Solicitation No. R15PS00515 Chandler Trash Rake
Amendment 001
A. Project Title: R15PS00515 Chandler Trash Rake
B. Acknowledgement: Vendors must acknowledge this amendment in an email to cgordon@usbr.gov
C. Summary of Changes: Statement of Work (SOW) has been revised, with an effective date of 9 June 2015, please see attachment. Please ensure updated SOW is used in establishment of quote.
D. Request for Quote Date: The deadline for the quote is not being extended as a result of this amendment. Quotes are due no later than 1:00pm Mountain Time, 23 June 2015
Attachment
R15PS00515
Chandler Trash Rake, Yakima, WA
Page 1 of 27 (revised) Attachment A
STATEMENT OF REQUIREMENTS
US BUREAU OF RECLAMATION
YAKIMA FIELD OFFICE
CHANDLER TRASH RAKE REPLACEMENT
9 June 2015
Background The Chandler Screen site was designed and built in 1986 as a complete system to screen anadromous fish species. Part of the system includes a mechanical raking system to clean debris from the trash rack that is located approximately 100 yards upstream of the fish facility.
The system installed and currently in use is an Atlas Polar Mdl. ST8000 and has now performed beyond the estimated capacity and must be replaced.
Site Visit Offerors are strongly urged to participate in the site visit. Failure by bidders to inspect the site will not relieve them of the responsibility of properly estimating the difficulty or cost of successfully performing the work in accordance with the specifications and within the allowed time. Attendees are to provide and wear safety boots, hard hats, safety glasses with side shields, and safety vests.
Date: June 3, 2015 Time: 9:00 AM Place: The site located at 990 Grande Road, Prosser, Washington 99350
General Supply, deliver, and provide technical assistance with installation (installation will be performed by Reclamation) and start up for a complete trash rake system to include:
1. Heavy running rail system w/supports.
2. Auto/manual PLC controls
3. Festoon power and control cables
4. Outdoor weatherproof control enclosure
5. O/M manuals w/ as-built drawings
6. O/M school at installation completion
7. Spare parts
8. Handheld controller/remote.
Description of work Reclamation responsibility:
Reclamation will decommission the existing trashrake rake including disconnection of power, draining of fluids, etc.
Disassemble and remove existing trashrake rake including rake, boom, drive motors, festoon system, travel beam, and structural steel frame work.
Vendor responsibility:
Provide a complete trash rake system to include: rake, boom, drive motors, festoon system, travel beam, travel beam support system, control cabinet, handheld wireless controls for manual operation, weatherproof electrical plugs and conduits, and all other accessories to make a complete operational system.
Page 2 of 27 (revised) Attachment A
Delivery Delivery of the trash rake shall be NLT 31 October 2015.
References
A. American Welding Society (AWS)
1 . AWS D1.1-06
2 . AWS D1.6-06 Structural Welding Code — Steel Structural Welding Code
B. American Society for Testing and Materials International (ASTM)
1. ASTM A 27-05 Steel Castings, Carbon, for General Application
2. ASTM A 36-05 Carbon Structural Steel
3. ASTM A 53-05 Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
4. ASTM A 108-03e1 Steel Bar, Carbon and Alloy, Cold-Finished
5. ASTM A 269-04 Seamless and Welded Austenitic Stainless Steel Tubing for General Service
6. ASTM A 276-06 Stainless Steel Bars and Shapes
7. ASTM A312/A312M-06 Seamless, welded, and Heavily Cold Worked Austenitic Stainless Steel pipe
8. ASTM A 325-04b Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength
9. ASTM A 500-03a Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes
10. ASTM A 513-00 Electric-Resistance-Welded Carbon and Alloy Steel Mechanical Tubing
11. ASTM A 519-03 Seamless Carbon and Alloy Steel Mechanical Tubing
12. ASTM A 588-05 High-Strength Low-Alloy Structural Steel with 50 ksi 345 MPa Minimum Yield Point to 4 in. [100 mm] Thick
13. ASTM B 150-03 Aluminum Bronze Rod, Bar, and Shapes
C. National Electrical Manufacturer's Association (NEMA)
1. NEMA FU 1-2002 Low Voltage Cartridge Fuses
2. NEMA ICS 2-2000 Industrial Control and Systems: Controllers, Contactors and Overload Relays, Rated 600 Volts
3. NEMA ICS 5-2000 Industrial Control and Systems: Control Circuit and Pilot Devices
4. NEMA 250-2003 Enclosures for Electrical Equipment (1000 VoltsMaximum)
5. NEMA MG 1-2003 Motors and Generators
D. Joint Standard Society for Protective Coatings (SSPC)/NACE International (NACE):
1. SSPC-SP6/ NACE No. 3-94 Joint Surface Preparation Standard - Commercial
Blast Cleaning
2. SSPC-SP11-95 Power Tool Cleaning to Bare Metal
3. SSPC-SP10/NACE No. 2-94 Joint Surface Preparation Standard - Near-White Blast Cleaning
4. SSPC-SP7/NACE No. 4-94 Joint Surface Preparation Standard - Brush-Off Blast C leaning
5. SSPC-SP3-95 Power Tool Cleaning
Page 3 of 27 (revised) Attachment A
Solicitation Submittals
1.
