Wheeled Fire Extinguishers

PERFORMANCE WORK STATEMENT

FOR

UPGRADING WHEELED FIRE EXTINGUISHERS

ON CHANNEL ISLANDS AIR NATIONAL GUARD STATION, CA

1 May 2021

Portable & Wheeled Fire Extinguishers 2

SECTION 1

DESCRIPTION OF SERVICES

1.1. Scope of Work. Furnish all personnel, equipment, tools, materials, supplies, transportation, and labor necessary to perform the Required Upgrade to twenty (20) 150 LBS wheeled Halon Fire Extinguishers as defined in this Performance Work Statement (PWS).

Conform to all federal, state, local requirements, the Air Force Consolidated Occupational Safety Instruction (AFI91-203 para 6), Occupational Safety and Health Administration (OSHA) and applicable manufacture recommendations as required in the PWS. Work must be performed in accordance with (IAW) the current National Fire Protection Association (NFPA) 10 standards, “Portable Fire Extinguishers, for the inspection and maintenance of all types of portable and wheeled fire extinguishers that are on Channel Islands Air National Guard Station (ANGS), California. The Air National Guard shall provide all Halon 1211 fire extinguisher for flight line operations.

1.2. Operational Requirements and Specific Tasks

1.2.1. Period of Performance. Duration for this task is a 30 day period.

1.2.2. Scheduling. The Contractor shall coordinate with the 146th Civil Engineer Squadron (CES) for extinguisher locations and points of contact. The Contractor shall notify the 146 CES before commencing any inspection/maintenance.

1.3. Upgrading Wheeled Extinguishers

1.3.1. Install Down Tube Assembly

The Contractor shall perform the installation in accordance with Technical Exhibit 2, TCTO 13F4-4-501.

1.3.2 Fire Extinguisher Recharging

1.3.2.1. The dry chemical may be reused, provided a closed system is used for emptying and the agent is stored in a sealed container to prevent contamination.

1.3.2.2 Halon 1211 is classified as a Class I Ozone Depleting Chemical. The Government will provide, as Government-furnished material (GFM), all halon required for fire extinguisher maintenance. The Contractor is not allowed to provide halon from its own stock. This contract does not authorize the purchase of halon to charge Air Force fire extinguishers. All halon provided to the Contractor in fire extinguishers or as GFM for fire extinguisher maintenance shall remain the property of the U.S. Government. Furthermore, this contract does not authorize the Contractor to dispose of or claim any “Government-owned” Halon 1211.

1.3.2.3. The Contractor shall return, to the 146 CES, all unused or excess halon. The Contractor shall not dispose of any U.S. Government-owned halon.

Portable & Wheeled Fire Extinguishers 3

1.4. Records Keeping and Documentation. The Contractor shall record on all fire extinguishers, provided by the Government or other automated product that meets the requirement listed in para. 1.3. of this PWS. The Inventory Record consists of a computer-generated listing of the following: all facilities showing each extinguisher type, size, location, serial number, and last inspection date. A copy of this Inventory Record shall be sent, via email, to the 146 CES the same day as invoicing in Wide Area Work Flow (WAWF).

1.5. Reporting. The Contractor shall provide a report (the Service Report and the Halon Report) to the 146 CES.

1.5.1. The Service Report, which is included in the Inventory Records, shall accompany the invoice and shall itemize all services the Contractor performed. This report shall list the following data for each fire extinguisher serviced during the reporting/invoice period.

• Date

• Tracking number or serial number of the fire extinguisher (from Inventory Record)

• Type of service (e.g. initial fill, annual service maintenance, 6-year complete maintenance, 12-year hydrostatic testing, corrective maintenance/recharging, refurbishment, transfer to Government, and salvage preparation)

• Quantity of halon (in pounds) recovered from fire extinguisher prior to servicing (or quantity remaining in fire extinguisher following salvage preparation and/or transfer of the fire extinguisher to Government control)

• Quantity of halon (in pounds) used to recharge fire extinguisher

• Amount returned of halon (in pounds) returned to [state to whom]

SECTION II

SERVICE SUMMARY

The Service Summary is a list of performance objectives and performance thresholds that represent the minimum acceptable level of performance. The performance objectives and thresholds shall be regularly verified by the 146 CES. Each performance objective represents a significant task as identified by the Government at the time of contract award.

