN CIRCUIT BREAKER MCC MOTOR CONTROL CENTER MOTOR CONTROL CENTER MCP MOTOR CIRCUIT PROTECTOR MOTOR CIRCUIT PROTECTOR MDP MAIN DISTRIBUTION PANEL MAIN DISTRIBUTION PANEL MLO MAIN LUGS ONLY MAIN LUGS ONLY MS MOTOR STARTER MOTOR STARTER MTD MOUNTED MOUNTED NEC NATIONAL ELECTRICAL CODE NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL MANUFACTURER NATIONAL ELECTRICAL MANUFACTURER ASSOCIATION P POLE POLE PH, PHASE PNL PANEL PANEL PRI PRIMARY PRIMARY STRT STARTER STARTER SZ SIZE SIZE TYP TYPICAL TYPICAL UNO UNLESS NOTED OTHERWISE UNLESS NOTED OTHERWISE V VOLT VOLT VA VOLTS-AMPERE VOLTS-AMPERE WP WEATHERPROOF WEATHERPROOF XFMR TRANSFORMERTRANSFORMER
S
PANELBOARD, SURFACE MOUNTED TRANSFORMER DISCONNECT SWITCH COMBINATION MOTOR STARTER MOTOR TOGGLE SWITCH, MOTOR RATED JUNCTION BOX MOUNTED ABOVE CEILING WALL MOUNTED JUNCTION BOX POINT OF ELECTRICAL CONNECTION CONDUIT CONCEALED IN WALL OR CLG. CONDUIT UNDER FLOOR HOMERUN TO PNL WITH (2) #12, #12G IN 3/4"C, UNO. CIRCUIT CONTINUATION DENOTES SCOPE OF DEMOLITION ON RISER
APPLICABLE TO ALL ELECTRICAL SHEETS: 1. ALL WORK SHALL COMPLY WITH NEC, NFPA, AND ALL APPLICABLE FEDERAL CODES. ALL WORK SHALL COMPLY WITH NEC, NFPA, AND ALL APPLICABLE FEDERAL CODES. 2. FIELD VISIT BY INTERESTED CONTRACTORS IS "STRONGLY RECOMMENDED" TO BECOME FAMILIAR WITH THE FIELD VISIT BY INTERESTED CONTRACTORS IS "STRONGLY RECOMMENDED" TO BECOME FAMILIAR WITH THE COMPLEXITIES OF THIS PROJECT AND THE NECESSARY CONSTRUCTION CONSTRAINTS. 3. ALL BRANCH CIRCUITS SHALL BE RUN WITH DEDICATED NEUTRALS: NO SHARED NEUTRALS. ALL BRANCH CIRCUITS SHALL BE RUN WITH DEDICATED NEUTRALS: NO SHARED NEUTRALS. 4. IT IS ANTICIPATED THAT ANY CRITICAL WORK (SHUTDOWNS, ETC.), AFFECTING OTHER AREAS, WILL BE DONE DURING IT IS ANTICIPATED THAT ANY CRITICAL WORK (SHUTDOWNS, ETC.), AFFECTING OTHER AREAS, WILL BE DONE DURING OFF HOURS (NIGHTS, WEEK-ENDS, HOLIDAYS, ETC.) AND INTERESTED CONTRACTORS SHOULD PLAN ACCORDINGLY. A TWO (2) WEEK ADVANCE NOTIFICATION IS REQUIRED. INTENSIVE PLANNING IS REQUIRED TO ALLOW SCHEDULED WORK TO BE ACCOMPLISHED DURING SCHEDULED SHUTDOWN PERIODS. 5. ALL EXISTING CIRCUITS THAT ARE TO BE RE-FED, ARE TO BE INTERCEPTED AT THE CLOSEST POSSIBLE POINT OF ALL EXISTING CIRCUITS THAT ARE TO BE RE-FED, ARE TO BE INTERCEPTED AT THE CLOSEST POSSIBLE POINT OF THE EXISTING CIRCUIT SOURCE (ELECTRICAL CLOSET, PANELBOARD, DISCONNECT, ETC.) TO MINIMIZE DISRUPTION WHILE REPLACING FEEDER CIRCUITS. 