Commercial product data; for all products provided
2.
Coatings / Paint
Product data
3.
Manufacture and delivery schedule
4.
Water level sensors
Make and model
5.
Inductive Proximity Sensor
Make and model
PERFORMANCE CRITERIA
A. Automated raking device: The unit shall rake all portions of the trashrack and deposits the debris back onto the trash bridge. The rake uses a cyclical raking motion that resembles manually hand-raking the trashrack. The cleaning and travel motion to not cause shock, vibration, or jarring of the trash raking mechanism or travel beam.
B. Raking cycle:
1. The parked position of the trash rake shall be over land on the left bank side of the trash racks. The trash rake shall be above and slightly downstream of the top of the trash rack when traveling.
2. When activated the trash rake will be lowered to the programmed cleaning level.
3. Apply the trash rake to the existing trashrack.
4. Rake upwards to remove trash
5. Deposit the trash onto the trash bridge
6. After one trash rack bay has been raked, travel to the next bay.
7. The trash rake system will be programmed to move from the right bank to left bank sides of the trash racks.
8. The completion of the cycle shall include repositioning the trash rake in the parked position, discussed in item 1.
C. Cleaning cycle:
1. Sound the alarm for 2 seconds.
2. Perform one rake cycle after another until the entire surface of the trashrack has been cleaned.
3. Move onto the next trashrack and perform rake cycles until all surfaces of all trashrack have been cleaned.
4. Return to the park position.
D. Continuous mode of operation: The rake to continuously perform one cleaning cycle after another.
E. Respond to a remote contact from the emergency stop safety switch. Contact closure from the emergency stop safety switch will immediately stop the rake. After an emergency stop is initiated by the remote contact from the emergency stop safety
Page 4 of 27 (revised) Attachment A switch, operation of the rake will be permitted to resume only after manually resetting the latch of the safety switch.
F. Manual mode of operation: The rake to be operated with hand-held, controller/remote.
G. OFF/AUTO/CONTINUOUS/MANUAL/LOCAL
H. Control travel back and forth along the travel beam.
I. Raise and lower the rake head.
DESIGN CRITERIA
Total track length = 135’ (approx.)
Total reach length of 18-20’ (approx.)
Main trashrake chassis beam/track must be able to span 38+ feet
A. Work with existing onsite power, 480v 3 phase.
B. Lockable main electrical power disconnect.
C. Double boom shall include:
1. Minimum 4,000 lbs. lift capacity.
2. 300-500 psi raking rack pressure.
3. Minimum 6 foot wide rake head.
D. PLC controls.
E. HMI touch screen panel for setting automatic start times and raking depths.
F. Multiple raking stations along the racks that allow for manual changes or adjustments.
G. Programmable automatic starts times.
H. Capable of being connected to depth sensors and starting automatically:
1. If the trash racks become plugged while the rake is in between cycles and the depth sensors detect a differential at the racks the rake will start automatically.
I . Variable raking depths w/certain stations set to a permanent depth.
J . Positive chain drive system to move the rake chassis.
K. Capable of raking in both directions of travel when on auto or continuous.
L. Inductive sensors for raking stations and depths.
M. Service access platform on rakes chassis.
Page 5 of 27 (revised) Attachment A
N. Use existing concrete piers, trash racks, structure, and trash bridge. Assume 4000 psi compressive strength concrete.
O. Main trash rake chassis beam/track must be able to span a minimum of 38 feet.
P. Minimum running distance of 120 feet.
Q. Must be able to dump all debris on trash bridge without snags.
R. Slack cable sensor.
S. Minimum 7 foot chassis and chassis beam/track height above the trash bridge deck.
T. Must function in all weather conditions:
1. Heaters on the raking booms at the boom rollers, and on the hydraulic oil tank.
2. Hydraulic oil suitable for winter operations down to 20 deg. F.
3. Hydraulic oil must have the proper viscosity to operate at low temperatures and move through the components without causing an overload or bypass condition.