These performance objectives and performance thresholds represent only the significant task of this contract and do not excuse the Contractor from performance of other responsibilities identified in this PWS and Section V, Technical Exhibits (TE). Additionally, performance objectives may be added or deleted and performance thresholds raised or lowered during the course of the contract by a modification to the contract.

Performance Ratings: E – Exceptional, VG – Very Good, S – Satisfactory, M - Marginal, U – Unsatisfactory

PERFORMANCE OBJECTIVE PARAGRAPH PERFORMANCE THRESHOLD

1. UPGRADE Wheeled Units

Fire extinguishers are upgraded and recharged IAW manufacturer’s recommendation and NFPA 10 standards. And Technical Exhibit 2.

1.3.1

E: No discrepancies noted during any records or equipment inspections.

VG: No more than one (1) discrepancy noted during any records or equipment inspections.

Portable & Wheeled Fire Extinguishers 4

S: No more than two (2) discrepancies noted during any records or equipment inspections.

M: No more than three (3) discrepancies noted during any records or equipment inspections.

U: > Three (3) discrepancies noted during any records or equipment inspections.

PERFORMANCE OBJECTIVE PARAGRAPH PERFORMANCE THRESHOLD

2. Recharging

Fire extinguishers are recharged IAW manufacturer’s recommendation and NFPA 10 standards.

1.3.2 E: No discrepancies noted during any

records or equipment inspections.

VG: No more than one (1) discrepancy noted during any records or equipment inspections per month.

S: No more than two (2) discrepancies noted during any records or equipment inspections.

M: No more than three (3) discrepancies noted during any records or equipment inspections.

U: > Three (3) discrepancies noted during any records or equipment inspections per month.

3. Record Keeping/Reports:

Submitted within specified time.

1.4; 1.5

E: No discrepancies noted during any records or equipment inspections.

VG: No more than one (1) discrepancy noted during any records or equipment inspections.

S: No more than two (2) discrepancies noted during any records or equipment inspections.

M: No more than three (3) discrepancies noted during any records or equipment inspections.

U: > Three (3) discrepancies noted during any records or equipment inspections.

SECTION III

GOVERNMENT-FURNISHED PROPERTY AND SERVICES

3.1. Government-Furnished Property (GFP). The Government will furnish all fire extinguishers, halon, an area to work in, electricity, water, and sewage service necessary to accomplish the work IAW this contract. The Contractor shall adhere to all base-level utility

Portable & Wheeled Fire Extinguishers 5 conservation practices. The Contractor shall be responsible for operating under conditions that prevent waste of utilities.

SECTION IV

GENERAL INFORMATION

4.1. Hours of Operation. Perform the inspection, pick-up, or delivery of fire extinguishers during the hours of 7:00 a.m. – 4:00 p.m., Monday through Friday, according to the pre-coordinated schedule as prescribed in Section 1, para. 1.2.2. of this PWS.

4.2. Hazardous Waste/Materials

4.2.1. Hazardous Waste. All hazardous waste generated from contract activities shall be disposed of according to all federal and state regulations. The Contractor shall make correct waste determinations for each waste stream. The Contractor shall ensure proper waste packing, labeling, hazardous waste manifesting, and transport from accumulation site to ultimate disposal. Ensure the waste goes to a properly permitted treatment/disposal facility and that all manifests and any other required documentation are available to the 146 CES Environmental Flight before submittal of invoice. Pay all costs associated with hazardous waste management and disposal. Any and all fines/penalties assessed by state, local or federal agencies for hazardous waste laws violated shall be paid by the Contractor. Contact the 146 CES Environmental Flight immediately at (805) 986-7839 upon hazardous waste generation.

4.2.2. Hazardous Materials. In the accomplishment of this contract, non-flammable, environmentally-friendly, biodegradable products IAW Air Force Instruction (AFI) AFI 32-7086, Hazardous Materials Management, Chapter 2.5.5, found in Section V-TE-2 must be used.

