Pricing_Schedule.pdf
PDF 111 KB Posted
- Attached to
- Geothermal Units - FOSM Federal contract opportunity
- Solicitation number
- P15PS01028
About this file
Attachment 1 - Pricing Schedule
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_P15PS01028_Amd_000001.pdf | ||
| Visitor_Center_HVAC_Location_Map.pdf | ||
| WageDetermination.pdf | ||
| Sol_P15PS01028.pdf | ||
| SOWGeothermalFOSM.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P15PS01028 Attachment 1 – Geothermal -FOSM Page 1 of 7
Pricing Schedule
Submit pricing for all items. In case of error in the extension of prices, unit price governs. In case of error in summation, the total of the corrected amounts governs. FOB for all items is “Destination”. Include are shipping, assembling, etc. charges in your unit price. The installation price includes all that is needed to bring unit to full operation to include on-site training.
Item Description QTY Unit Unit Cost
Total
10 Energy Star Rated high efficiency; 20-ton water source heat pump, vertical configuration, 208-230/60/3 (Volt/HX/Phase), ETL and CSA agency listing, front piping, left return arrangement, condensate overflow fault sensor, motor blower, low pressure switch, in line return air temperature sensors, factory wired components, low temp sensor, Energy Efficiency Ratio (EER) 17.1 or better, Coefficient of Performance (COP) of 3.6 or better. Supply air duct measurements: 18” x 46”, return air duct measurements; 55” x 58”
1 EA
20 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 10.
1 JB
30 Energy Star Rated high efficiency; 25-ton water source heat pump, vertical configuration, 208-230/60/3 (Volt/HX/Phase), ETL and CSA agency listing, front piping, right return arrangement, condensate overflow fault sensor, motor blower, low pressure switch, in line return air temperature sensor, factory wired components, low temp sensor, Energy Efficiency Ratio (EER) 17.1 or better, Coefficient of Performance (COP) of 3.6 or better. Supply Air Duct Measurements; 19” x 41”, Return Air Duct Measurements; 34” x 52”
40 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 30.
1 JB
P15PS01028 Attachment 1 – Geothermal -FOSM Page 2 of 7
50 Energy Star Rated high efficiency; 1.5-ton water source heat pump, vertical configuration, 208-230/60/1 (Volt/HX/Phase), ETL and CSA agency listing, front piping, left return arrangement, condensate overflow fault sensor, motor blower, low pressure switch, inline return air temperature sensor, factory wired components, low temp sensor, Energy Efficiency Ratio (EER) 17.1 or better, Coefficient of Performance (COP) of 3.6 or better. Supply Air Duct Measurements; 10” x 10”, Return Air Duct Measurements; 16” x 24”
60 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 50.
1 JB
70 Energy Star Rated high efficiency; 1.5-ton water source heat pump, vertical configuration, 208-230/60/1 (Volt/HX/Phase), ETL and CSA agency listing, front piping, left return arrangement, condensate overflow fault sensor, motor blower, low pressure switch, inline return air temperature sensor, factory wired components, low temp sensor, Energy Efficiency Ratio (EER) 17.1 or better, Coefficient of Performance (COP) of 3.6 or better. Supply Air Duct Measurements; 9” x 10”, Return Air Duct Measurements; 16” x 24”
80 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 70
1 JB
90 Energy Star Rated high efficiency; 1.5-ton water source heat pump, vertical configuration, 208-230/60/1 (Volt/HX/Phase), ETL and CSA agency listing, front piping, left return arrangement, condensate overflow fault sensor, motor blower, low pressure switch, inline return air temperature sensor, factory wired components, low temp sensor, Energy Efficiency Ratio (EER) 17.1 or better, Coefficient of Performance (COP) of 3.6 or better. Supply Air Duct Measurements; 11” x 11”, Return Air Duct Measurements; 16” x 25”
P15PS01028 Attachment 1 – Geothermal -FOSM Page 3 of 7
100 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 90.
1 JB
110 Energy Star Rated high efficiency; 3.5-ton water source heat pump, vertical configuration, 208-230/60/3 (Volt/HX/Phase), ETL and CSA agency listing, front piping, left return arrangement, condensate overflow fault sensor, motor blower, low pressure switch, inline return air temperature sensor, factory wired components, low temp sensor, Energy Efficiency Ratio (EER) 17.1 or better, Coefficient of Performance (COP) of 3.6 or better. Supply Air Duct Measurements; 16” x 17” Return Air Duct Measurements; 20” x 38”
120 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 120.
1 JB
130 Energy Star Rated high efficiency; 10-ton water source heat pump, vertical configuration, 208-230/60/3 (Volt/HX/Phase), ETL and CSA agency listing, front piping, right return arrangement, condensate overflow fault sensor, motor blower, low pressure switch, inline return air temperature sensor, factory wired components, low temp sensor, Energy Efficiency Ratio (EER) 17.1 or better, Coefficient of Performance (COP) of 3.6 or better. Supply Air Duct Measurements; 22” x 15”, Return Air Duct Measurements; 35” x 40”
140 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 130.