6. IT IS ANTICIPATED THIS PROJECT MAY INVOLVE WORK ON OR VERY NEAR LIVE CIRCUITS. ANY SUCH WORK WILL IT IS ANTICIPATED THIS PROJECT MAY INVOLVE WORK ON OR VERY NEAR LIVE CIRCUITS. ANY SUCH WORK WILL REQUIRE A WRITTEN, TASK SPECIFIC, DETAILED PLAN OF ACTION THAT IS AGREEABLE TO BOTH THE CONTRACTOR AND COR, SIGNED BY BOTH, AND SUBMITTED TWO (2) WEEKS PRIOR TO STARTING THE TASK. ALL ELECTRICAL WORKERS SHALL MEET THE MINIMUM TRAINING/EXPERIENCE REQUIREMENTS AS DESCRIBED IN THE SPECIFICATIONS. CONTRACTOR SHALL BE TRAINED ON ARC FLASH SAFETY PROCEDURES AND SHALL POSSESS THE PROTECTIVE EQUIPMENT. CONTRACTOR SHALL COMPLY WITH THE VAMC INTERNAL PROCEDURES FOR WORKING ON ENERGIZED CIRCUITS. ENERGIZED WORK SHALL FOLLOW REQUIREMENTS OF NFPA 70E AND VA FMS SOP NO. 7. 7. ALL PATIENT CARE AREAS MUST COMPLETE EQUIPOTENTIAL TESTING/CERTIFICATION, PRIOR TO RETURNING TO ALL PATIENT CARE AREAS MUST COMPLETE EQUIPOTENTIAL TESTING/CERTIFICATION, PRIOR TO RETURNING TO OPERATIONAL STATUS. 8. ALL CONDUITS SHALL BE CLEAN AND FREE OF DEBRIS PRIOR TO INSTALLING NEW CONDUCTORS. ALL CONDUITS SHALL BE CLEAN AND FREE OF DEBRIS PRIOR TO INSTALLING NEW CONDUCTORS. 9. ALL CONDUCTORS SHALL BE INSTALLED IN CONDUIT. GENERAL DESIGN INTENT IS TO USE EMT WITH COMPRESSION ALL CONDUCTORS SHALL BE INSTALLED IN CONDUIT. GENERAL DESIGN INTENT IS TO USE EMT WITH COMPRESSION FITTINGS FOR INTERIOR SPACES, RMC WITH THREADED FITTINGS FOR ABOVE GROUND EXTERIOR. 10. ELECTRICAL DEVICES SHALL BE FED WITH (1) #12, (1) #12 N, AND (1) #12 G, UNO. ELECTRICAL DEVICES SHALL BE FED WITH (1) #12, (1) #12 N, AND (1) #12 G, UNO. 11. ALL WORK ABOVE EXISTING AND NEW ELECTRICAL EQUIPMENT SHALL BE PLANNED SUCH THAT THERE IS NO ALL WORK ABOVE EXISTING AND NEW ELECTRICAL EQUIPMENT SHALL BE PLANNED SUCH THAT THERE IS NO CLIMBING OR STANDING ON ELECTRICAL EQUIPMENT. FURNISH AND INSTALL TEMPORARY SCAFFOLDING AS REQUIRED. WORK ABOVE OR AT THE TOP OF EQUIPMENT SHALL BE PERFORMED IN A MANNER THAT PREVENTS DEBRIS AND DROPPED PARTS FROM ENTERING THE EQUIPMENT. PROVIDE TEMPORARY PROTECTION FOR EQUIPMENT AS REQUIRED, HOWEVER DO NOT BLOCK EQUIPMENT VENTILATION OPENINGS. 12. THE CONTRACTOR SHALL NOT OPERATE ANY EXISTING EQUIPMENT INCLUDING, BUT NOT LIMITED TO BREAKERS, THE CONTRACTOR SHALL NOT OPERATE ANY EXISTING EQUIPMENT INCLUDING, BUT NOT LIMITED TO BREAKERS, DISCONNECT SWITCHES, ETC., WITHOUT AUTHORIZATION FROM THE VAMC ENGINEERING SERVICE, UNLESS AN EMERGENCY SITUATION EXISTS. IN GENERAL, THE OPERATING STAFF OF THE VAMC ENGINEERING SERVICE WILL OPERATE ANY EXISTING EQUIPMENT WHICH THE CONTRACTOR MAY REQUIRE. 13. IF AN OBSTRUCTION SHOULD BE ENCOUNTERED THAT REQUIRES A DEVIATION FROM THE ORIGINAL PLANS, THE IF AN OBSTRUCTION SHOULD BE ENCOUNTERED THAT REQUIRES A DEVIATION FROM THE ORIGINAL PLANS, THE CONTRACTOR SHALL CONTACT THE COR AND ENGINEER FOR GUIDANCE. 14. PRINTED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON CONSTRUCTION DOCUMENTS. THE PRINTED DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALES SHOWN ON CONSTRUCTION DOCUMENTS. THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE DOES NOT WARRANT THE ACCURACY OF SCALED DIMENSIONS. 