Submit AF Form 3952; “Chemical/ Hazardous Material Request Authorization” and the manufacturer’s “Safety Data Sheet (SDS)”, to the 146 CES Environmental Flight for all chemicals used on Channel Islands ANGS within two (2) weeks of contract award and within two (2) weeks after any new chemicals are purchased for use under this contract. No chemicals shall be used on Channel Islands ANGS prior to obtaining this approval. No chemicals shall be stored on Channel Islands ANGS. The Contractor shall contain, handle, and cleanup all spills from this operation. Cost to dispose of spilled materials, and any other waste items resulting from a spill, is the responsibility of the Contractor. All spills, leaks, and inadvertent releases of hazardous materials shall immediately be reported to the 146 Base Defense Operations Center (BDOC) at (805) 986-7440.

4.3. Contractor Qualification/Experience. For the life of the contract, a trained and certified person(s) who has undergone the factory training and certification for the specific type and brand of portable and wheeled-type fire extinguishers being to reliably perform inspections; or certification by an organization acceptable to the authority having jurisdiction; or registration, license or certification by the state or local authority having jurisdiction; and IAW NFPA 10, to maintain, service, and recharge all portable and wheeled fire extinguishers. Provide certificate(s) upon request. The certified person(s) shall have available the appropriate manufacture’s service manual(s), the proper types of tools, recharge materials, lubricants, and

Portable & Wheeled Fire Extinguishers 6 manufacturer’s recommended replacement parts or parts specifically listed for use in the fire extinguisher and IAW with NFPA 10.

4.3.1. Contractor Employees. Do not employ persons for work on this contract if such employee is identified to the Contractor as a potential threat to the health, safety, security, or operational mission of the installation and its population.

4.3.2. Present a neat appearance and be easily recognized as Contractor employees.

Identification of all employees shall be accomplished by wearing badges and by Contractor-provided distinctive clothing bearing the name of the Contractor. A Government-issued identification badge shall be worn visibly at all times.

4.4. Security Requirements for Channel Islands ANGS. Comply with all Channel Islands ANGS security requirements imposed by the installation commander at all times while on the premises to include not using cell phones while operating a vehicle on base. Obtain necessary access privileges required to enter Channel Islands ANGS. The contractor’s employees shall become familiar with and obey the regulations of the installation; including fire, traffic, safety and security regulations while on the installation. Contractor employees shall only enter restricted areas when required to do so and only upon prior approval. All contractor employees shall carry proper identification with them at all times. The contractor shall ensure compliance with all regulations and orders of the installation which may affect performance.

4.4.1. Contractor’s List. Requests for access to Channel Islands ANGS shall be submitted to the 146 CES no later than ten (10) days prior to the work start date. Requests shall be submitted on company stationery; include address, telephone number, and contract number.

The request shall also include a list of all employees requiring access to Channel Islands ANGS, along with their full legal name, social security number, date of birth, and place of birth.

When new employees require access to Channel Islands ANGS, an updated employee list must be sent to the 146 CES.

4.4.1.1. Identification Badges. All Contractor personnel shall wear identification badges with a minimum of the Contractor’s name and the employee’s last name. Identification on the badge shall be readily discernible from a distance of five feet. Identification badges worn shall indicate their job title. In addition, security passes will be required to enter and leave the post and must be safeguarded and turned in on the last day of this contract after cleaning.

4.4.2. Vehicle Requirements. Proper state vehicle registration, proof of insurance, and a valid driver’s license are required to drive onto Channel Islands ANGS. .

4.5. Quality Assurance. The Government will evaluate the Contractor’s performance under this contract through on-site inspections and customer complaints. 146 CES inspectors will routinely perform quality checks during their scheduled and unscheduled building inspections.

4.6. CONTRACTOR MANPOWER REPORTING (CMR): The contractor shall report ALL contractor labor hours (including subcontractor labor hours) required for performance of services provided under this contract for the Air Force collection site. The contractor is required

1393800417N Cross-Out

Portable & Wheeled Fire Extinguishers 7 to completely fill in all required data fields using the following web address:

http://www.ecmra.mil/. Reporting inputs will be for the labor executed during the period of performance during each Government fiscal year (FY), which runs October 1 through September 30. While inputs may be reported any time during the FY, all data shall be reported no later than October 31 of each calendar year. Contractors may direct questions to the help desk at http://www.ecmra.mil/.

