Industrial Water Treatment and Preventive Maintenance Services

Phoenix Indian Medical Center

RFQ-19-PHX-16

4/23/2019

QUESTIONS

No. Vendor Question Government Response 1 What is the tonnage of the cooling towers?

500 Tons Each

2 What is the horse power of each boiler? 1. 6900 steam lbs/hr

2. 8625 steam lbs/hr

3 Does the Indian Health Service own all of the equipment that is on site? (i.e. the chemical pumps, day tanks, controllers)

The chemical feed pumps are not owned by the Phoenix Indian Medical Center.

4 What (if any) oxidizing biocide are you currently using in your condenser cooling water system? The only one noted during the site visit was Isothiazoline non oxidizing biocide.

K-BAC 7015-Biocide, CT-535-Cooling Water Treatment(Amino Mixture) ACT(Advanced Chemical Technology, Inc.)

5 What is the tonnage of the two (2) chillers?

500 Tons Each