15. OMISSIONS IN AND CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE CONSTRUCTION DOCUMENTS SHALL BE OMISSIONS IN AND CONFLICTS BETWEEN THE VARIOUS ELEMENTS OF THE CONSTRUCTION DOCUMENTS SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE ENGINEER AND COR. CONFLICTS SHALL BE RESOLVED BY THE SAME BEFORE PROCEEDING WITH ANY WORK INVOLVED. 16. THE CONTRACTOR SHALL BECOME FAMILIAR WITH ALL PORTIONS OF THE CONSTRUCTION DOCUMENTS AND SHALL THE CONTRACTOR SHALL BECOME FAMILIAR WITH ALL PORTIONS OF THE CONSTRUCTION DOCUMENTS AND SHALL ENSURE THAT ALL SUBCONTRACTORS ARE FAMILIAR WITH THOSE PORTIONS PERTAINING TO THEIR AREA OF WORK. THE CONTRACTOR SHALL VERIFY ALL SITE CONDITIONS, DIMENSIONS, ELEVATIONS, COORDINATE ALL DOORS, WINDOWS, NON-BEARING INTERIOR AND EXTERIOR WALLS, ELEVATIONS, SLOPES, STAIRS, CURBS, DRAINS, RECESSES, DEPRESSIONS, RAILINGS, WATERPROOFING, FINISHES, CHAMFER, KERFS, AND SO FORTH, AND IMMEDIATELY NOTIFY THE REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE REGARDING ACTUAL CONDITIONS WHICH ARE NOT IN AGREEMENT WITH THE CONSTRUCTION DOCUMENTS. 17. CONTRACTOR SHALL MAKE PROVISIONS PER CODE AND SPECIFICATIONS FOR ALL EXPANSION JOINT CROSSINGS. CONTRACTOR SHALL MAKE PROVISIONS PER CODE AND SPECIFICATIONS FOR ALL EXPANSION JOINT CROSSINGS. 18. PROPOSED RACEWAY ROUTING FOR CONDUITS 2" AND LARGER IS SHOWN ON THE PLANS. RACEWAY ROUTING PROPOSED RACEWAY ROUTING FOR CONDUITS 2" AND LARGER IS SHOWN ON THE PLANS. RACEWAY ROUTING DEPICTED ON PLANS IS APPROXIMATE AND DIAGRAMMATIC. CONTRACTOR SHALL PROVIDE ALL OFFSETS AND PULLBOXES AS REQUIRED BY EXISTING CONDITIONS AND NEC TO ACCOMPLISH INSTALLATIONS. ALTERNATE ROUTING DIAGRAMS MAY BE CONTRACTOR-PROPOSED, CONTRACTOR-DESIGNED, CONTRACTOR-DRAWN, AND CONTRACTOR-SUBMITTED TO COR FOR REVIEW AND APPROVAL; ALTERNATE ROUTINGS WILL ONLY BE CONSIDERED IF ALTERNATE REQUIRES NO ADDITIONAL COST TO THE GOVERNMENT. CONTRACTOR SHALL PROVIDE ALL FIELD INVESTIGATION AND COORDINATION AS REQUIRED TO COMPLETE THE CONDUIT RUNS (FROM START TO END). 19. ALL CONDUITS SHALL BE INSPECTED BY COR, ELECTRIC SHOP, AND IRMS (IF APPLICABLE) PRIOR TO CLOSING WALLS ALL CONDUITS SHALL BE INSPECTED BY COR, ELECTRIC SHOP, AND IRMS (IF APPLICABLE) PRIOR TO CLOSING WALLS (TO CONFIRM BENDS, CONDUIT TYPES, BOXES, FITTINGS, ETC.) CONTRACTOR SHALL COORDINATE WITH VA FOR NECESSARY INSPECTIONS AND SHALL OBTAIN SIGNATURES UPON INSPECTION COMPLETIONS. 20. CONTRACTOR SHALL PROVIDE INFRARED SCANNING SERVICES TO CONFIRM TEMPERATURES AT ALL FINAL SPLICES AND CONTRACTOR SHALL PROVIDE INFRARED SCANNING SERVICES TO CONFIRM TEMPERATURES AT ALL FINAL SPLICES AND CONNECTIONS. 21. ALL NEW CIRCUIT BREAKERS RATED 225A AND LARGER SHALL BE 100% RATED WITH SOLID STATE LSIG TRIP UNITS.ALL NEW CIRCUIT BREAKERS RATED 225A AND LARGER SHALL BE 100% RATED WITH SOLID STATE LSIG TRIP UNITS.
