Statement of Work (SOW)
The Naval Air Warfare Center Aircraft Division (NAWCAD), Lakehurst in support of the Prototype, Manufacturing, and Test Division is seeking sources that can provide a Combustible Powder Storage
Container for the Advanced Manufacturing and Prototype Engineering Branch. Scope of work as follows:
1. Scope
1.1 Purpose
The purpose of this Statement of Work (SOW) is to identify the requirements for a combustible powder storage container which will house the branches supply of combustible metal powder. The container will be placed on a concrete pad at the location outlined below. The concrete pad will be installed by a separate vendor.
2 Requirements
2.1 Dimensions
The storage container shall be approximately 26 feet long by 8 feet wide by 8 feet tall.
2.2 Fire Rating
The storage container shall be 4-hour fire rated.
2.3 Fire Suppression System
The storage container shall have a Class D dry chemical fire suppression system. The design of this system shall be one of the following, with the first being priority:
1. Automatic fire detection and suppression system capable of detecting a fire and releasing the Class D dry chemical fire suppression material within the storage container in accordance with applicable fire and safety standards
2. Placement of manually operated Class D fire extinguishers inside/outside the storage container in accordance with applicable fire and safety standards
2.4 Fire Alarm
The storage container shall have a remote fire alarm capable of detecting a fire, producing an audible alarm, and relaying the alarm status to the on-base fire station.
2.5 Temperature Controls
The storage container shall have environmental controls capable of heating and cooling to maintain a consistent adequate temperature inside.
2.6 Interior Lighting
The storage container shall have interior lighting bright enough to safely facilitate normal working conditions. Conditions include, but are not limited to, reading and writing, lifting, stacking, and moving powder containers.
2.7 Electrical
The storage container shall be able to receive 100 Amp, 208y/120v, 3 phase power to power all subsystems including but not limited to the fire alarm system, environmental controls, and lighting.
2.8 Shelving/Cabinets
The storage container shall facilitate optimal storage of powder canisters containing different metal powders. Each powder canister measures a maximum of 11 inches in diameter by 10 inches tall. The storage container shall be able to store a maximum of
5000lbs of powder. The design shall be one of the following:
1. 3 tiers of shelves, the layout of which shall maximize the total amount of shelf space and include designated shelving for each type of metal powder
2. OSHA & NFPA rated high visibility flammable storage cabinets, the layout of which shall maximize the total amount of cabinet space and include designated cabinets for each type of metal powder
2.9 Door and Ramp
The exterior door of the storage container and ramp leading up to it must be able to accommodate a hand cart with a width of 30 inches and a height of 40 inches.
2.10 Signage
The storage container shall have signage on at least two sides detailing the general contents of the storage container, the hazardous nature of those contents, and the use of Class D fire extinguishers should a fire occur.
2.11 Location
The vendor shall place and install the storage container on a pre-constructed concrete pad with dimensions 24” wider and 24” longer than the storage container. The location will be determined by the NAWCAD Advanced Manufacturing & Prototype
Manufacturing Branch
2.12 Technical Data
The vendor shall include drawings and technical data to facilitate the short and long term installation and maintenance of the storage container.
2.13 Freight Charge
The vendor shall include the freight and installation charge of the storage container for delivery to Highway 547 Joint Base MDL Lakehurst NJ 08733.