U. Hydraulic oil suitable for over water
V. Overload protection for the hydraulic, electrical, and travel systems.
Differential Water-Level System
A. The differential controller shall be capable of operating outdoors in ambient temperatures ranging between -40° to 185°F. The continuous level transmitters shall be capable of operating outdoors in temperatures ranging between -40° to 170°F.
B. Electrical power at 120 VAC shall be provided at the differential controller in accordance with project drawings.
C. Provide equipment better than or equal to Milltronics Corporation: Model AirRanger
DPL
Plus ultrasonic level measurement system with EchomaX XPS-10 transducers, or approved equal with the following salient characteristics:
1. The system electronics shall accept two 4-20ma inputs from the transducers and shall provide for display the surface elevation at each sensing unit, the differential between sensing units and preset differential alarm points.
2. The system shall be designed to operate with an adjustable range of between 1 foot and 30 feet and shall be accurate to within 1/4-inch at each transducer.
3. The system shall provide a minimum of one 4-20ma outputs proportional to the differential for use by external systems, such as auxiliary read-outs or analog inputs to PLC devices.
4. The system shall provide 5 high/low adjustable alarm points providing dry contacts for telephone dialers, PLC devices, or auxiliary equipment.
Page 6 of 27 (revised)
Inductive Proximity Sensor
A. Provide equipment as manufactured by Automation Direct, 3505 Hutchinson Road, Cumming GA 30040, (800) 633-0405: Model PKW-0N-2H inductive proximity sensor with cable CD12L-0B-070-C0 or approved equal with the following salient characteristics:
1. Sensor shall have IP67/68 protection rating and stainless steel housing for harsh environments.
2. Sensor shall be provided with a factory quick disconnect-type connector.
3. Sensor shall have a minimum sensing distance of 0.3-inches.
4. Largest target required for proper sensing shall be a 1-inch square iron plate 1/16-inch thick.
5. Sensor output shall be standard dry contact
Delivery and Handling
A. Protect equipment from corrosion, deformation, and other types of damage while in transit.
B. All Products shall be delivered to 990 Grande Road, Prosser, Washington 99350 attn.
Kevin Yancy (509) 575-5848 ext. 256
Spare Parts as stated or recommended by the manufacturer
A. Spare parts shall be provided in a metal box.
B. Spare parts shall include but not be limited to the following:
1. One spare operating coil for each type of motor contact.
2. Three spare renewable contacts for each type of motor contact.
3. Six spare fuses of each type of fuse.
4. One limit switch of each type.
5. Three high-pressure filter elements and one suction strainer element.
6. Two indicating lamps of each type used.
7. One color cap for the indicating lamps of each type used.
Trash Rake System
The trash rake system can be either a hydraulic or electric operated or a combination of both.
Controls
A. Control Panel:
1. General: Furnish the control panel. All electrical controls in a single control cabinet.
2. Lockable enclosure.
3. The control devices mounted on an inner door that provides a dead-front panel or box for the operator, with all the necessary relays, contacts, and timers for complete operation of the unit.
4. An alarm light at the control panel to indicate a unit stop in mid-cycle, overload tripping of any motor, or timer feedback with provisions for an alarm signal to a remote location.
Page 7 of 27 (revised) Attachment A
5. Provide a master OFF/AUTO/CONTINUOUS/MANUAL/LOCAL selector switch at the control cabinet:
a. In the OFF position, the drive motors stop, and will not start in response to any automatic or manual operation.
b. In the Auto setting, the trash rake will run off of the programming (time delay or head differential) only.
c. In continuous setting, the trashrack rake works continuously only.
d. In the manual/local setting, rake works only from the manual control.
6. Provide an EMERGENCY STOP pushbutton and manual RESET pushbutton. The EMERGENCY STOP pushbutton to be the latching,mushroom head type pushbutton.
7. MANUAL position — Rake controlled by a manually operated pushbutton station from wireless controller. This mode locks out all other modes of operation. Controls the following:
a. ON/OFF
b. TRAVEL RIGHT/LEFT pushbuttons to provide manually control travel back and forth along the travel beam.
c. RAKE UP/DOWN pushbuttons to provide raising and lowering of the rake head.
d. EMERGENCY STOP pushbuttons to provide emergency stopping and resetting of the rake.
e. Contact closure from the transporter emergency stop safety switch will immediately stop the operation of the trash rake.