FITTINGS SHALL BE PAINTED IN ACCORDANCE WITH BRANCH CLASSIFICATION. ALTERNATIVELY, CONDUIT MAY BE PAINTED WITH 3" WIDE STRIPS AT 8' MIN. INTERVALS, WITHIN 12" OF WALL PENETRATIONS, AND WITHIN 6" OF CONDUIT TERMINATIONS. (LS) LIFE SAFETY YELLOW LIFE SAFETY YELLOW YELLOW (CRIT) CRITICAL ORANGE CRITICAL ORANGE ORANGE (EQUIP) EQUIPMENT GREEN EQUIPMENT GREEN GREEN (NORM) NORMAL BLACK NORMAL BLACK BLACK (ESS) ESSENTIAL PURPLE ESSENTIAL PURPLE PURPLE FIRE ALARM RACEWAY (AND BOXES) SHALL BE RED PER SPECS
1. THE CONTRACTOR SHALL NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL-INCLUSIVE. IT IS THE CONTRACTOR'S THE CONTRACTOR SHALL NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL-INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH AREA AND TO FULFILL THE INTENT OF THE DESIGN INDICATED BY THE CONTRACT DOCUMENTS. REFER TO SPECIFICATION SECTION 010000 - GENERAL REQUIREMENTS AND THE VA MEDICAL CENTER FOR WORK RESTRICTIONS. CONTRACTOR SHALL COORDINATE DEMOLITION DRAWINGS AND NOTES WITH ALL DISCIPLINES INVOLVED. PATCH OR REBUILD ANY AREAS TO REMAIN THAT HAVE BEEN DAMAGED OR DISTURBED BY DEMOLITION. 2. REMOVE ALL EXISTING CONSTRUCTIONS AND FINISHES NECESSARY FOR THE COMPLETION OF THE WORK AS DEPICTED ON THE DRAWINGS. REMOVE ALL EXISTING CONSTRUCTIONS AND FINISHES NECESSARY FOR THE COMPLETION OF THE WORK AS DEPICTED ON THE DRAWINGS. INCLUDING BUT NOT LIMITED TO, ITEMS SHOWN ON THE PLANS. NECESSARY DISCONNECTS AND ALTERATIONS TO EXISTING MECHANICAL AND ELECTRICAL SYSTEMS SHALL BE INCLUDED. PATCH AS REQUIRED ALL CONSTRUCTIONS TO REMAIN IN ACCORDANCE WITH THE CONTRACT DRAWINGS. WHERE CONTRACTOR IS DESIGNATED TO MAKE REMOVALS, DISPOSITION OF MATERIALS IS THE RESPONSIBILITY OF THE CONTRACTOR. VERIFY WITH VA MEDICAL CENTER, THE DISPOSITION AND REMOVAL OF ANY COMPONENTS OF SALVAGEABLE VALUE. 3. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS WITHIN THE CONTRACT LIMITS AND NOTIFY THE COR IMMEDIATELY IN THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS WITHIN THE CONTRACT LIMITS AND NOTIFY THE COR IMMEDIATELY IN WRITING OF ANY DEVIATION FROM CONTRACT DOCUMENTS NECESSITATED BY FIELD CONDITIONS OR ITEMS NOT DEPICTED ON THE DRAWINGS. 4. ALL REMOVALS AND SALVAGE, UNLESS SPECIFICALLY NOTED OR REQUESTED BY THE VA MEDICAL CENTER SHALL BECOME THE PROPERTY OF ALL REMOVALS AND SALVAGE, UNLESS SPECIFICALLY NOTED OR REQUESTED BY THE VA MEDICAL CENTER SHALL BECOME THE PROPERTY OF THE CONTRACTOR. 