Unit Identification Code (UIC) for the Requiring Activity: F8S3CC Issuing Office DoDAAC: W912LA

4.7. Fire hoses and extinguishers shall not be moved or used for any purpose other than firefighting. Smoking is strictly prohibited in any federal facility or near flammables. The Contractor shall notify 146 CES of any utility outage that might affect fire suppression or detection systems. Prior to leaving the work site at the end of each day, the Contractor shall ensure the area is left in a fire safe condition. Bulk storage of gasoline and burning of any materials is strictly prohibited.

4.9. Welding, Cutting, or Flame Operations. Any welding, cutting, or open flame operations will require the Contractor to secure a welding permit. Contact the 146 CES Production Control on procedures on obtaining a permit at (805) 986-7860.

5.0. Toilet Facilities. Public toilet facilities available in the vicinity of the work site may be used by Contractor’s personnel.

5.1. Equipment, Machines, and Tools. All equipment, machines, and tools used the performance of the work shall be approved and maintained in satisfactory operating condition, and used in the manner that the tool was designed to be used for.

5.2. Conflict of Interest. The Contractor shall not employ any person who is an employee of the United States Government or Department of Defense, military or civilian, if the employment of that person would create, or appear as, a conflict of interest, as defined in DOD 5500.7-R Joint Ethics Regulation.

5.3. Use of Alcoholic Beverages/Drugs. The use of alcoholic beverages or illegal drugs by Contractor personnel, while on duty, is strictly forbidden. The Contractor shall immediately remove and replace employees who are under the influence of alcohol or drugs.

5.4. Fire Prevention. The Contractor shall report any fire, no matter how small, by dialing 911.

5.5. Emergency Medical Treatment. Government furnished medical service is not available to Contractor personnel. Contractor is responsible to ensure employees are provided medical care in the local community.

5.5.1. Accident/Injury Reporting. Immediately upon the occurrence of a job-related injury, the Contractor shall notify the 146 CES.

1393800417N Cross-Out

Portable & Wheeled Fire Extinguishers 8

5.6. Fraud, Waste & Abuse. The Contractor shall immediately notify Government personnel of any instance of suspected waste, fraud, abuse, or theft of Government Furnished Property by employees or Sub-Contractors.

SECTION V

TECHNICAL EXHIBITS (TE)

6.1. Technical Exhibit 1 – Government-Furnished Property/Equipment Services (attached)

6.2. Technical Exhibit 2 – TCTO 13F4-4-501 (attached)

6.3. After award, the following will be provided:

a. Base Map

b. AF Form 3952 - Chemical/Hazardous Material Request Authorization SDS form(s)

Portable & Wheeled Fire Extinguishers 9

TECHNICAL EXHIBIT 1

GOVERNMENT-FURNISHED PROPERTY/EQUIPMENT SERVICES

ITEM TYPE EXTINGUISHER SERVICE REQUIRED ESTIMATED

QUANTITY

2 150 lbs. Halon

Extinguishers (wheeled) Upgrade IAW Technical Exhibit 2 & Recharge

Portable & Wheeled Fire Extinguishers 10

TECHNICAL EXHIBIT 2

TCTO 13F4-4-501

(Next 6 Pages)

CUI

DEPARTMENT OF THE AIR FORCE

TECHNICAL ORDER

INSPECTION OF THE DOWN TUBE AND VALVE

ASSEMBLY SOLDER ON AMEREX HALON 1211 150Lb

WHEELED FLIGHTLINE FIRE EXTINGUISHER

NOTE

Commanders are responsible for bringing this technical order to the attention of all Air Force personnel cleared for operation of affected systems.

In accordance with TO 00-5-15, all affected Wheeled Flightline Fire Extinguishers that are in non-compliance by the compliance date of this TCTO will be removed from service. Extensions will only be granted on a case-by-case basis. The local/host Mission Support Group Commander (or equivalent) must submit requests for extensions via the owning MAJCOM to WR-

ALC/WNZ.

Requests must include the justification or extension, and expected date the extinguisher will be in full compliance.

This is an AFLCMC/WNZ TCTO. POC at AFLCMC/WNZ is Willie Edwards, DSN 468-6462.