8. Transporter start signal relay.
9. Provide contacts (for future use) and install in control panels for the following conditions:
a. "Manual," "Continuous," or "Automatic" mode of operation.
b. Status of main power disconnect.
10. Disconnect switch:
a . Horsepower rated.
b . Unfused.
c . Heavy-duty industrial type.
d . Rated 600-volts, 3-pole, single throw.
e . Mounted in the trash rake control panel and lockable in the open position.
11. Contactor:
a. Magnetic, ali--bieak, full-voltage type.
b. Power supply: 120-volts, alternating current, 60-hertz.
c. Thermal overloads provided in each phase.
12. Enclosure:
a. NEMA type 4.
b. Outdoor use, rigid, and dead-front type with swing-out panel.
13. Control panel for full programmable unattended operation and include overload protection for the entire control system.
Page 8 of 27 (revised) Attachment A
14. Provide an automatic stop if the unit is jammed or overloaded. Provide interlocks to prevent travel of the assembly while the trash rake is being raised or lowered in continuous or AUTO modes.
15. Provide control circuit transformers, with double-pole circuit breakers, of adequate capacity to carry the maximum circuit load. The control circuit through the pushbutton control panel to be 120 volts.
16. All wiring connections to be front connected and wired to a terminal block within the cabinet. An electrical diagram of the system shall be mounted in the cabinet.
17. Manually-Operated Wireless Hand-Held Pushbutton Station: Provide the hand-held pushbutton controller (pendant) with the following:
1. 300 foot (minimum) wireless control distance.
2. A lockable, steel enclosure to store the wireless controller, charging unit, and power cord when not in use.
3. The wireless pushbutton controller to allow manual operation of the trash rake.
4. The wireless controller charging station and power cord.
5. The manually-operated wireless pushbutton station to be provided with the following:
a. ON/OFF/AUTO pushbuttons or selector switch to start/stop the hydraulic motors.
b. TRAVEL RIGHT and TRAVEL LEFT pushbuttons. Pushbuttons to be momentary contact type pushbuttons.
c. Rake UP and rake DOWN pushbuttons to provide raising and lowering of the trash rake head.
d. EMERGENCY STOP pushbutton.
18. Mechanical equipment to be simple and substantial in design, easily assembled, inspected, adjusted, painted, and taken apart.
Programmable Controllers, Auto Dialer and Transient Voltage Surge Supressor
The Contractor shall furnish a transient voltage surge suppressor (TVSS), a programmable logic controller (PLC), a touch panel for user interface, and an autodialer.
Touch panel shall be programmable to allow user to configure for changing operation requirements.
References:
A. National Electrical Manufacturers Association (NEMA):
1. NEMA ICS 1-93 Industrial Control and Systems General Requirements
2. NEMA ICS 3-93 Industrial Control and Systems Factory Built Assemblies
3. NEMA ICS 6-93 Industrial Control and Systems Enclosures
B. National Fire Protection Association (NFPA):
1. NFPA 70-99 National Electrical Code (NEC)
Regulatory requirements
A. Conform to requirements of NFPA 70.
B. Furnish Products listed and classified by Underwriters Laboratories, Inc. as suitable for purpose specified and indicated.
Page 9 of 27 (revised)
Qualifications
A. Manufacturer: Company specializing in manufacturing the Products specified in this section with minimum five years documented experience.
B. Supplier: Authorized distributor of specified manufacturer with minimum five years documented experience.
Environmental Requirements
A. Equipment shall be designed for ambient temperatures between -25°C to 50°C.
Provide proper heating/cooling for equipment to operate within designed parameters.
B. Maintain area free of dirt and dust during and after installation of products.
Mainteance Manuals A. Provide a disk copy of the ladder logic control program.
B. Furnish five enclosure keys of each type.
Transient Voltage Surge Supressor (TVSS)
The TVSS shall be Leviton Manufacturing Co., Inc., Model 51120, or DITEK, DTK 120/240 CM; or equal, with the following salient characteristics:
1.The TVSS device shall feature a multi-component suppression circuit.
2. The TVSS device shall meet the requirements of UL 1449 Transient Voltage Surge Suppressors.
3. The single-pulse peak surge current shall be 50,000 amperes.
4. The clamping voltage at 0.3 kA shall be 330 volts, with rated energy rating of 350 joules.
Programmable Controller
The Programmable Logic Controller (PLC) shall be a GE Fanuc Series 90 - 30 as manufactured by GE Fanuc Automation, ph: 800-648-2001; or approved equal, with the following modules:
1. Two (2) DC Voltage Input Modules, IC693MDL241; or equal, with the following salient characteristics:
a. Input voltage: 0-30.
b. Number of points: 16.
c. Input current: 7 mA.
d. Connector type: Terminal block.