5. ANY FLOOR OPENINGS SHALL BE PROTECTED AND SECURED DURING DEMOLITION AND CONSTRUCTION. ANY FLOOR OPENINGS SHALL BE PROTECTED AND SECURED DURING DEMOLITION AND CONSTRUCTION. 6. ANY EXTERIOR WALL OPENINGS SHALL BE CLOSED IMMEDIATELY OR BE PROVIDED WITH TEMPORARY WEATHER AND SECURITY PROTECTION IN ANY EXTERIOR WALL OPENINGS SHALL BE CLOSED IMMEDIATELY OR BE PROVIDED WITH TEMPORARY WEATHER AND SECURITY PROTECTION IN ACCORDANCE WITH SPECIFICATIONS. 7. PATCH ALL FINISHES TO MATCH EXISTING, INCLUDING BUT NOT LIMITED TO, GYPSUM BOARD, PLASTER, ACOUSTIC SYSTEMS, WOOD TRIM, PATCH ALL FINISHES TO MATCH EXISTING, INCLUDING BUT NOT LIMITED TO, GYPSUM BOARD, PLASTER, ACOUSTIC SYSTEMS, WOOD TRIM, COVERS, BASE, PANELS, RAILS AND WAINSCOT. FOR ALL SURFACES SCHEDULED TO REMAIN, PATCH AND MATCH SURFACES DISTURBED BY DEMOLITION OR REMOVAL OF EQUIPMENT OR UTILITIES. INSTALL PATCHING TO MATCH ADJACENT WORK IN FINISH, STRUCTURAL QUALITIES, COURSING OF MASONRY, AND OTHER CHARACTERISTICS. VERIFY MATCH OF NEW FINISH MATERIALS TO EXISTING IN COLOR, TEXTURE, THICKNESS, CUT, ETC… TO SATISFACTION OF VA MEDICAL CENTER PRIOR TO INSTALLATION. PROVIDE OTHER MATERIALS TO MATCH EXISTING TO SATISFACTION OF VA MEDICAL CENTER PRIOR TO INSTALLATION. PROVIDE OTHER MATERIALS TO MATCH EXISTING WHEN REQUIRED (TO BE APPROVED BY VA MEDICAL CENTER). PATCH EXISTING WALLS GYPSUM DRYWALL OR PLASTER TO MATCH EXISTING OF SUFFICIENT THICKNESS TO MAINTAIN UNIFORM WALL THICKNESS. ALL EXPOSED PORTIONS OF WALL SHALL BE FINISHED WITH THREE (3) COATS OF SPACKLING, SANDED AND LEFT IN A PAINT READY CONDITION. WHERE APPLICABLE, LEVEL ALL EXISTING FLOORS AS REQUIRED TO RECEIVE NEW FLOOR FINISHES. INSTALL REQUIRED TRANSITION PIECES BETWEEN VARIOUS FLOOR FINISHES SUITABLE FOR CONDITIONS, MEETING ADA REQUIREMENTS AND ACCEPTABLE TO THE VA MEDICAL CENTER. MATCH EXISTING WHEREVER POSSIBLE. PATCH SURFACES TO COMPLY WITH FIRE RATINGS, SMOKE-TIGHT RATINGS, ACOUSTICAL CRITERIA AND OTHER PERFORMANCE CRITERIA INDICATED. 8. MAINTAIN ACCESS TO EXITS AND EXIT STAIRS AT ALL TIMES. FIRE ALARM AND SMOKE DETECTION SYSTEM SHALL REMAIN OPERATIONAL AT MAINTAIN ACCESS TO EXITS AND EXIT STAIRS AT ALL TIMES. FIRE ALARM AND SMOKE DETECTION SYSTEM SHALL REMAIN OPERATIONAL AT ALL TIMES. PROTECT SMOKE DETECTORS AS REQUIRED AND IN CONFORMANCE WITH CODES AND LOCAL AUTHORITIES HAVING JURISDICTION. REFER TO MEDICAL CENTER CONTRACTOR HANDBOOK FOR WORK RESTRICTIONS. 