1. APPLICATION.

1.1 Identification. This Time Compliance Technical Order (TCTO) is applicable to the

AMEREX, HALON 1211 150 LB Wheeled Flightline Fire Extinguisher (WFFE), Model 600.

NSN 4210-01-140-2233, NSN 4210-01-332-0793 and NSN 4210-01-457-9062.

1.2 Kit Applicability by Model and Serial Number. Not Applicable.

1.3 Verification. TCTO verification was accomplished in accordance with TO 00-5-15, at Ellsworth AFB, SD and Wright Patterson AFB, OH, on Class A Mishap AFSAS #983980, 15 September 2020.

2. PURPOSE.

The purpose of this Time Compliance Technical Order (TCTO) is to perform a One-Time Visual Inspection on the solder quality found at the joint connecting the Down Tube and Valve Assembly. Note in mid-2006 the manufacturer changed the material used in the Down Tube from Copper to Stainless Steel.

DISCLOSURE NOTICE: This information is furnished upon the condition that it will not be released to another nation without the specific authority of the Department of the Air Force of the United States, that it will be used for military purposes only, that individual or corporate rights originating in the information, whether patented or not, will be respected, that the recipient will report promptly to the United States, any known or suspected compromise, and that the information will be provided substantially the same degree of security afforded it by the Department of Defense of the United States. Also, regardless of any other markings on the document, it will not be downgraded or declassified without written approval of the originating United States agency.

TCTO: 13F4-4-501

DATA CODE: 1300051

DATE: 20210312

RESCISSION DATE: 20220301

1174670621N Text Box "WORKING COPY/DESTROY WHEN COMPLETE" TO: MXOOP, MXQ, Flightline

1174670621N Text Box

APPLICABLE

1174670621N Text Box

DATE RECEIVED:

7 APR 2021

DISTRIBUTION STATEMENT A - Approved for public release; distribution is unlimited. Other requests for this document shall be referred to 406 SCMS/GUEE, Robins AFB, GA 31098. Questions concerning technical content shall be referred to AFLCMC/WNZ.

HANDLING AND DESTRUCTION NOTICE: Comply with distribution statement and destroy by any method that will prevent disclosure of contents or reconstruction of the document.

3. WHEN TO BE ACCOMPLISHED.

3.1 Compliance Period. Work shall be accomplished not later than 180 days after receipt of this TCTO. Failure to accomplish the work by the expiration of compliance period shall be justification for withdrawing the affected system/equipment from service until compliance is accomplished. If the compliance period cannot be met before the TCTO rescission date, the performing organization will request an extended compliance period according to TO 00-5-15.

3.2 TCTO Rescission Date. The TCTO rescission date is 01 Mar 2022, unless extended via TCTO supplement or notices received through the Reliability and Maintenance Information System (REMIS) or other Management Information Systems. TCTOs will be retained until listed as rescinded in the applicable index.

4. BY WHOM TO BE ACCOMPLISHED.

Maintenance, servicing, and recharging shall be performed by trained persons having available the appropriate servicing manual(s), the proper types of tools, recharge materials, lubricants, and manufacturer’s recommended replacement parts. If these conditions cannot be met, all Wheeled Flightline Fire Eextinguisher’s within compliance of maintenance standards will be sent to a local Amerex Distributor (https://www.amerex-fire.com/distributors/find-a-distributor/).

If maintenance is to be performed by contract, the contractor must perform all maintenance and inspections using technical manual 13F4-4-121 or appropriate vendor’s commercial manual.

5. WHAT IS REQUIRED.

5.1 Supply Information and Requirements. Not Applicable

5.2 Personnel Information and Requirements.

Work Phases Man-Hours

Inspection 1.0

Removal/Replacement of Down Tube and Valve Assembly

1.0

Total Man-Hours 2.0

6. HOW WORK IS ACCOMPLISHED. (Refer to TO 13F4-4-121, Chapter 5 prior to doing any work)

Controlled by: AFLCMC/WNZD CUI Category: Controlled Technical Information Distribution/Dissemination Control: A POC: Willie Edwards DSN: 468-6462 https://www.amerex-fire.com/distributors/find-a-distributor/

Before attempting to de-valve the extinguisher, be sure that it is completely depressurized. Never have any part of your body over the extinguisher while removing the valve assembly. Failure to comply could result in injury to, or death of, personnel or long term health hazards.