1 JB
150 Energy Star Rated high efficiency; 2.5-ton water source heat pump, vertical configuration, 208-230/60/3 (Volt/HX/Phase), ETL and CSA agency listing, front piping, left return arrangement, condensate overflow fault sensor, motor blower, low pressure switch, inline return air temperature sensor, factory wired components, low temp sensor, Energy Efficiency Ratio (EER) 17.1
P15PS01028 Attachment 1 – Geothermal -FOSM Page 4 of 7 or better, Coefficient of Performance (COP) of 3.6 or better. Supply Air Duct Measurements; 11” x 12”, Return Air Duct Measurements; 18” x 30”
160 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 150.
1 JB
170 Energy Star Rated high efficiency; 8-ton water source heat pump, vertical configuration, 208-230/60/3 (Volt/HX/Phase), ETL and CSA agency listing, front piping, left return arrangement, condensate overflow fault sensor, motor blower, low pressure switch, inline return air temperature sensor, factory wired components, low temp sensor, Energy Efficiency Ratio (EER)
17.1 or better, Coefficient of Performance (COP) of 3.6 or better. Supply Air Duct Measurements; 16” x 21” Return Air Duct Measurements; 38” x 40”
180 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 170.
1 JB
190 Energy Star Rated high efficiency; 6-ton water source heat pump, vertical configuration, 208-230/60/3 (Volt/HX/Phase), ETL and CSA agency listing, front piping, right return arrangement, condensate overflow fault sensor, motor blower, low pressure switch, inline return air temperature sensor, factory wired components, low temp sensor, Energy Efficiency Ratio (EER) 17.1 or better, Coefficient of Performance (COP) of 3.6 or better. Supply Air Duct Measurements; 13” x 13”, Return Air Duct Measurements; 41” x 28”
200 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 190.
1 JB
210 Energy Star Rated high efficiency; 4-ton water source Heat Pump, horizontal configuration, 208-230/60/3 (Volt/HX/Phase), ETL and CSA agency listing, front piping, left return
P15PS01028 Attachment 1 – Geothermal -FOSM Page 5 of 7 arrangement, condensate overflow fault sensor, motor blower, low pressure switch, inline return air temperature sensor, factory wired components, low temp sensor, Energy Efficiency Ratio (EER) 17.1 or better, Coefficient of Performance (COP) of 3.6 or better. Supply Air Duct Measurements; 12” x 15”, Return Air Duct Measurements; 20” x 38”
220 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 210.
1 JB
230 Energy Star Rated high efficiency; water source heat pump. NOTE: Heat Pump is currently a 2.5-ton water source heat pump and short-cycles due to the unit being oversized. A new heat pump needs to be evaluated and sized accordingly.
New heat pump must meet the parameters set forth on the current system layouts as well as meet the Energy Efficiency Ratio (EER) and Coefficient of Performance (COP) of similar new heat pumps. Supply Air Duct Measurements; 12” x 15”, Return Air Duct Measurements; 20” x 38”
240 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 230.
1 JB
250 High efficiency 208/60/3 (Volt/HX/Phase),
7.5 HP / 1760 RPM, 7.7” Impeller, F.L.
Amps / S.F. 20 / 1.15, Ceramic Sealed, 225- 230 GPM, ground loop heat/water pumps.
2 EA
260 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 250.
1 JB
270 New adjustable speed drive controllers.
VFD’s operate pumps: 1 to 400 HP, 2.2 to 250 kW, 460 V 1 to 50 HP, 2.2 to 37 kW, 23V adjustable frequency AC drive controllers capable of controlling either constant or variable torque loads and designed to handle simple or complex applications, functioning as a stand-alone drive controller or part of a complex drive system.
2 EA
P15PS01028 Attachment 1 – Geothermal -FOSM Page 6 of 7
280 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 270.
1 JB
290 Building Automation Control BACnet System. BACnet is a communications protocol for building automation and control networks. New system must be ASHRAE, ANSI, and ISO standard and be a system that has been in the commercial industry for a minimum of 10 years (Alteron, Honeywell, TRANE, etc.) along with local service provider support capable of providing warranty and on-site tech support. New system be compatible with current controls, modules, etc., and have at a minimum:
Capable of time of day scheduling Timed override Custom programming Routines Zone Control Priority Control Global Binary Input/output points Global Analog Input/output points Custom Status Displays Trend Log History Humidity Trend Log Report Event Log Data Monthly Custom Reporting Daily Summary Reporting Weekly Temperature Report Input / Output Status Report Multiple Unit Manager System Web based Smart Phone App Control Capability.
300 Services Nonpersonal: Provide all necessary labor, parts, equipment, facilities and transportation necessary for the installation, training and startup of the equipment in items 290.
1 JB
310 Flush and fill geothermal system with new antifreeze in geothermal loop system.
Contractor to verify quantity of antifreeze/water solution in current system. System to be re-filled according to manufacturer’s recommendation to support new loop circuit.
1 JB
310A Alternative to Item 310 using sustainable glycol or antifreeze that will meet the manufacturer’s recommendation and warranty requirements. This would be the
P15PS01028 Attachment 1 – Geothermal -FOSM Page 7 of 7 cost (decrease or increase in cost) if a viable alternative is available and will not void the manufacturers warranty.
320 Replace current self-balancing hose kits for each current water source heat pumps with in kind or approved equal kits.
330 Remove and replace 6” O.D. one way supply water flow valves located at ground loop water/heat pumps (one for each pump) and replace with new to match existing supply piping and accommodate flow and volume of new pump units.
340 Replace current auto-flow valves with in-kind or approved equal auto-flow valve.
GRAND TOTAL
Pricing Schedule
File details come from the government source that posted it. Updated .