9. ALL DEMOLITION SHALL BE PERFORMED IN A SAFE AND ACCEPTABLE MANNER TO ALL AUTHORITIES HAVING JURISDICTION AND THE VA ALL DEMOLITION SHALL BE PERFORMED IN A SAFE AND ACCEPTABLE MANNER TO ALL AUTHORITIES HAVING JURISDICTION AND THE VA MEDICAL CENTER. A FIRE WATCH SHALL BE PROVIDED IF ANY HAZARDOUS SITUATIONS ARE THOUGHT TO BE PRESENT OR POSSIBLE. COMPLY WITH GOVERNING REGULATIONS PERTAINING TO ENVIRONMENTAL PROTECTION FOR POLLUTION CONTROL. THOROUGHLY CLEAN ADJACENT AREAS OF DUST, DIRT AND DEBRIS CAUSED BY DEMOLITION WORK. BEFORE NEW WORK BEGINS, RETURN ADJACENT AREAS TO CONDITION FOUND PRIOR TO START OF DEMOLITION WORK. 10. ALL WORK SHALL BE DONE IN PROTECTED SPACE. NO DUST OR DIRT SHALL TRAVEL FROM CONSTRUCTION AREA TO ADJACENT AREAS. ALL WORK SHALL BE DONE IN PROTECTED SPACE. NO DUST OR DIRT SHALL TRAVEL FROM CONSTRUCTION AREA TO ADJACENT AREAS. TEMPORARY DUST PROTECTION SHALL BE ERECTED PRIOR TO START OF WORK. CONTRACTORS SHALL REVIEW PROVISIONS TO CONTROL AIRBORNE DUST WITH INFECTION CONTROL DIRECTOR, FACILITIES-BUILDING MANAGER AND CONSTRUCTION MANAGER. COORDINATE ADDITIONAL FILTRATION OF EXTERIOR AIR INTAKES TO MECHANICAL SYSTEMS. CONTRACTOR SHALL ASSIGN A PERSON(S) TO CLEAN ALL CONSTRUCTION AND COMMON AREAS, USED BY THE CONTRACTOR AND STAFF, DURING THE THE CONSTRUCTION HOURS. 11. PROVIDE TEMPORARY PARTITIONS/DUST PROTECTION (RATED AND/OR NON-RATED) AS REQUIRED. REVIEW LOCATIONS OF TEMPORARY PROVIDE TEMPORARY PARTITIONS/DUST PROTECTION (RATED AND/OR NON-RATED) AS REQUIRED. REVIEW LOCATIONS OF TEMPORARY PARTITIONS/DUST PROTECTION WITH VA MEDICAL CENTER AND COR PRIOR TO START OF WORK. 12. IF HAZARDOUS MATERIAL IS ENCOUNTERED OR SUSPECTED TO BE PRESENT, CONTRACTOR SHALL STOP WORK AND INFORM VA MEDICAL IF HAZARDOUS MATERIAL IS ENCOUNTERED OR SUSPECTED TO BE PRESENT, CONTRACTOR SHALL STOP WORK AND INFORM VA MEDICAL CENTER IMMEDIATELY IN WRITING OF ANY HAZARDOUS MATERIAL ENCOUNTERED OR THOUGHT TO BE HAZARDOUS MATERIAL. THE VA MEDICAL CENTER, AFTER RECEIVING WRITTEN NOTICE SHALL INSTRUCT CONTRACTOR ON HOW TO PROCEED. THIS INCLUDES, BUT IS NOT LIMITED TO PAINT THAT IS SUSPECT ON PIPING, CONDUIT, DUCTWORK OR ADJACENT SURFACES. 13. WHERE REMOVAL OF AN EXISTING CONCRETE HOUSEKEEPING PAD IS CALLED FOR, THE FOLLOWING ITEMS SHALL BE INCLUDED: A) CUT ANY WHERE REMOVAL OF AN EXISTING CONCRETE HOUSEKEEPING PAD IS CALLED FOR, THE FOLLOWING ITEMS SHALL BE INCLUDED: A) CUT ANY VERTICAL REINFORCING STEEL BACK BELOW FINISHED SLAB ELEVATION; B) CUT AND PLUG ANY UNUSED CONDUIT BACK BELOW FINISHED SLAB ELEVATION; C) ENSURE ANY ACTIVE EXISTING CONDUIT TO REMAIN IS NOT DISTURBED DURING DEMO OF THE PAD; D) REPAIR DEMO AREA WITH NEW CONCRETE AND REFINISH PER DIV 3 SPECIFICATIONS.