2. Analog Input Module, IC693ALG221; or equal, with the following salient characteristics:
a. Range: 4-20mA or 0-20mA on all channels.
b. Number of channels: 4.
c. Update rate: 2ms all channels.
d. Resolution: 12 bit, 0-20mA (5μA/bit), 4-20mA (4μA/bit).
e. Accuracy: 0.1% full scale.
f. Input Impedance: 250 ohms.
3. Analog Input Module, IC693ALG222; or equal, with the following salient characteristics:
a. Range: -10V to +10V or 0 to +10V on all channels.
b. Number of channels: 16 single ended, 8 differential.
c. Update rate: 13ms all channels.
d. Resolution: 12 bit; ± 10V, 5mV/20μA/bit; 0-10V, 5mv/20μA/bit.
e. Accuracy: 0.25% at 25°C (77°F).
Page 10 of 27 (revised) Attachment A
f. Input Impedance: 250 ohms.
4. Analog Output Module, IC693ALG391; or equal, with the following salient characteristics:
a. Range: 1-5V and 0-5V; 0-20mA and 4-20mA on all channels.
b. Number of channels: 2.
c. Update rate: 5ms all channels.
d. Resolution: 12 bit; 0-20mA, 5μA/bit; 4-20mA, 4μA/bit.
e. Accuracy: 0-20mA, ±8μA at 25° (77°F); 0-20mA, 4-20mA ±0.1% at 25°
(77°F).
f. Maximum output load: 5mA (2K ohms).
g. Output load capacitance: 200pF, Inductance 1H.
5. DC Voltage Output Modules, IC693MDL940; or equal, with the following salient characteristics:
a. Input voltage: 5-30VDC.
b. Number of points: 16.
c. Response time: 15 ms on, 15ms off.
d. Load current per point: 2A.
e. Output type: Relay.
f. Points per common: 4.
g. Connector type: Terminal block.
6. CPU, IC693CPU350; or equal with the following salient characteristics:
a. I/O discreet points: 4096.
b. I/O analog words: 2048 In - 512 Out.
c. Total number of racks: 8.
d. Register memory words: 9999.
e. User logic memory: 32K bytes.
f. Boolean execution speed: 0.22ms/K.
g. Internal coils: 4096.
h. Timers/counters: >2000.
i. Programmable co-processor: yes.
j. Communication options: serial-SNP, SNPX, RTU, CCM, LAN-Genius, Ethernet.
k. Built-in ports: 1.
l. Override: yes.
m. Battery backed clock: yes.
n. Type of memory storage: RAM, Flash, EEPROM.
7. Power Supply, IC693PWR321; or equal with the following salient characteristics:
a. Power source: 120 VAC nominal- 240 VAC nominal - 180 to 264 VAC.
Frequency: 47 to 63 Hz, 125 VDC nominal - 90 to 150 VDC.
b. Input source: 50 watts.
c. Output source: 30 watts total, 15 watts 5V, 15 watts 24V relay, 20 watts 24V isolated.
d. 24 VDC output current capacity: 0.8A.
8. Communication Module, IC693CMM311; or equal with the following salient characteristics:
a. Protocols: SNP/SNPX.
b. Port configuration: Master/Slave.
Page 11 of 27 (revised)
c. Baud rate: Up to 19200.
B. Unit shall be capable of accommodating I/O as required, including:
1. Discrete inputs:
a. Start pushbutton.
b. Stop pushbutton.
c. Selector switch, three position.
d. Limit switch 2.
e. Differential water level system.
f. Programmable touch screen.
2. Discrete outputs:
a. LED status indicators (run and alarm).
b. Motor start.
c. Motor stop.
d. Motor forward.
e. Motor reverse.
C. The PLC shall be furnished with a standard RS232 programming port for insertion of a computer generated control sequence.
D. Supply 10 slot base plate, minimum.
PLC Heating/Cooling
A. The Contractor shall provide heating/cooling to ensure proper operation of the PLC within the a temperature range of -25°C to 50°C. An air conditioning unit shall be side mounted to the PLC enclosure with integral thermostat to maintain constant operating temperature.
Provide McLean Midwest Model CR29-0426-G002, or equivalent with the following characteristics:
1. Minimum of 3500 BTU cooling.
2. 230 VAC, single-phase, 60 Hz.
