Attachment_1_N2_TANK_RENTAL.doc
DOC document 36 KB Posted
- Attached to
- Liquid Nitrogen Tank Rental Federal contract opportunity
- Solicitation number
- N39040-16-T-0166
About this file
Attachment 1
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| RFQ_N39040-16-T-0166.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REQ DOC NO. -
6088V040
| ATTACHMENT |
| 1 |
CONTINUATION SHEET
CONTRACT NO. –
| N39040-16-P-0166 |
| PAGE |
| 1 |
| OF |
| 2 |
NAME OF OFFEROR/CONTRACTOR
ITEM #
SUPPLIES/SERVICES
QTY
U/I
| SERVICE |
| 1 |
JO
C. DESCRIPTION/SPECIFICATIONS.
C.1 RENTAL OF TWO (2) 1500 GALLON LIQUID NITROGEN TANKS WITH ATTACHED VAPORIZER PER ATTACHMENT 1 TECHNICAL REQUIREMENTS.
THE EQUIPMENT SHALL BE DELIVERED IN FIRST CLASS OPERATING CONDITION WITH COMPLETE OPERATING INSTRUCTIONS.
THE CONTRACTOR SHALL MAINTAIN A STRINGENT MAINTENANCE PROGRAM AND SHALL BE RESPONSIBLE FOR ALL REPAIRS AND MAINTENANCE FOR THE DURATION OF THE RENTAL.
THE CONTRACTOR SHALL PROVIDE SERVICE WITHIN EIGHT (8) HOURS AFTER NOTIFICATION BY THE CONTRACTING OFFICER OR REPRESENTATIVE. IN THE EVENT THE CRYOGENIC STORAGE TANK CANNOT BE RETURNED TO SERVICE WITHIN TWENTY-FOUR (24) HOURS OF NOTIFICATION, A REPLACEMENT SHALL BE DELIVERED AT NO EXTRA CHARGE TO THE GOVERNMENT.
THE CONTRACTOR SHALL BE RESPONSIBLE FOR EQUIPMENT FAILURE NOT ARISING OUT OF ABUSE OR NEGLEGENCE BY THE GOVERNMENT.
EQUIPMENT REQUIRED FROM 5/1/2016 TO 4/1/2018 WITH POTENTIAL TO EXTEND.
C.2 C528 SPECIFICATION CHANGES.
C.3 C500 MERCURY CONTROL.
D. PRESERVATION/PACKAGING/PACKING.
D.1 D4 PREPARATION FOR DELIVERY (COMMERCIALLY PACKAGED).
E. INSPECTION AND ACCEPTANCE.
E.1 E2 INSPECTION AND ACCEPTANCE (DESTINATION).
E.2 G505 VENDOR DISPOSITION OF NON-CONFORMING MATERIAL.
The rental agent shall provide that each liquid nitrogen storage tank shall have the following minimum attributes:
A cryogenic storage tank of either vertical or horizontal configuration with:
(1) Capacity to store 1500 gallons (U.S.) of liquid nitrogen.
(2) A maximum operating pressure (inner vessel) of 250 PSIG.
(3) An external tank mounted atmospheric vaporizer with a capacity to provide up to 2000 SCFH of nitrogen gas and associated components.
(4) A pressure building coil and regulator circuit and associated components.
(5) An economizer regulator circuit and associated components.
(6) A standard 1-½” fill connector with a 1” bottom fill valve and a 1” top fill valve. Fill line required to be elevated and secured to frame.
(7) A check valve in the fill line.
(8) A ¾” or 1” liquid withdrawal valve.
(9) A ¾” or 1” vent blowdown valve.
(10) A full trycock valve.
(11) A liquid level gauge reading in inches of water with a corresponding chart indicating the liquid content of the tank in gallons (chart for liquid nitrogen at –320 degrees F / 250 psig max operating pressure).
(12) A tank pressure gauge to indicate inner vessel pressure in PSIG.
(13) At least one tank safety pressure relief valve to protect the inner vessel (two preferred) that is/are stamped with date code within 5 years of date for projected use.
(14) A tank safety rupture disc to protect the inner vessel.
(15) Thermal safety valves at all points where liquid nitrogen might be isolated between shut-off valves.
(16) A vacuum isolation valve.
(17) A vacuum thermocouple isolation valve and thermocouple electrical connector.
(18) A vacuum of 100 microns or less at time of delivery.
(19) A schematic diagram of the tank identifying all components.
(20) A permanent ID tag attached to each component corresponding to the schematic diagram.
(21) A permanent tag attached to each pressure relief device indicating the set pressure in PSIG, the date the device was tested or installed and the agency or company that performed the test.
(22) Each tank shall be a new or re-manufactured unit in excellent operating condition capable of immediate operation upon delivery. Tanks may be delivered in a dry or pre-chilled condition.
(23) Orifices/openings capped for delivery following visual inspection indicating no grease, oil, or foreign particles present.
(24) Owners manual OR provide schematic with valve designation.
(25) Shipyard will provide tank off load capability but requires a two day notice of delivery to the Shipyard point of contact.
(26) Each tank shall be clearly marked with the applicable contract number and contract expiration date in letters/numbers a minimum of 2” high. All invoices forwarded to Portsmouth Naval Shipyard for payment shall include the applicable contract number.
File details come from the government source that posted it. Updated .