Halon 1211 should not be mixed with even the slightest amount of moisture. Prolonged exposure of a de-valved cylinder to ambient air should be avoided to prevent moisture contamination.

NOTE

Halon agent removed from an extinguisher at the time of maintenance or recharging shall be placed in a separate recovery cylinder and the extinguisher cylinder examined internally for contamination. The Halon agent, retained in the recovery cylinder, may be reused only if no evidence of internal contamination is observed in the extinguisher cylinder. Halon removed from extinguishers that exhibit evidence of internal contamination or corrosion shall be processed in accordance with the extinguisher manufacturer’s instructions.

6.1 Use instruction (5.4 COMPLETE MAINTENANCE) from TO 13F4-4-121 to discharge the valve assembly and remove the down tube from the cylinder assembly.

6.2 Once the down tube has been removed, use the inspection criteria below.

a. Visual inspection should ensure solder joint is fully penetrated by solder. A good solder joint will have a completely full solder bead all the way around the tube/valve joint and form a “fillet” between the valve and the down tube. This bead will be fully filled around the circumference with no gaps. (Refer to Fig 1-1)

Figure 1-1

b. A suspect joint will have pits, voids, and valleys in the joint. If a visible gap (lack of solder) is found between the Retainer and Down Tube interface (Figure 1-2 & 1-3), replace downtube/retainer assembly with approved Amerex manufacturer part (P/N:

04938).

Figure 1-2 Figure 1-3

7. SUPPLEMENTAL INFORMATION.

7.1 Fuel System Defuel/Purge. Not Applicable

7.2 Operational Checkout Requirements. Not Applicable

7.3 Weight and Balance Information. Not Applicable

7.4 Technical Manuals Affected.

TO NUMBER DATE OF BASIC ISSUE

13F4-4-121 02 DEC 2018

8. RECORDS.

8.1 Action Required on Maintenance Records.

a. Upon completion of TCTO, update applicable Model 600 Fire Extinguisher AFTO 244 and maintenance data collection systems in accordance with command directives. Update IMDS or REMIS using the following data.

b. Action Required on Supply Records. Not Applicable

c. Retrofit Change or Inspection Identification Marking. Not Applicable

d. Item requiring TCTO accomplishment

8.2 Action Required on Supply Records. Not Applicable

8.3 Retrofit Change or Inspection Identification Marking.

Completion of the down tube inspection will be represented by the decal provided below stating the “The TCTO Number and TCTO Completion Date”. Per the standard, a decal is used to avoid corrosion that a stamp would cause. This page can be printed out and (Figure 1-4) can be cut out and used to create a decal once filled out. After the data for TCTO # and Date Completed is written in, apply clear tape to the front and back of the paper to laminate it. Placement for the decal will be on the right-hand side of the discharge valve. (Figure 1-5) Apply clear epoxy (NSN: 8040-01-628-6226) over the decal, to seal it from the elements. (Figure 1-6)

Figure 1-4 Figure 1-5 Figure 1-6

9. POINT OF CONTACT.

The Technical Content Manager (TCM) POC for this TCTO is Willie Edwards, AFLCMC/WNZ, willie.edwards@us.af.mil, DSN 468-6462. Engineering POC is Chris Peisher, AFLCMC/WNZ, christopher.peisher@us.af.mil, DSN 472-1371.

THE END

BY ORDER OF THE SECRETARY OF THE AIR

FORCE

CHARLES Q. BROWN, GENERAL, USAF

Chief of Staff

ROBERT D. MCMURRY, LIEUTENANT GENERAL, USAF

Commander, AFMC

Prepared by AFLCMC/WNZ DSN 468-6462

PWS_Upgrade Wheeled Extinguishers
PERFORMANCE WORK STATEMENT
FOR
HYDROSTATIC TESTINGUPGRADING FOR WHEELED FIRE EXTINGUISHERS
ON CHANNEL ISLANDS AIR NATIONAL GUARD STATION, CA
13F4-4-501.pdf
COVER