3. Closed loop cooling.
4. Surface air filters.
5. Standard thermostat control.
6. Solid-state electronic noise suppressor.
7. Ball bearing fans.
B. A thermostatically controlled, fan-driven 200 watt heater shall be provided for the internal heating of the control cabinet. The unit shall be Hoffman Design Aire, Hoffman Engineering Co., or equal with characteristics as described.
Power Supply
A. Input Voltage: 120 volts, 60 Hz.
Programmable User Interface
A. Provide a programmable touch panel as the user interface. Panel to be monochrome back-lit LCD, minimum of 5-inch diagonal dimension. Provide GE Fanuc Model QPJ- 2D100-L2P, or equivalent with the above salient characteristics.
Page 12 of 27 (revised)
Programming Accessories
A. All required equipment, software and connectors shall be provided. Provide a portable computer (laptop type) with all the necessary software installed to program/maintain all elements of the trash rake control system.
Laptop shall be provided with the following as a minimum:
Processor: Pentium II 450MHz, Intel or Intel compatible Operating system: Windows 98 Memory: 64 MB Hard drive: 6 GB CD-ROM: 8x Modem: 56K B.Provide diskette with installed PLC logic sequence for maintenance personnel.
Push Button Units
A. Each unit shall be heavy-duty oil-tight type, contacts shall meet rating designation A600 of part ICS 2-125 of NEMA standards. Unit shall be momentary or maintained-contact type as required. Buttons shall be marked with engraved three-ply nameplate, white lettering on black background.
Indicating Lamps
Indicating lamps shall be furnished as required or indicated in these specifications. The indicating lamp assemblies shall be oil-tight type with color caps. Bulb voltage shall not exceed 125 volts. Lamps shall be LED-type.
Selector Switch
A. Selector switch shall be fully enclosed with 1 amp make/break contact and 10 amp carry, 125 VAC max. Switch shall be single pole and provide 1 or 2 additional positions for future system growth.
Autodialer
A. The autodialer shall have the following characteristics as a minimum:
1. Contact inputs: 4 isolated normally open or closed contacts.
2. Real voice: A user spoken 10 second ID and a total of four independent 6 second fault messages.
3. Call progress decoding: Recognizes busy signal and no answer.
4. Tone or pulse dialing: Programmable.
5. Battery back-up: NiCad battery with internal charger. 24 hour standby with 6 hours active calling.
6. Programming: Configure locally or remotely from standard touch-tone phone.
7. Alarm notification: To either a telephone, cell phone, pager, or answering machine.
8. Acknowledgments: Via a touch-tone phone or user callback.
9. Phone numbers: Up to 8 phone numbers with up to 30 digits each.
10. Common local output: Relay contact output to control onsite alarm.
11. Cellular capability: Can be configured with a cell phone.
12. Auto initiate: Upon power failure with message separate from user alarm messages.
Page 13 of 27 (revised)
Field Quality Control
A. Perform operational testing on control systems to verify proper operation and field wiring connections. Contracting Officer/representative shall be present during system testing.
B. Contractor shall demonstrate operation and programming of controller.
C. Provide 8 hours of instruction each for two persons, to be conducted at project site with manufacturer's representative.
Description of Operations A. The PLC will be programmed by the Contractor for the following functions.
B. In continuous mode:
1. Push buttons start the trashrake operation. The trashrake cycles continuously between proximity sensors until the selector switch is set to “off” or “auto” position.
2. Stop button will initiate immediate mid-cycle motor stop and system will wait until start or return button is activated. Start button will continue trashrake cycle in the same direction while the return button will return the trashrake to the designated park position.
3. Return button will initiate immediate return of trashrake to the designated park position and wait until start button is again activated.
C. In auto mode:
1. Push buttons start trashrake operation for one cycle to remove initial debris.
System then starts interval countdown. When interval has lapsed, the trashrake is activated for one cycle and the process is repeated until selector switch is set to “off” or “continuous”. User inputs run interval via programmable touch panel.
2. Stop button will initiate immediate mid-cycle motor stop and system will wait until start or return button is activated. Start button will continue trashrake cycle in the same direction while the return button will return the trashrake to the designated park position.
3. Return button will initiate immediate return of trashrake cleaner to the designated park position and wait until start button is again activated.
4. Differential water level sensors will immediately activate trashrake until level setpoints are once again achieved. Interval countdown cycle is not interrupted during this process. Sensor level 1 will initiate the trashrake only while sensor level 2 will initiate autodialer as well as trashrake.