THIS PROJECT MAY REQUIRE NEW PENETRATIONS THROUGH EXISTING CONCRETE FLOORS. PRIOR TO LAYOUT AND INSTALLATION OF NEW CONDUIT REQUIRING NEW PENETRATIONS OF EXISTING CONCRETE FLOOR SLABS, THE CONTRACTOR SHALL SUBMIT TO THE COR THE TESTING AND INVESTIGATION SERVICE (TIS) WHICH WILL BE USED TO LOCATE THE EXISTING SLAB REINFORCEMENT FOR APPROVAL. THE TIS SHALL HAVE A MINIMUM OF 5 YEARS OF EXPERIENCE IN THE USE OF X-RAY AND GROUND PENETRATING RADAR (GPR). THE CONTRACTOR SHALL SUBMIT THE INVESTIGATIVE TESTING SERVICES WORK PLAN AND SCHEDULE FOR APPROVAL. THE TIS SHALL USE X-RAY, GPR OR OTHER SUITABLE NON-DESTRUCTIVE TESTING METHODOLOGY TO ACCURATELY IDENTIFY THE SLAB REINFORCING, FROM WHICH ADJUSTMENTS TO THE PENETRATIONS WILL BE MADE SO AS NOT TO COMPROMISE THE STRUCTURAL INTEGRITY OF THE EXISTING CONCRETE FLOOR SLABS. THE X-RAY OR GPR SHALL BE A CONTINUOUS 3-D GRID PROCESS (SCANNING GRID OF 2” ON CENTER) FOR AN AREA OF 24” BEYOND THE PROPOSED PENETRATION IN ALL ON CENTER) FOR AN AREA OF 24” BEYOND THE PROPOSED PENETRATION IN ALL BEYOND THE PROPOSED PENETRATION IN ALL DIRECTIONS. THE IDENTIFIED X-RAY OR GPR OF THE REINFORCING SHALL BE IDENTIFIED BY PENETRATION TYPE AND COLUMN GRID LINE DESIGNATION. THE AREA SHALL BE SURVEYED, MAPPED AND SUBMITTED TO THE COR FOR RECORD PURPOSES. THE REINFORCING SHALL BE MARKED ON THE CONCRETE SLAB AND USE DIFFERING COLORS FOR THE IDENTIFICATION OF TOP AND BOTTOM REINFORCING. THE CONTRACTOR SHALL GIVE THE COR 72 HOURS NOTICE PRIOR TO ANY INVESTIGATIVE TESTING WORK.
Sheets and Views
EP001
2022-03-23T10:43:23-0400
Robert Haffeman
Phone: (352) 474-6124 Fax: (352) 553-4437
MECH ROOM FB29-1
EP724
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
Sheets and Views
EP724
2022-03-23T11:34:18-0400
Robert Haffeman
JN
25 24 23
JN
25 24 23
Phone: (352) 474-6124 Fax: (352) 553-4437
BID DOCUMENTSELECTRICAL PLANS - EB60-1
EP101
FLOOR PLAN - EB60-1 - NEW WORK
EXISTING & DEMOLITION PLAN - EB60-1
KEY PLAN - BLDG 1 BASEMENT
MCC-E2
MCC-Q
MCC-N
CTRL RELAYS
DWP CP
AC-4
AC-4E
AC-4E SF VFD
HWP-1&2 VFD
AC-4 SF VFD
ORAL EVAC CNTRL
HONEYWELL CP
HWP-2
HWP-1
HWP-3
HWP-4
AIR COMP
AIR COMP CONTROLLERS
CP-5 MS
FLR CAB
AC4E-EF-1 (VFD)
AC4E-RHE-1 (VFD)
METAL CATWALK
AC-4E SOURCE MTS
PNL AC-4E
AC-4E EF VFD
ERV-4E VFD
H-N
H-Q
L-E2
XF-E2
H-E2
AC-4E
ORAL EVAC COMP
CTRL RELAYS
AC-4
AC-4 SF VFD
DWP CP
HWP-2
HWP-1
HWP-3
HWP-4
CONTROLLERS
CP-5 MS
AC-4E SF VFD
AC-4E EF VFD
ERV-4E VFD
HWP-1&2 VFD
AC-4E SOURCE MTS
PNL AC-4E
HONEYWELL CP
This item has been electronically signed and sealed by the individual named at right. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
A. NOT USED.NOT USED.
1. COORDINATE WITH THE VA FOR THE COORDINATE WITH THE VA FOR THE RELOCATION OF FLOOR SHELVING/CABINET. 2. REMOVE EXIST HOUSEKEEPING PAD. REMOVE EXIST HOUSEKEEPING PAD. REFINISH CONC FLOOR SLAB TO MATCH SURROUNDING CONDITIONS.