D. In the off mode:
1. Start buttons and touch panel, are by-passed. PLC sends a signal to an “off” indicator light (LED). Trashrake lockout is initiated until selector switch is set to auto or continuous.
E. Changing selector switch to “off” position will initiate immediate return of trashrake to designated park position.
F. Indicator lights (LED) will be utilized for all conditions, run, alarm, auto, and/or stop.
Page 14 of 27 (revised) Attachment A
G. Four spare I/O contact points minimum, 2 input and 2 output, shall be provided for future system monitoring/control.
H. The autodialer will be initiated upon PLC failure giving message to indicate such.
I. The autodialer shall have 2 messages for level 2 sensor alarm. One message shall indicate system running normal and cannot maintain clean the trash rack. The other message shall indicate that due to operator input error, selector switch set but no motor initiation, level 2 alarm has occurred.
J. The autodialer shall also initiate if there is a power failure, giving appropriate message.
K. All timer, interval, and speed values necessary for system control and monitoring shall be user input through the programmable touch panel.
L. The motor drive shall provide alarm conditions to the PLC upon initiation of shutdown or other adverse condition. PLC shall initiate autodialer upon such conditions.
M. The water differential system shall provide real-time water level values to the PLC/user interface. The Contractor shall coordinate with the end user for desired units of measure.
Performance And Design Requirements
A. All components shall be balanced so that jamming at any point will not result in structural failure or tipping of the unit. Provide safety interlocks that will prevent the drive motor from stalling.
B. The rake system shall be inherently stable under unbalanced loads and under external design forces, including wind and seismic. The rake trolley unit shall include integral counter weights that offset unbalanced loads associated with the operation of the rake. The rake trolley unit shall include locking devices that transfer overturning forces to the rails for loading combinations that result in overturning safety margin of less than or equal to 2.
C. All components, including the gear reducer, shall be designed to withstand, without damage or permanent distortion, the full stalling torque of the drive motor.
D. All mechanical components shall be readily accessible for maintenance.
E. The trash rake system shall have a minimum lifting capacity of 4,000 lbs. The trash rake system shall be able to clean the trash racks and traverse in wind speeds of up to 70 MPH. The trash rake system shall be designed to withstand 181 mph wind speed, and Exposure “C” parked. Assume 4000psi compressive strength of existing concrete.
F. It is anticipated that the trash rake system can be supported on the existing trash bridge. The footings shall be designed for all operational and gravity loads (dead and live loads), a 181 mph wind speed, and Exposure “C”.
Page 15 of 27 (revised) Attachment A
G. The structural steel frame elements shall be designed in accordance with industry standard design methodologies. The loading shall account for all site conditions, lines, grades, adjacent site features and structures to remain, and the requirements for the trash rake system operation.
H. Coatings / Paint: All exterior / exposed components and equipment without factory finish, whether exposed to water or direct or ultra-violet light.
Items to be coated Manufacture Supplied: coupling housings, pillow-block bearing housings, gearboxes, instrumentation cases, electrical boxes and other associated equipment.
NOTE: Do not paint gear teeth, bolt threads, brass, bronze, stainless steel, galvanized surfaces, seal and bearing contact surfaces, mating machined surfaces, seals, wire rope sockets and pins, and sections of shaft internal to gear reducers.
Manufactures coating system:
1. Factory's standard surface preparation and permanent coating system.
2. Items subject to sunlight are to be top coated with ultraviolet (UV) stable materials.
3. Color and gloss: ANSI #70 light gray or Munsell 5BG 7/0.4, in gloss or semi-gloss.
4. Unless otherwise specified, unexposed surfaces that require coatings, such as interior of cabinets, enclosures, and equipment, are be given the factory’s standard permanent coated finish.
Material
A. Rake unit construction materials shall be as follows:
1. Rake Boom - Hot-dip zinc galvanized steel.
2. Rake – Hot-dip zinc galvanized steel.
3. Raker trolley unit frame - Carbon Steel, ASTM A 36/A 36M, minimum.
4. Rake trolley unit housing – Sheet metal with a powder coating
5. Sprockets – carbon steel
6. Submerged Bearings – carbon steel, water lubricated, babbitt, or Ryertex, with grease fitting.
7. Rake support frame - carbon steel, ASTM A 36/A 36M, minimum.
8. Servicing Platform - Hot-dip zinc galvanized steel.
9. Rake support foundation – Existing concrete trash bridge.
Submittals Due with Delivery of Trash Rake
1.
Detailed design drawings for the Trash Rake.
2.
Electrical control diagrams
Interconnection wiring diagrams and schematics showing all wire connections and conduit layout for all electrical. Provide electrical control schematic diagrams in ladder-logic format
3.
Hydraulic schematics
Show the hydraulic system components and sizes, along
Page 16 of 27 (revised) Attachment A with the operating pressures, capacities, and relief settings.
4.
Calculations
Drive unit, travel beam and support structure, and for the rake carriage, boom, and rake head.
Include calculations for the design of the support of the components to the intake structure. These calculations shall include seismic and wind loads as required by IBC 2012. The support design calculations and drawings shall be signed and stamped by a licensed professional engineer.
5.
Final Drawings and Data
6.
Operational/Service Manuals
Minimum of 6 copies /
a. Operating and maintenance instructions.
b. Full-size prints of detailed shop drawings.
c. Schematics and wiring diagrams.
d. Detailed instructions for installing, operating, lubricating, and maintaining the equipment.
e. Parts identification lists, lists of special tools, and accessories
7.
Electronic drawings
AUTOCAD® format (.dwg) or Drawing Transfer Format
8.
Certified copies of mechanical and electrical tests.
9.
Recommended Spare Parts
Include but not be limited to the following:
1. One spare operating coil for each type of motor contact.
2. Three spare renewable contacts for each type of motor contact.
3. Six spare fuses of each type of fuse.
4. One limit switch of each type.
5. Three high-pressure filter
Page 17 of 27 (revised) Attachment A elements and one suction strainer element.
6. Two indicating lamps of each type used.
7. One color cap for the indicating lamps of each type used.
Installation A. Due to irrigation requirements, installation will begin in late November of the calendar year with the work to be completed within a 20 day window.
B. Installation will be accomplished by Reclamation in accordance with the manufacturer's recommendation and technical assistance
C. Contractor to provide 8 hours of training to Government forces upon completion of installation for proper operation, trouble shooting, inspection, and maintenance.
D. Technical assistance of 24 hours shall be provided only by a skilled technician fully experienced in the installation, start up, and operation of the manufactured unit being proposed. He / she shall instruct Reclamation point of contact with the overall installation, start up, and operation of the unit.
Informational Drawings
A. Drawings marked "For Information Only" in the drawing list are included to show existing features about which knowledge is required to perform work under this contract. These drawings do not show work to be performed under this contract.
B. If there are differences as determined by the CO between details and dimensions shown on these drawings and those of existing features at jobsite, use details and dimensions of existing features at jobsite.
COPIES OF DRAWINGS
A. One set of full-size (22 inches by 34 inches) drawings, except standard drawings, will be furnished to the Contractor.
B. Upon request, additional half-size (11 inches by 17 inches) copies of standard drawings will be furnished to the Contractor.
LIST OF DRAWINGS
A. Drawings listed in Table 52 00 00A - List of Drawings, are made a part of Section C - Description/Specifications.
Yakima Project, Washington
Page 18 of 27 (revised)
Table 52 00 00A - List of Drawings
Sheet No.
Drawing No. Title
General:
33-100-6151
Location Map
2 33-100-1399 Chandler Site Plan
For Information Only:
3 33-D-4035A Chandler Canal Fish Facilities- General Plan and Sections
33-D-4037
Chandler Canal Fish Facilities- Trashrack Bridge Structure Concrete Outline
33-D-4038
Chandler Canal Fish Facilities- Trashrack Bridge Structure- Left Abutment
33-D-4039
Chandler Canal Fish Facilities- Trashrack Bridge Structure- Right Abutment
33-D-4040
Chandler Canal Fish Facilities- Trashrack Bridge Structure- Pier 1 and 2 Plan Elevation and Sections
33-D-4041
Chandler Canal Fish Facilities- Trashrack Bridge Structure- Superstructure Span 1, 2, and 3
33-D-4042
Chandler Canal Fish Facilities- Trashrack Bridge Structure- Superstructure Details
33-D-4043
Chandler Canal Fish Facilities- Trashrack Bridge Structure- Curb and Guardrail
33-D-1394
Canal and Trashrack Modifications at Sunnyside and Chandler- Pier Plans, Sections, and Details
33-D-1397
Plan and Sections
33-D-1393
Plan and Elevations
33-D-1395
Chandler Canal - Sections
END OF SECTION
Page 19 of 27 (revised)
SECTION 51 00 10
PHOTOGRAPHS
Page 20 of 27 (revised)